Summary
PRRES20151242
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
HOUSE - 2 STORY - FINISHED BASEMENT *ROOF TRUSSES
06/02/2015
06/12/2015
11/29/2015
12/18/2015
Locations
Contacts
SUMMIT CUSTOM HOMES LLC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 06/12/2015 06/12/2015
Tara Mitchell
Plot Plan Review (P&D) Approved 06/11/2015 06/12/2015
Tara Mitchell
Plot Plan Review Rejected 06/04/2015 06/10/2015
James Fletchall
Plot Plan Review (P&D) Approved 06/04/2015 06/09/2015
Ron Seyl
Residential Plan Review Approved 06/05/2015 06/03/2015
Tara Mitchell
Residential Plan Review Rejected 06/04/2015 06/02/2015
Tara Mitchell
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,059.87 $1,059.87 Paid 06/12/2015
Right of Way Permit Fee $75.00 $75.00 Paid 06/12/2015
8331507-Sewer Connection Fee $600.00 $600.00 Paid 06/12/2015
Water Tap Fee $3,198.00 $3,198.00 Paid 06/12/2015
Water Meter Fee $354.05 $354.05 Paid 06/12/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Not Ready 6/18/2015 (2:30) 6/18/2015 at 12:00 AM 06/18/2015
Footing Inspection - Residential Passed 6/19/2015 (8:00) 6/19/2015 at 12:00 AM 06/19/2015
Sewer Service Inspection - R Passed 7/17/2015 (10:45) 7/17/2015 at 12:00 AM 07/17/2015
Water Service Inspection - R Partial 07/17/2015
Water Service Inspection - R Passed 7/22/2015 (10:00) 7/22/2015 at 12:00 AM 07/22/2015
All Rough Inspection - Residential Not Ready 9/10/2015 9/10/2015 at 12:00 AM 09/10/2015
Misc
Corrective Action Required
09/10/2015
DENIED DUE TO INCORRECT SUB-CONTRACTOR
Electrical Service Inspection Passed 9/21/2015 9/21/2015 at 12:00 AM 09/15/2015
Gas Service Inspection - Residential Failed 09/15/2015
All Rough Inspection - Residential Failed 9/15/2015 9/15/2015 at 12:00 AM 09/15/2015
Misc
Corrective Action Required
09/10/2015
-no interior braced walls installed -corner studs nailing -fill all holes in hangers -security blocking rear door -stud support 2 2x10 over garage door -garage straps -FIRESTOP chases -over drilled studs throughout -multiple top plates drilled over 50% with no reinforcement -nail floor joists from top into plates and sills -fireblock top plate basement -vent basement bar -install plate bolts per code Do not insulate.
All Rough Inspection - Residential Failed 9/21/2015 9/21/2015 at 12:00 AM 09/21/2015
Misc
Corrective Action Required
09/15/2015
-INSTALL STUD SHOES AND TOP PLATE REINFORCEMENT. -FIRESTOP AREAS WHERE M.E.P. SYSTEMS PREVENT FIREBLOCKING OKAY INSULATE
Gas Service Inspection - Residential Passed 9/21/2015 9/21/2015 at 12:00 AM 09/21/2015
All Rough Inspection - Residential Passed 9/25/2015 9/25/2015 at 12:00 AM 09/25/2015
Misc
Resolved
09/25/2015
-INSTALL STUD SHOES AND TOP PLATE REINFORCEMENT. -FIRESTOP AREAS WHERE M.E.P. SYSTEMS PREVENT FIREBLOCKING OKAY INSULATE
All Rough Inspection - Residential Passed 11/24/2015
Misc
Resolved
11/24/2015
-INSTALL STUD SHOES AND TOP PLATE REINFORCEMENT. -FIRESTOP AREAS WHERE M.E.P. SYSTEMS PREVENT FIREBLOCKING OKAY INSULATE **25-SEPT-NO ACCESS CODE
Occupancy Inspection - Codes Residential Failed 11/24/2015 at 12:00 AM 11/24/2015
Misc
Corrective Action Required
11/24/2015
-UNDERSLAB PLUMBING NOT APPROVED ON RECORD -DRIVEWAY NOT APPROVED ON RECORD -ALL SIDING IS LESS THAN 2" ABOVE PATIO CONCRETE SLAB AND 6" ABOVE SOIL SHALL BE TREATED WOOD -CANNOT POUR THE CONCRETE STAIR TO THE SIDING. SAME MINIMUM 2" CLEARANCE FROM CONCRETE IS REQUIRED -BRING WATER METER UP TO FINAL GRADE -SEAL FRONT GARAGE LIGHTS -INSTALL WATER HAMMERING ARRESTOR FOR THE DISH WASHER WATER SUPPLY -MOVE THE HYDROTUB RECEPTACLE WITH DIRECT VIEW OF OPENING. SECURE ALL WIRING PER CODE. -THE HYDROTUB ACCESS OPENING FOR THE REMOVAL OF THE MOTOR SHALL BE MINIMUM 12"X12" CLEAR AND UNOBSTRUCTED OPENING -INSTALL HANDRAILS TO MIDSTAIR LANDING AND TO BASEMENT -ENCLOSED&ACCESSIBLE SPACE UNDER THE STAIR SHALL BE PROTECTED WITH 1/2" GYPSUM BOARD COVERING BOTH WALL AND CEILING. MAKE SURE TO PROVIDE READY ACCESS TO THE SUMP PUMP AND RECEPTACLE IN THIS SPACE. CANNOT SCREW THE COVERING TO WALL -INSTALL HANDLE TIE FOR THE SUB PANEL BREAKER -REPLACE THE AC BREAKER WITH MAXIMUM 40 AMP PER LABEL -SUPPORT THE GAS CSST LINE TO WATER HEATER PER CODE -VENT WATER HEATER -SECURE FURNACE RACEWAY WITHIN 3FT OF UPPER END -INSTALL FACE PLATE FOR FURNACE SWITCH -WATER SERVICE: INSTALL WATER PRESSURE REDUCER; SECURE LINE AS REQUIRED -PROVIDE ACCESS TO UFER GROUNDING CONNECTION
Underslab Plumbing Inspection - Residential Passed 11/30/2015
Occupancy Inspection - Codes Residential Temporary C of O 11/30/2015 at 12:00 AM 11/30/2015
Misc
Corrective Action Required
11/24/2015
-INSTALL SOD -DRIVEWAY NOT APPROVED ON RECORD -ALL SIDING IS LESS THAN 2" ABOVE PATIO CONCRETE SLAB AND 6" ABOVE SOIL SHALL BE TREATED WOOD -CANNOT POUR THE CONCRETE STAIR TO THE SIDING. SAME MINIMUM 2" CLEARANCE FROM CONCRETE IS REQUIRED -BRING WATER METER UP TO FINAL GRADE -SEAL FRONT GARAGE LIGHTS
Occupancy Inspection - Codes Residential Failed 12/16/2015 12/16/2015 12/16/2015
Misc
Corrective Action Required
11/30/2015
-DRIVEWAY NOT APPROVED ON RECORD
Driveway Inspection Passed 12/18/2015
Occupancy Inspection - Codes Residential Full C of O 12/18/2015 12/18/2015
Misc
Resolved
12/18/2015
-DRIVEWAY NOT APPROVED ON RECORD
Documents & Images
Date Uploaded File Type Document Name
06/12/2015 Letter Codes Building Permit
06/12/2015 Receipt Receipt for transaction: 2015-002861
06/15/2015 Plot Plan DOC061515-002
06/18/2015 Letter Inspection Summary
06/19/2015 Letter Inspection Summary
07/17/2015 Letter Inspection Summary
07/22/2015 Letter Inspection Summary
09/10/2015 Letter Inspection Summary
09/15/2015 Letter Inspection Summary
09/15/2015 Letter Inspection Summary
09/21/2015 Letter Inspection Summary
09/21/2015 Letter Inspection Summary
09/25/2015 Letter Inspection Summary
11/24/2015 Letter Inspection Summary
11/30/2015 Letter Codes Temporary Certificate of Occupancy
12/16/2015 Letter Inspection Summary
12/18/2015 Letter Field Certificate of Occupancy
12/21/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home