Summary
PRRES20122126
Building Permit - Residential
Certificate of Occupancy
TRAVIS RUF
ALTERATION SINGLE FAMILY
INTERIOR RENOVATION; ELECTRIC SERVICE; DECK; GAS SERVICE
09/24/2012
09/24/2012
12/12/2013
Locations
Contacts
TRAVIS RUF, Address:301 NW VIEW HIGH DR, Phone:(816) 813-2292  
HIGHWAY STAR ELECTRIC LLC, Address:706 YORK DR, Phone:(816) 896-5758  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review (P&D) Approved 09/24/2012
Codes Admin
Internal Plan Review (Res) Approved 09/24/2012
Codes Admin
True
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Add/Alter Single Family $38.37 $38.37 Paid 09/24/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Gas Service Inspection - Residential Failed 12/19/2012 at 12:00 AM 12/19/2012
Misc
Corrective Action Required
12/19/2012
LSCO 7-608: GAS PIPING TEST PRESSURE DECREASED DURING MONITORING PERIOD. PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT MINIMUM 10 PSI
Electrical Service Inspection Partial 12/19/2012 at 12:00 AM 12/19/2012
Misc
Corrective Action Required
12/19/2012
ONE GROUND ROD INSTALLED, BUT EXISTING WATER LINE GROUND NEEDS TO BE EXTENDED AND TERMINATED AT PANEL. SERVICE RELEASED ON TEMPORARY BASIS.
Electrical Service Inspection Partial 1/23/2013 1/23/2013 at 12:00 AM 01/23/2013
Misc
Resolved
01/23/2013
ONE GROUND ROD INSTALLED, BUT EXISTING WATER LINE GROUND NEEDS TO BE EXTENDED AND TERMINATED AT PANEL. SERVICE RELEASED ON TEMPORARY BASIS.
Misc
Corrective Action Required
01/23/2013
NEC 250-64: USE NON-REVERSIBLE CONNECTORS ON GROUNDING ELECTRODE CONDUCTOR SPLICES. DO NOT COVER SPLICE BEFORE RE-INSPECTION.
Gas Service Inspection - Residential Passed 1/23/2013 1/23/2013 at 12:00 AM 01/23/2013
Misc
Resolved
01/23/2013
LSCO 7-608: GAS PIPING TEST PRESSURE DECREASED DURING MONITORING PERIOD. PRESSURIZE PIPING SYSTEM TO HOLD STEADY AT MINIMUM 10 PSI
All Rough Inspection - Residential Failed 2/27/2013 2/27/2013 at 12:00 AM 02/27/2013
Misc
Corrective Action Required
02/27/2013
FRAMING: -FIREBLOCKING: FB BASEMENT BED CLOSET WALL FROM JOIST SPACE AND AT I BEAM POCKET; FB BASEMENT FAMILY RM WALL EVERY 10 FT HORIZONTALLY; FB DEAD SPACE AT BASEMENT FAMILY RM CORNER -REINFORCE SUPPORT FOR OVERNOTCHED JOIST ABOVE BASEMENT BED RM CORNER -BASEMENT BED RM ESCAPE WINDOW SHALL HAVE MIN. 5 SQ. FT IN CLEAR OPENING AREA, MIN. 20" IN WIDTH, MIN. 24" IN HEIGHT -ANCHOR BASEMENT FAMILY RM EXTERIOR SILL PLATE WITH 2 (1/2") ANCHORS PER PLATE. -BLOCK DOOR STUD PER LS SECURITY CODE (BASEMENT EXTERIOR DOOR) ELECTRICAL: -INSTALL LIGHT FIXTURE ABOVE BASEMENT BATH SHOWER -THE BONDING CONNECTION TO RIGID GAS PIPING REQUIRED BY WARDFLEX SHALL BE ACCESSIBLE -OVERFILLED ELECTRICAL SWITCH BOX AT BASEMENT BED CLOSET -SECURE ALL NM CABLES WITHIN 8" OF ALL BOXES -INSIDE ALL BOXES, TIE ALL EQUIPMENT GROUNDING CONDUCTORS TOGETHER WITH LISTED DEVICE (WIRE NUTS, LISTED CRIMPS, ETC). LEAVE PIG TAILS FOR GROUNDING DEVICES -ADD A WALL RECEPTACLE IN HALLWAY OUTSIDE BEDROOMS -PROVIDE MIN. 12" CLEARANCE FROM INCANDESENT LUMINAIRE TO CLOSET SHELF; OR 6" FOR FLOURESCENT LUMINAIRE @MAIN FLOOR CLOSET AT LAUNDRY RM -CANNOT USE 20 AMP CIRCUITS FOR KITCHEN COUNTERTOP RECEPTACLES TO FEED LIGHTS.INSTALL SEPARATE CIRCUIT FOR THIS OR CONNECT TO OTHER AVAILABLE GENERAL LIGHTING CIRCUIT. -INSTALL A SEPARATE CIRCUIT FOR THE MICROWAVE. CANNOT CONNECT TO LIVING RM LIGHTING AND OUTLET CIRCUIT. TOO MUCH LOAD PLUMBING: -INSTALL STRUCTURAL STRAP ACROSS KITCHEN EXTERIOR WALL TOP PLATE WHERE THE SINK VENT PENETRATES THROUGH -SHALL VENT BOTH THE LAUNDRY UTILITY SINK AND LAUNDRY STAND PIPE -SUPPORT LAUNDRY RM PLUMBING EVERY 4 FT -THE LAUNDRY PLUMBING HORIZONTAL-HORIZONTAL CONNECTION TO THE 3" HORIZONTAL DRAIN SHALL BE EITHER COMBINATION FITTING, OR WYE FITTING. NO SANITARY TEE FITTING ALLOWED MECHANICAL: -PROVIDE COMBUSTION AIR OPENINGS: ONE WITHIN 12" OF FLOOR AND ONE WITHIN 12" OF CEILING. EACH OPENING IS SIZED BASED ON 1 SQUARE INCH OF FREE AREA FOR EVERY 1000 BTU OF COMBINED MECHANICAL THERMAL INPUT ; OR INSTALL LOUVERED DOOR **DO NOT INSULATE.DO NOT ROCK
Electrical Service Inspection Failed 2/27/2013 2/27/2013 at 12:00 AM 02/27/2013
Misc
Corrective Action Required
01/23/2013
NEC 250-64: USE NON-REVERSIBLE CONNECTORS ON GROUNDING ELECTRODE CONDUCTOR SPLICES. DO NOT COVER SPLICE BEFORE RE-INSPECTION. **USE UL LISTED NON-REVERSIBLE DEVICE; OR PROVIDE LISTING
All Rough Inspection - Residential Passed 3/28/2013 3/28/2013 at 12:00 AM 03/28/2013
Misc
Resolved
03/28/2013
FRAMING: -FIREBLOCKING: FB BASEMENT BED CLOSET WALL FROM JOIST SPACE AND AT I BEAM POCKET; FB BASEMENT FAMILY RM WALL EVERY 10 FT HORIZONTALLY; FB DEAD SPACE AT BASEMENT FAMILY RM CORNER -REINFORCE SUPPORT FOR OVERNOTCHED JOIST ABOVE BASEMENT BED RM CORNER -BASEMENT BED RM ESCAPE WINDOW SHALL HAVE MIN. 5 SQ. FT IN CLEAR OPENING AREA, MIN. 20" IN WIDTH, MIN. 24" IN HEIGHT -ANCHOR BASEMENT FAMILY RM EXTERIOR SILL PLATE WITH 2 (1/2") ANCHORS PER PLATE. -BLOCK DOOR STUD PER LS SECURITY CODE (BASEMENT EXTERIOR DOOR) ELECTRICAL: -INSTALL LIGHT FIXTURE ABOVE BASEMENT BATH SHOWER -THE BONDING CONNECTION TO RIGID GAS PIPING REQUIRED BY WARDFLEX SHALL BE ACCESSIBLE -OVERFILLED ELECTRICAL SWITCH BOX AT BASEMENT BED CLOSET -SECURE ALL NM CABLES WITHIN 8" OF ALL BOXES -INSIDE ALL BOXES, TIE ALL EQUIPMENT GROUNDING CONDUCTORS TOGETHER WITH LISTED DEVICE (WIRE NUTS, LISTED CRIMPS, ETC). LEAVE PIG TAILS FOR GROUNDING DEVICES -ADD A WALL RECEPTACLE IN HALLWAY OUTSIDE BEDROOMS -PROVIDE MIN. 12" CLEARANCE FROM INCANDESENT LUMINAIRE TO CLOSET SHELF; OR 6" FOR FLOURESCENT LUMINAIRE @MAIN FLOOR CLOSET AT LAUNDRY RM -CANNOT USE 20 AMP CIRCUITS FOR KITCHEN COUNTERTOP RECEPTACLES TO FEED LIGHTS.INSTALL SEPARATE CIRCUIT FOR THIS OR CONNECT TO OTHER AVAILABLE GENERAL LIGHTING CIRCUIT. -INSTALL A SEPARATE CIRCUIT FOR THE MICROWAVE. CANNOT CONNECT TO LIVING RM LIGHTING AND OUTLET CIRCUIT. TOO MUCH LOAD PLUMBING: -INSTALL STRUCTURAL STRAP ACROSS KITCHEN EXTERIOR WALL TOP PLATE WHERE THE SINK VENT PENETRATES THROUGH -SHALL VENT BOTH THE LAUNDRY UTILITY SINK AND LAUNDRY STAND PIPE -SUPPORT LAUNDRY RM PLUMBING EVERY 4 FT -THE LAUNDRY PLUMBING HORIZONTAL-HORIZONTAL CONNECTION TO THE 3" HORIZONTAL DRAIN SHALL BE EITHER COMBINATION FITTING, OR WYE FITTING. NO SANITARY TEE FITTING ALLOWED MECHANICAL: -PROVIDE COMBUSTION AIR OPENINGS: ONE WITHIN 12" OF FLOOR AND ONE WITHIN 12" OF CEILING. EACH OPENING IS SIZED BASED ON 1 SQUARE INCH OF FREE AREA FOR EVERY 1000 BTU OF COMBINED MECHANICAL THERMAL INPUT ; OR INSTALL LOUVERED DOOR **DO NOT INSULATE.DO NOT ROCK
Plot Plan Inspection Passed 9/19/2013 at 12:00 AM 09/19/2013
Electrical Service Inspection Passed 9/19/2013 at 12:00 AM 09/19/2013
Misc
Resolved
09/19/2013
NEC 250-64: USE NON-REVERSIBLE CONNECTORS ON GROUNDING ELECTRODE CONDUCTOR SPLICES. DO NOT COVER SPLICE BEFORE RE-INSPECTION. **USE UL LISTED NON-REVERSIBLE DEVICE; OR PROVIDE LISTING. P.H. STATES KN APPROVED 2/27/13
Occupancy Inspection - Codes Residential Failed 9/19/2013 9/19/2013 at 12:00 AM 09/19/2013
Misc
Corrective Action Required
09/19/2013
COURTESY PRELIMINARY OCCUPANCY INSPECTION PERFORMED 9/19/13. ADDITIONAL ISSUES MAY BE CITED WHEN READY FOR FORMAL FINAL INSPECTION. DO NOT OCCUPY PRIOR TO APPROVAL.
Misc
Corrective Action Required
09/19/2013
CHECK ALL ELECT RECEPTS FOR CORRECT WIRING OPEN GROUND FOUND ON SOME.
Misc
Corrective Action Required
09/19/2013
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. USE SPARK RINGS TO RESOLVE WHERE NECESSARY.
Misc
Corrective Action Required
09/19/2013
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: MOST ARE NOT TIGHT TO BOX; CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Corrective Action Required
09/19/2013
NEC 370-25; 410-56 ELECTRICAL RECEPTACLE/SWITCH FACE PLATES: ENSURE ALL BOXES HAVE PLATES IN PLACE.
Misc
Corrective Action Required
09/19/2013
CAUTION TO PERMIT HOLDER / HOMEOWNER: INDUSTRY STANDARD MANUFACTURER INSTRUCTIONS REQUIRE MOUNTING HEIGHT OF CEILING FANS PROVIDE MINIMUM 7' FLOOR-TO-BLADES CLEARANCE; LOWER INSTALLATION COULD RESULT IN PERSONAL INJURY.
Misc
Corrective Action Required
09/19/2013
PIPING AT KITCHEN SINK: DISPOSAL DISCHARGE CANNOT BE BELOW ELEVATION OF TRAP ARM. GRAVITY FLOW IS PREVENTED. ENSURE ALL MATERIALS ARE LISTED FOR USE.
Misc
Corrective Action Required
09/19/2013
GFI PROTECTION REQUIRED AT ELECT RECEPT ABOVE-RIGHT OF BASEMENT BAR SINK.
Misc
Corrective Action Required
09/19/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
09/19/2013
PROTECTIVE NON-METALLIC BUSHING REQUIRED WHERE NM ELECT CABLE EXITS METALLIC RACEWAY. SEE AT FURNACE.
Misc
Corrective Action Required
09/19/2013
NEC 330.30: NON-METALLIC ELECTRICAL WHIP NOT SECURED TO STRUCTURE WITHIN 12" OF ENTRY TO A/C DISCONNECT ENCLOSURE.
Misc
Corrective Action Required
09/19/2013
IRC R316.2 STAIR TREAD / RISER / GUARD TRIANGULAR OPENINGS AT OPEN SIDE(S) OF STAIRWAY: OPENINGS MUST NOT ALLOW PASSAGE OF 6" SPHERE
Misc
Corrective Action Required
09/19/2013
LSCO 7-915 HANDRAIL AT STAIR MUST BE GRASPABLE: WIDTH OF HANDRAIL ON NON-REQUIRED EXTERIOR STAIR EXCEEDS 3-1/2" ALLOWABLE HORIZONTAL CROSS SECTIONAL DIMENSION. ENDS MUST RETURN TO STRUCTURE.
Misc
Corrective Action Required
09/19/2013
DECK FRAMING FASTENERS: EXISTING JOIST HANGERS NOT FULLY SCREWED/NAILED. HARDWARE LISTING IS BASED ON ALL HOLES USED.
Occupancy Inspection - Codes Residential Failed 12/3/2013 12/3/2013 at 12:00 AM 12/03/2013
Misc
Resolved
12/03/2013
COURTESY PRELIMINARY OCCUPANCY INSPECTION PERFORMED 9/19/13. ADDITIONAL ISSUES MAY BE CITED WHEN READY FOR FORMAL FINAL INSPECTION. DO NOT OCCUPY PRIOR TO APPROVAL.
Misc
Resolved
12/03/2013
CHECK ALL ELECT RECEPTS FOR CORRECT WIRING OPEN GROUND FOUND ON SOME.
Misc
Resolved
12/03/2013
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. USE SPARK RINGS TO RESOLVE WHERE NECESSARY.
Misc
Corrective Action Required
09/19/2013
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SEVERAL ARE NOT SOLID TO BOX; CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Resolved
12/03/2013
NEC 370-25; 410-56 ELECTRICAL RECEPTACLE/SWITCH FACE PLATES: ENSURE ALL BOXES HAVE PLATES IN PLACE.
Misc
Corrective Action Required
09/19/2013
CAUTION TO PERMIT HOLDER / HOMEOWNER: INDUSTRY STANDARD MANUFACTURER INSTRUCTIONS REQUIRE MOUNTING HEIGHT OF CEILING FANS PROVIDE MINIMUM 7' FLOOR-TO-BLADES CLEARANCE; LOWER INSTALLATION COULD RESULT IN PERSONAL INJURY.
Misc
Resolved
12/03/2013
PIPING AT KITCHEN SINK: DISPOSAL DISCHARGE CANNOT BE BELOW ELEVATION OF TRAP ARM. GRAVITY FLOW IS PREVENTED. ENSURE ALL MATERIALS ARE LISTED FOR USE.
Misc
Resolved
12/03/2013
GFI PROTECTION REQUIRED AT ELECT RECEPT ABOVE-RIGHT OF BASEMENT BAR SINK.
Misc
Resolved
12/03/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Resolved
12/03/2013
PROTECTIVE NON-METALLIC BUSHING REQUIRED WHERE NM ELECT CABLE EXITS METALLIC RACEWAY. SEE AT FURNACE.
Misc
Resolved
12/03/2013
NEC 330.30: NON-METALLIC ELECTRICAL WHIP NOT SECURED TO STRUCTURE WITHIN 12" OF ENTRY TO A/C DISCONNECT ENCLOSURE.
Misc
Resolved
12/03/2013
IRC R316.2 STAIR TREAD / RISER / GUARD TRIANGULAR OPENINGS AT OPEN SIDE(S) OF STAIRWAY: OPENINGS MUST NOT ALLOW PASSAGE OF 6" SPHERE
Misc
Resolved
12/03/2013
LSCO 7-915 HANDRAIL AT STAIR MUST BE GRASPABLE: WIDTH OF HANDRAIL ON NON-REQUIRED EXTERIOR STAIR EXCEEDS 3-1/2" ALLOWABLE HORIZONTAL CROSS SECTIONAL DIMENSION. ENDS MUST RETURN TO STRUCTURE.
Misc
Resolved
12/03/2013
DECK FRAMING FASTENERS: EXISTING JOIST HANGERS NOT FULLY SCREWED/NAILED. HARDWARE LISTING IS BASED ON ALL HOLES USED.
Misc
Corrective Action Required
12/03/2013
FLEXIBLE PLUMBING CONNECTORS USED UNDER SINKS DO NOT CONFORM WITH IRC PLUMBING SECTION 3002.
Misc
Corrective Action Required
12/03/2013
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE: SEE AT KITCHEN SINK DISPOSAL UNIT.
Misc
Corrective Action Required
12/03/2013
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Misc
Corrective Action Required
12/03/2013
ELECTRICAL RECEPTACLES AT LAUNDRY ROOM: - RECEPT AT WASHER LOCATION MUST BE GFCI OR BE SINGLE PLUG - RECEPT AT WEST WALL SHOULD BE GFI PROTECTED
Misc
Corrective Action Required
12/03/2013
ELECT RECEPT AT BASEMENT STORAGE ROOM NOT COMPLETED.
Occupancy Inspection - Codes Residential Full C of O 12/12/2013 12/12/2013 at 12:00 AM 12/12/2013
Misc
Resolved
12/12/2013
NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SEVERAL ARE NOT SOLID TO BOX; CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE.
Misc
Resolved
12/12/2013
CAUTION TO PERMIT HOLDER / HOMEOWNER: INDUSTRY STANDARD MANUFACTURER INSTRUCTIONS REQUIRE MOUNTING HEIGHT OF CEILING FANS PROVIDE MINIMUM 7' FLOOR-TO-BLADES CLEARANCE; LOWER INSTALLATION COULD RESULT IN PERSONAL INJURY.
Misc
Resolved
12/12/2013
FLEXIBLE PLUMBING CONNECTORS USED UNDER SINKS DO NOT CONFORM WITH IRC PLUMBING SECTION 3002.
Misc
Resolved
12/12/2013
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE: SEE AT KITCHEN SINK DISPOSAL UNIT.
Misc
Resolved
12/12/2013
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Misc
Resolved
12/12/2013
ELECTRICAL RECEPTACLES AT LAUNDRY ROOM: - RECEPT AT WASHER LOCATION MUST BE GFCI OR BE SINGLE PLUG - RECEPT AT WEST WALL SHOULD BE GFI PROTECTED
Misc
Resolved
12/12/2013
ELECT RECEPT AT BASEMENT STORAGE ROOM NOT COMPLETED.
Documents & Images
Date Uploaded File Type Document Name
09/24/2012 Letter Building Permit
09/24/2012 Activity Document DOC092412-004.pdf
09/24/2012 Plot Plan
12/19/2012 Letter Inspection Summary
01/23/2013 Letter Inspection Summary
02/27/2013 Letter Inspection Summary
03/28/2013 Letter Inspection Summary
08/15/2013 Letter Codes 140 Day Letter
09/19/2013 Letter Inspection Summary
12/03/2013 Letter Inspection Summary
12/12/2013 Letter Field Certificate of Occupancy
12/13/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home