Permit Application Status

PRRES20130212


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20130212
Building Permit - Residential
Certificate of Occupancy
LAKE RIDGE LLC
NEW SINGLE FAMILY
HOUSE
02/14/2013
02/25/2013
10/08/2013
Locations
Contacts
SUMMIT CUSTOM HOMES LLC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
LAKE RIDGE LLC, Address:PO BOX 1447  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review (P&D) Approved 02/19/2013 02/25/2013
Codes Admin
Plot Plan Review Approved 02/21/2013 02/22/2013
Gene Williams, P.E.
Plot Plan Review Rejected 02/19/2013 02/19/2013
Gene Williams, P.E.
Corrective Action Required
02/19/2013

1. Two water valves are missing near the northwest corner of the site.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $897.06 $897.06 Paid 02/25/2013
$897.06
9110073-Right of Way Permit Fee $60.00 $60.00 Paid 02/25/2013
$60.00
8331507-Sewer Connection Fee $570.00 $570.00 Paid 02/25/2013
$570.00
8331401-Water Tap Fee $3,085.00 $3,085.00 Paid 02/25/2013
$3,085.00
8350015-Water Meter Fee $253.99 $253.99 Paid 02/25/2013
$253.99
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 3/22/2013 (11:30) 3/22/2013 at 12:00 AM 03/22/2013
Sewer Service Inspection - R Passed 04/04/2013
Water Service Inspection - R Partial 04/04/2013
Water Service Inspection - R Passed 4/5/2013 (3:00) 4/5/2013 at 12:00 AM 04/05/2013
Underslab Plumbing Inspection - Residential Passed 4/8/2013 4/8/2013 at 12:00 AM 04/08/2013
Piers/Caissons Inspection - Residential Passed 5/21/2013 (8:30) 5/21/2013 at 12:00 AM 05/21/2013
All Rough Inspection - Residential Not Ready 5/23/2013 5/23/2013 at 12:00 AM 05/23/2013
All Rough Inspection - Residential Failed 6/21/2013 6/21/2013 at 12:00 AM 06/21/2013
Misc
Corrective Action Required
06/21/2013
-ALL TOP PLATES WHERE CUT DRILLED OVER 50% REQUIRE STRAPS WITH A MINIMUM 4 12d NAILS EACH SIDE OF THE NOTCH -TRUSSES OVER HALL TO WEST 1ST FLOOR BATH HAVE NO BEARING -REPAIR STRUCTURAL STRAP CUT FOR HVAC AT FIRST FLOOR -STRUCTURAL STRAP FOR DOUBLE TOP PLATE IN CORNER OF PANTRY -NAIL ALL EXTERIOR CORNER STUDS MINIMUM 12 INCHES ON CENTER -FIREBLOCK HVAC CHASE FIRST FLOOR -INSTALL FIREPLACE FRAMING -FIREBLOCK FUR DOWN AT 2ND FLOOR CLOSET -BASEMENT, JOISTS SUPPORTING KITCHEN AND PANTRY, PLANS CALL FOR DOUBLE 2x10 EVERY OTHER THEN DOUBLE EVERY WHERE SUPPORTING ISLAND DO NOT INSUALTE
Gas Service Inspection - Residential Passed 6/21/2013 6/21/2013 at 12:00 AM 06/21/2013
Electrical Service Inspection Passed 6/21/2013 6/21/2013 at 12:00 AM 06/21/2013
All Rough Inspection - Residential Failed 6/28/2013 6/28/2013 at 12:00 AM 06/28/2013
Misc
Corrective Action Required
06/21/2013
-REPAIR STRUCTURAL STRAP CUT FOR HVAC AT FIRST FLOOR -FIREBLOCK HVAC CHASE FIRST FLOOR -INSTALL FIREPLACE FRAMING *SECURE FIREPLACE TO FRAME *OK TO INSUALTE. NO ROCK
All Rough Inspection - Residential Passed 7/2/2013 7/2/2013 at 12:00 AM 07/02/2013
Misc
Resolved
07/02/2013
-REPAIR STRUCTURAL STRAP CUT FOR HVAC AT FIRST FLOOR -FIREBLOCK HVAC CHASE FIRST FLOOR -INSTALL FIREPLACE FRAMING *SECURE FIREPLACE TO FRAME *OK TO INSUALTE. NO ROCK
Driveway Inspection Passed 7/16/2013 at 3:00 AM 07/18/2013
Sidewalk Inspection Passed 7/17/2013 at 3:15 AM 07/18/2013
Occupancy Inspection - Codes Residential Failed 10/1/2013 10/1/2013 at 12:00 AM 10/01/2013
Misc
Corrective Action Required
10/01/2013
-NO ACCESS CODE TO THE HOUSE. REINSPECTION FEE ASSESSED. NO FURTHER INSPECTION UNTIL THE FEE IS PAID.
Occupancy Inspection - Codes Residential Failed 10/4/2013 at 12:00 AM 10/04/2013
Misc
Resolved
10/04/2013
-NO ACCESS CODE TO THE HOUSE. REINSPECTION FEE ASSESSED. NO FURTHER INSPECTION UNTIL THE FEE IS PAID.
Misc
Corrective Action Required
10/04/2013
GYP BD AT ACCESS OPENING @ HYDRO TUB NOT COMPLETELY CUT OUT
Misc
Corrective Action Required
10/04/2013
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT FASTENED SOLID TO BOX. CHECK ALL AT BEDROOMS AND BREAKFAST NOOK AND ENSURE NONE ARE LOOSE SIDE-TO-SIDE.
Misc
Corrective Action Required
10/04/2013
ELECT RECEPT @ FIREPLACE LACKS FACE PLATE.
Misc
Corrective Action Required
10/04/2013
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT KITCHEN BACKSPLASH.
Misc
Corrective Action Required
10/04/2013
IRC R407.3 POST BASE PLATES NOT SECURED TO BASEMENT SLAB
Occupancy Inspection - Codes Residential Full C of O 10/8/2013 10/8/2013 at 12:00 AM 10/08/2013
Misc
Resolved
10/08/2013
GYP BD AT ACCESS OPENING @ HYDRO TUB NOT COMPLETELY CUT OUT
Misc
Resolved
10/08/2013
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT FASTENED SOLID TO BOX. CHECK ALL AT BEDROOMS AND BREAKFAST NOOK AND ENSURE NONE ARE LOOSE SIDE-TO-SIDE.
Misc
Resolved
10/08/2013
ELECT RECEPT @ FIREPLACE LACKS FACE PLATE.
Misc
Resolved
10/08/2013
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT KITCHEN BACKSPLASH.
Misc
Resolved
10/08/2013
IRC R407.3 POST BASE PLATES NOT SECURED TO BASEMENT SLAB
Documents & Images
Date Uploaded File Type Document Name
02/25/2013 Letter Building Permit
02/25/2013 Plot Plan
03/22/2013 Letter Inspection Summary
04/04/2013 Letter Inspection Summary
04/05/2013 Letter Inspection Summary
04/08/2013 Letter Inspection Summary
05/21/2013 Letter Inspection Summary
05/23/2013 Letter Inspection Summary
06/21/2013 Letter Inspection Summary
06/28/2013 Letter Inspection Summary
07/02/2013 Letter Inspection Summary
10/01/2013 Letter Inspection Summary
10/01/2013 Letter Re-Inspection Fee
10/04/2013 Letter Inspection Summary
10/08/2013 Letter Field Certificate of Occupancy
10/09/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home