Summary
PRRES20131167
Building Permit - Residential
Certificate of Occupancy
JOHN KNOX VILLAGE
NEW 3 OR 4 FAMILY
3PLEX
06/12/2013
06/28/2013
07/10/2014
Locations
Contacts
LARRY HARKRADER CONSTRUCTION, Address:401 NW MURRAY RD, Phone:(816) 607-7191  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
S & L ELECTRIC INC, Address:1301 S POWELL, Phone:(816) 796-6859  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 06/14/2013 06/21/2013
Codes Admin
Plot Plan Review (P&D) Approved 06/17/2013 06/17/2013
Jennifer Thompson
Plot Plan Review Approved 06/14/2013 06/13/2013
Gene Williams, P.E.
Plot Plan Review (P&D) Rejected 06/14/2013 06/13/2013
Jennifer Thompson
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New 3 or 4 Family $1,416.72 $1,416.72 Paid 06/28/2013
$1,416.72
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 8/28/2013 (10:00) 8/28/2013 at 12:00 AM 08/28/2013
Underslab Plumbing Inspection - Residential Passed 9/20/2013 at 12:00 AM 09/20/2013
Sewer Service Inspection - R Partial 10/1/2013 (1:45) 10/1/2013 at 12:00 AM 10/01/2013
Misc
Partial Correction
10/01/2013
OK TO COVER WHEN READY SANITARY SEWER SERVICE INSTALLATIONS AS FOLLOWS: COMMON SERVICE AT UNITS A & B FROM BUILDING ENTRIES TO CONNECTION AT STUB;
Water Service Inspection - R Partial 6/19/2014 at 12:00 AM 10/01/2013
Misc
Partial Correction
10/01/2013
OK TO COVER WHEN READY WATER SERVICE LINE INSTALLATIONS AS FOLLOWS: FROM UNIT A BUILDING ENTRY TO NEAR METER LOCATION;
Sewer Service Inspection - R Passed 10/2/2013 (1:00) 10/2/2013 at 12:00 AM 10/02/2013
Misc
Resolved
10/02/2013
OK TO COVER WHEN READY SANITARY SEWER SERVICE INSTALLATIONS AS FOLLOWS: COMMON SERVICE AT UNITS A & B FROM BUILDING ENTRIES TO CONNECTION AT STUB;
Water Service Inspection - R Passed 10/2/2013 (1:00) 10/2/2013 at 12:00 AM 10/02/2013
Misc
Resolved
10/02/2013
OK TO COVER WHEN READY WATER SERVICE LINE INSTALLATIONS AS FOLLOWS: FROM UNIT A BUILDING ENTRY TO NEAR METER LOCATION;
All Rough Inspection - Residential Partial 11/1/2013 11/1/2013 at 12:00 AM 11/01/2013
Misc
Partial Correction
11/01/2013
NO ISSUES FOUND ON INTERIM INSPECTION OF COMPLETE PLACEMENT AND WASHER/NUT TIGHTENING AT SILL PLATE ANCHOR BOLTS.
All Rough Inspection - Residential Not Ready 2/14/2014 2/14/2014 at 12:00 AM 02/14/2014
Misc
Partial Correction
11/01/2013
NO ISSUES FOUND ON INTERIM INSPECTION OF COMPLETE PLACEMENT AND WASHER/NUT TIGHTENING AT SILL PLATE ANCHOR BOLTS.
Misc
Corrective Action Required
02/14/2014
ELECTRICAL WORK IN PROGRESS. PLUMBING AT BASEMENT NOT COMPLETED? ENSURE ALL TOP & BOTTOM PLATES ARE FIRE-BLOCKED WHERE BORED. ALSO, FIRE-BLOCK BELOW BATH TUB. REQUEST ALL-ROUGH WHEN ALL IS COMPLETED.
Gas Piping Inspection - Residential Passed 2/14/2014 at 12:00 AM 02/14/2014
All Rough Inspection - Residential Partial 2/18/2014 2/18/2014 at 12:00 AM 02/18/2014
Misc
Partial Correction
02/14/2014
OK TO INSULATE AND DRYWALL MAIN LEVEL CEILINGS AND WALLS.
Misc
Corrective Action Required
02/14/2014
BASEMENT TO BE INSPECTED AFTER FLOOR IS DE-WATERED.
Electrical Service Inspection Passed 2/28/2014 2/28/2014 at 12:00 AM 02/28/2014
Gas Piping Inspection - Residential Passed 3/3/2014 3/3/2014 at 12:00 AM 03/03/2014
All Rough Inspection - Residential Partial 3/3/2014 3/3/2014 at 12:00 AM 03/03/2014
Misc
Partial Correction
02/18/2014
OK TO INSULATE AND DRYWALL MAIN LEVEL CEILINGS AND WALLS AT UNIT: C; B EXCEPT AT BOTH ENDS WHERE FIRE SEPERATION IS YET TO BE COMPLETED;
Misc
Resolved
03/03/2014
BASEMENT TO BE INSPECTED AFTER FLOOR IS DE-WATERED.
All Rough Inspection - Residential Partial 3/6/2014 at 12:00 AM 03/06/2014
Misc
Partial Correction
03/03/2014
OK TO INSULATE AND DRYWALL MAIN LEVEL CEILINGS AND WALLS AT UNIT: C; B INCLUDING AT BOTH ENDS WHERE FIRE SEPARATION IS NOW COMPLETED;
All Rough Inspection - Residential Not Ready 3/10/2014 at 12:00 AM 03/10/2014
Misc
Partial Correction
03/06/2014
OK TO INSULATE AND DRYWALL MAIN LEVEL CEILINGS AND WALLS AT UNIT: C; B; ;
Misc
Corrective Action Required
03/10/2014
UNIT A: - LEVEL-TO-LEVEL FIRE BLOCKING NOT DONE - CLARIFICATION REQUIRED RE R/A PATH WHERE ELECT WIRE & BOXES ARE INSTALLED - NOTE: R602.6.1 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load-bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 11/2 inches (38 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) having a minimum length of 11/2 inches (38 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches past the opening. See Figure R602.6.1.
All Rough Inspection - Residential Passed 3/11/2014 at 12:00 AM 03/11/2014
Misc
Resolved
03/11/2014
OK TO INSULATE AND DRYWALL MAIN LEVEL CEILINGS AND WALLS AT UNIT: C; B; A
Misc
Resolved
03/11/2014
UNIT A: - LEVEL-TO-LEVEL FIRE BLOCKING NOT DONE - CLARIFICATION REQUIRED RE R/A PATH WHERE ELECT WIRE & BOXES ARE INSTALLED - NOTE: R602.6.1 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load-bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 11/2 inches (38 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) having a minimum length of 11/2 inches (38 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches past the opening. See Figure R602.6.1.
Gas Piping Inspection - Residential Partial 3/13/2014 at 12:00 AM 03/13/2014
Misc
Partial Correction
03/13/2014
GAS PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN AT UNIT(S): C, B, UNIT "A" 3/13: LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM
Gas Piping Inspection - Residential Passed 3/14/2014 3/14/2014 at 12:00 AM 03/14/2014
Misc
Resolved
03/14/2014
GAS PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN AT UNIT(S): C, B, UNIT "A" 3/13: LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM
Occupancy Inspection - Codes Residential Temporary C of O 3/28/2014 3/28/2014 at 12:00 AM 03/28/2014
Misc
Partial Correction
03/28/2014
FOLLOWING UIT(S) OK FOR USE AND OCCUPANCY: UNIT "C" AFTER GRADE DIFFERENTIAL AT BACK DOOR AT GARAGE IS REDUCED TO <= 7-3/4";
Occupancy Inspection - Codes Residential Failed 5/7/2014 5/7/2014 at 12:00 AM 05/07/2014
Misc
Partial Correction
03/28/2014
FOLLOWING UIT(S) OK FOR USE AND OCCUPANCY: UNIT "C";
Misc
Corrective Action Required
05/07/2014
UNIT B: 1) PROVIDE MAINTENANCE CLEARANCE AROUND HOSE BIB AT FRONT OF UNIT 2) INSTALL VACUUM BREAKER AT HOSE BIB IN BASEMENT AT WATER SERVICE ENTRY 3) SECURE PIPE POST BASE PLATES TO BASEMENT FLOOR SLAB
Occupancy Inspection - Codes Residential Temporary C of O 5/9/2014 5/9/2014 at 12:00 AM 05/09/2014
Misc
Partial Correction
05/07/2014
FOLLOWING UIT(S) OK FOR USE AND OCCUPANCY: UNIT "C"; UNIT "B"; FINISH LANDSCAPING TO BE COMPLETED BY JKV. ENSURE NO EROSION OF TOPSOIL ONTO STREET AND INTO STORM WATER SYSTEM. PERMIT HOLDER AND JKV TO ENSURE SMOKE ALARM SYSTEM IS ACTIVATED AND WORKING PROPERLY BEFORE UNITS ARE OCCUPIED.
Misc
Resolved
05/09/2014
UNIT B: 1) PROVIDE MAINTENANCE CLEARANCE AROUND HOSE BIB AT FRONT OF UNIT 2) INSTALL VACUUM BREAKER AT HOSE BIB IN BASEMENT AT WATER SERVICE ENTRY 3) SECURE PIPE POST BASE PLATES TO BASEMENT FLOOR SLAB
Occupancy Inspection - Codes Residential Failed 6/3/2014 6/3/2014 at 12:00 AM 06/03/2014
Misc
Partial Correction
05/09/2014
FOLLOWING UIT(S) OK FOR USE AND OCCUPANCY: UNIT "C"; UNIT "B"; PERMIT HOLDER AND JKV TO ENSURE SMOKE ALARM SYSTEM IS ACTIVATED AND WORKING PROPERLY BEFORE UNITS ARE OCCUPIED.
Misc
Corrective Action Required
06/03/2014
UNIT "A': 1) LOWER BUILDING SEWER CLEANOUTS TO (NEAR) GRADE 2) IPC 308.5; IRC P2605 PEX MAXIMUM SUPPORT SPACING INTERVAL: HORIZONTAL RUNS 32" (CRAWL SPACE) 3) COPPER WATER PIPE AT S WALL OF FURN RM: CLAMPS APPEAR TO BE NAILED INTO GYP BOD ONLY -- DO NOT HOLD 4) NEC 110.26A; IRC 3405.1 WORKING SPACE IN FRONT OF A/C DISCONNECT OBSTRUCTED
Misc
Corrective Action Required
06/03/2014
VEGETATION YET TO BE ESTABLISHED BEHIND BUILDING
Occupancy Inspection - Codes Residential Temporary C of O 6/6/2014 6/6/2014 at 12:00 AM 06/06/2014
Misc
Resolved
06/06/2014
FOLLOWING UIT(S) OK FOR USE AND OCCUPANCY: UNIT "C"; UNIT "B"; PERMIT HOLDER AND JKV TO ENSURE SMOKE ALARM SYSTEM IS ACTIVATED AND WORKING PROPERLY BEFORE UNITS ARE OCCUPIED.
Misc
Resolved
06/06/2014
UNIT "A': 1) LOWER BUILDING SEWER CLEANOUTS TO (NEAR) GRADE 2) SUPPORT HORIZONTAL RUNS OF PEX @ 32" MAX (CRAWL SPACE) 3) COPPER WATER PIPE AT S WALL OF FURN RM: CLAMPS APPEAR TO BE NAILED INTO GYP BOD ONLY -- DO NOT HOLD 4) NEC 110.26A; IRC 3405.1 WORKING SPACE IN FRONT OF A/C DISCONNECT OBSTRUCTED
Misc
Resolved
06/06/2014
VEGETATION YET TO BE ESTABLISHED BEHIND BUILDING
Misc
Corrective Action Required
06/06/2014
PROVIDE WELL STRUCTURE WHERE GAS PRESSURE REGULATORS AND SHUT-OFF VALVES ARE BELOW GRADE AT UNITS "B" AND "C".
Occupancy Inspection - Codes Residential Temporary C of O 6/24/2014 at 12:00 AM 06/24/2014
Misc
Corrective Action Required
06/17/2014
TCO REINSTATED THROUGH 7/10/14 TO ACCOMODATE PROVISION OF WELL STRUCTURE WHERE GAS PRESSURE REGULATORS AND SHUT-OFF VALVES ARE BELOW GRADE AT UNITS "B" AND "C".
Occupancy Inspection - Codes Residential Full C of O 7/10/2014 at 12:00 AM 07/10/2014
Misc
Resolved
07/10/2014
PROVIDE WELL STRUCTURE WHERE GAS PRESSURE REGULATORS AND SHUT-OFF VALVES ARE BELOW GRADE AT UNITS "B" AND "C".
Occupancy Inspection - Codes Residential Full C of O 7/10/2014 at 12:00 AM 07/10/2014
Misc
Resolved
07/10/2014
TCO REINSTATED THROUGH 7/10/14 TO ACCOMODATE PROVISION OF WELL STRUCTURE WHERE GAS PRESSURE REGULATORS AND SHUT-OFF VALVES ARE BELOW GRADE AT UNITS "B" AND "C".
Plot Plan Inspection Passed 7/10/2014 at 12:00 AM 07/10/2014
Miscellaneous Inspection Passed 7/10/2014 at 12:00 AM 07/10/2014
Documents & Images
Date Uploaded File Type Document Name
06/28/2013 Letter Building Permit
08/28/2013 Letter Inspection Summary
09/20/2013 Letter Inspection Summary
10/01/2013 Letter Inspection Summary
10/02/2013 Letter Inspection Summary
11/01/2013 Letter Inspection Summary
02/14/2014 Letter Inspection Summary
02/18/2014 Letter Inspection Summary
02/28/2014 Letter Inspection Summary
03/03/2014 Letter Inspection Summary
03/06/2014 Letter Inspection Summary
03/10/2014 Letter Inspection Summary
03/11/2014 Letter Inspection Summary
03/14/2014 Letter Inspection Summary
03/28/2014 Letter Codes Temporary Certificate of Occupancy
05/07/2014 Letter Inspection Summary
05/09/2014 Letter Codes Temporary Certificate of Occupancy
06/03/2014 Letter Inspection Summary
06/06/2014 Letter Codes Temporary Certificate of Occupancy
06/19/2014 Letter Codes 10 Day Letter
06/24/2014 Letter Codes Temporary Certificate of Occupancy
07/10/2014 Letter Field Certificate of Occupancy
07/11/2014 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.