Permit Application Status

PRRES20162560


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20162560
Building Permit - Residential
Certificate of Occupancy
SILVERSTONE DEVELOPMENT LLC
NEW SINGLE FAMILY
NEW HOUSE WITH COVERED DECK
10/05/2016
10/11/2016
06/06/2017
Locations
Contacts
SILVERSTONE DEVELOPMENT LLC, Address:PO BOX 219119  
MCGRAW HOMES INC, Address:902 SE WILLOW PL, Phone:(816) 985-6909  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 10/07/2016 10/11/2016
Development Center
Plot Plan Review (P&D) Approved 10/07/2016 10/06/2016
Hector Soto Jr.
Plot Plan Review Approved 10/07/2016 10/06/2016
James Fletchall
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,103.18 $1,103.18 Paid 10/11/2016
Right of Way Permit Fee $75.00 $75.00 Paid 10/11/2016
Water Tap Fee $3,310.00 $3,310.00 Paid 10/11/2016
Water Meter Fee $405.36 $405.36 Paid 10/11/2016
8331507-Sewer Connection Fee $540.00 $540.00 Paid 10/11/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Not Ready 10/13/2016 (4:30) 10/13/2016 10/13/2016
Footing Inspection - Residential Passed 10/14/2016 10/14/2016 10/14/2016
Underslab Plumbing Inspection - Residential Passed 11/17/2016 11/17/2016 11/17/2016
Erosion Control Inspection Residential Failed 11/17/2016 11/17/2016
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
11/17/2016
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Sewer Service Inspection - R Passed 1/17/2017 (1:00) 1/17/2017 01/17/2017
Water Service Inspection - R Passed 1/17/2017 01/17/2017
Gas Service Inspection - Residential Passed 3/7/2017 3/7/2017 03/07/2017
Electrical Service Inspection Passed 3/7/2017 3/7/2017 03/07/2017
All Rough Inspection - Residential Failed 3/7/2017 3/7/2017 03/07/2017
Misc
Corrective Action Required
03/07/2017
FRAMING: -SHALL SHIM GAPS UNDER ALL STUDS IN GARAGE -NAIL WALL INTERSECTION AT MASTER CLOSET/TOILET WALL -INSTALL HANGERS AND NAIL ABOVE MASTER SHOWER -PROVIDE FULL SUPPORT TO I BEAM UNDERNEATH TWO POINT LOADS AT MASTER SHOWER WALL -FIREBLOCK FIREPLACE SPACE AT WALL WITH 3/4" SHEATHING -BRACE 3X LVL BEAM (ABOVE GREAT RM) ENDS FROM ROTATION -SUPPORT HIP&VALLEY ABOVE 3X LVL BEAM (ABOVE GREAT RM) -FRONT BED: FRAME THE HIP SUPPORT PER 4/S2 DETAIL; THE FRONT CLOSET WALL IS NOT A BEARING WALL -SEAL CEILING JOIST RETURN AIR SPACE PENETRATIONS ABOVE BASEMENT -AT THE TEN FT WALL FIREBLOCKING IN BASEMENT, FB THE TOP GAP ELECTRICAL: -PAN OFF ELECTRICAL INSIDE RETURN AIR SPACE AT MASTER BATH/BED WALL **MAKE SURE TO HAVE MIN. 12"X12" CLEAR ACCESS OPENING FOR THE HYDROTUB MOTOR **OK TO INSULATE
All Rough Inspection - Residential Passed 3/9/2017 3/9/2017 03/09/2017
Misc
Resolved
03/09/2017
FRAMING: -SHALL SHIM GAPS UNDER ALL STUDS IN GARAGE -NAIL WALL INTERSECTION AT MASTER CLOSET/TOILET WALL -INSTALL HANGERS AND NAIL ABOVE MASTER SHOWER -PROVIDE FULL SUPPORT TO I BEAM UNDERNEATH TWO POINT LOADS AT MASTER SHOWER WALL -FIREBLOCK FIREPLACE SPACE AT WALL WITH 3/4" SHEATHING -BRACE 3X LVL BEAM (ABOVE GREAT RM) ENDS FROM ROTATION -SUPPORT HIP&VALLEY ABOVE 3X LVL BEAM (ABOVE GREAT RM) -FRONT BED: FRAME THE HIP SUPPORT PER 4/S2 DETAIL; THE FRONT CLOSET WALL IS NOT A BEARING WALL -SEAL CEILING JOIST RETURN AIR SPACE PENETRATIONS ABOVE BASEMENT -AT THE TEN FT WALL FIREBLOCKING IN BASEMENT, FB THE TOP GAP ELECTRICAL: -PAN OFF ELECTRICAL INSIDE RETURN AIR SPACE AT MASTER BATH/BED WALL **MAKE SURE TO HAVE MIN. 12"X12" CLEAR ACCESS OPENING FOR THE HYDROTUB MOTOR **OK TO INSULATE
Piers/Caissons Inspection - Residential Passed 3/22/2017 3/22/2017 03/22/2017
Driveway Inspection Passed 5/4/2017 5/4/2017 05/05/2017
Piers/Caissons Inspection - Residential Passed 5/12/2017 5/12/2017 05/12/2017
Occupancy Inspection - Codes Residential Failed 5/26/2017 05/26/2017
Misc
Corrective Action Required
05/26/2017
1. Property address shall be capable of being illuminated. 2. Obtain sprinkler permit. 3. Final grade; erosion control; splashblocks. 4. Receptacle cover over fireplace not seated - leaves live conductors exposed. 5. Receptacles in laundry room are within 6-feet of sink and should be GFCI protected. 6. Install four (4) 3-inch security screws through metal jamb-plate at downstairs entry door.
Occupancy Inspection - Codes Residential Temporary C of O 6/1/2017 6/1/2017 06/01/2017
Misc
Corrective Action Required
05/26/2017
3. Final grade; erosion control; splashblocks. 6. Install four (4) 3-inch security screws through metal jamb-plate at downstairs entry door. **Install a security strike plate
Erosion Control Inspection Residential Passed 06/01/2017
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
06/01/2017
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Occupancy Inspection - Codes Residential Full C of O 6/6/2017 6/6/2017 06/06/2017
Misc
Resolved
06/06/2017
3. Final grade; erosion control; splashblocks.
Documents & Images
Date Uploaded File Type Document Name
10/11/2016 Receipt Receipt for transaction: 2016-006349
10/11/2016 Letter Codes Building Permit
10/11/2016 Plot Plan DOC101116-030
10/13/2016 Letter Inspection Summary
10/14/2016 Letter Inspection Summary
11/17/2016 Letter Inspection Summary
01/17/2017 Letter Inspection Summary
03/07/2017 Letter Inspection Summary
03/09/2017 Letter Inspection Summary
03/22/2017 Letter Inspection Summary
05/05/2017 Letter Inspection Summary
05/12/2017 Letter Inspection Summary
05/26/2017 Letter Inspection Summary
06/01/2017 Letter Codes Temporary Certificate of Occupancy
06/06/2017 Letter Field Certificate of Occupancy
07/14/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home