Permit Application Status

PRCOMCOM20215136


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOMCOM20215136
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR IV CENTER HEALTH SPA
10/01/2021
11/15/2021
04/26/2022
03/07/2022
Locations
Contacts
NEW LEAF CONSTRUCTION LLC, Address:38308 EAST CLINE ROAD, Phone:(816) 536-7637  
Shynel.krause@thedripbar.com, Address:Shynel.krause@thedripbar.com  
NEW LEAF CONSTRUCTION LLC, Address:38308 EAST CLINE ROAD, Phone:(816) 536-7637  
NEW LEAF CONSTRUCTION LLC, Address:38308 EAST CLINE ROAD, Phone:(816) 536-7637  
Lasky Architect, PA, Address:3330 NE 34 Street, Phone:(954) 566-5051  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/29/2021 12/29/2021
Michael Weissenbach
Licensed Contractors Approved 11/02/2021 11/11/2021
Joe Frogge
LC - General Contractor
Resolved
11/11/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact. 10/28/21 - acknowledged in letter
LC - MEP Subs
Resolved
11/11/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/28/21 - acknowledged in letter
Building Plan Review Approved 11/09/2021 11/02/2021
Joe Frogge
NEC Article 517.13 Grounding of receptacles patient care
Resolved
11/02/2021

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 10/28/21 - Unable to locate design references for redundant grounding specified in 517.13.
Fire Plan Review Approved with Conditions 11/09/2021 11/02/2021
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
11/02/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
11/02/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for Bio-Hazard containers and/or rooms.
Construction documents - Fire protection systems
Corrective Action Required
11/02/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
11/02/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Alarm Plan Review Released for Construction 11/02/2021 11/02/2021
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
11/02/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fire Plan Review Approved with Conditions 11/03/2021 10/28/2021
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
10/28/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
10/28/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for Bio-Hazard containers and/or rooms.
Construction documents - Fire protection systems
Corrective Action Required
10/28/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/28/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 11/03/2021 10/28/2021
Joe Frogge
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
10/28/2021

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 10/28/21 - Unable to locate design references for redundant grounding specified in 517.13.
Building Plan Review Rejected 11/03/2021 10/28/2021
Joe Frogge
IBC 1209.2 Finish materials
Resolved
10/28/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials within 2' of mop sink and toilet. (not just where mounted - side walls too). If paint is used it must be epoxy based.
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
10/27/2021

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 10/28/21 - Unable to locate design references for redundant grounding specified in 517.13.
Licensed Contractors Rejected 11/03/2021 10/28/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
10/27/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact. 10/28/21 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
10/27/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/28/21 - acknowledged in letter
Fire Plan Review Approved with Conditions 11/03/2021 10/28/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/27/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
10/27/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for Bio-Hazard containers and/or rooms.
Construction documents - Fire protection systems
Corrective Action Required
10/27/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/27/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 10/22/2021 10/18/2021
Joe Frogge
IBC 1209.2 Finish materials
Corrective Action Required
10/18/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials within 2' of mop sink and toilet. (not just where mounted - side walls too). If paint is used it must be epoxy based.
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
10/18/2021

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Licensed Contractors Rejected 10/22/2021 10/18/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
10/18/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Corrective Action Required
10/18/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 10/22/2021 10/14/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/07/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
10/07/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for Bio-Hazard containers and/or rooms.
Construction documents - Fire protection systems
Corrective Action Required
10/07/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/07/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $100.00 $100.00 Paid 11/11/2021
8331507-Sewer Connection Fee $240.00 $240.00 Paid 11/11/2021
7232302-Commercial License Tax Fee $1,080.00 $1,080.00 Paid 10/18/2021
$1,080.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/20/2021 12/20/2021
Underslab Electrical Inspection - Commercial Passed 12/20/2021 12/20/2021
In-wall Inspection Failed 12/20/2021 12/20/2021 12/20/2021
Miscellaneous Correction
Corrective Action Required
12/20/2021
PROVIDE BOCA PLATES DWV BREAK ROOM PROVIDE MIDPOINT SUPPORT VERTICALE DWV 2" & SMALLER PROVIDE PLUMBING PROTECTION PLATES BREAK ROOM PROVIDE BONDING SCREW METAL ELECTRICAL BOXES LAND CONDUCTORS IN A BOX ABOBE FRONT COUNTER
Above Ceiling Inspection Partial 12/21/2021 12/21/2021
Misc
Informational
12/21/2021
OK TO DROP EXISTING CEILING TILES IN AREAS WHERE METAL STUDS RUN ABOVE GRID
In-wall Inspection Passed 12/21/2021 12/21/2021 12/21/2021
Miscellaneous Correction
Resolved
12/21/2021
Alarm Test Passed 2/25/2022 02/25/2022
Occupancy Inspection - Fire Temporary C of O 2/25/2022 2/25/2022 02/25/2022
Corrective Action Required
02/25/2022
Front emergency exterior illumination was not operational. Fire extinguisher needs annual inspection/service.
Above Ceiling Inspection Passed 2/25/2022 02/25/2022
Misc
Informational
12/21/2021
OK TO DROP EXISTING CEILING TILES IN AREAS WHERE METAL STUDS RUN ABOVE GRID
Occupancy Inspection - Codes Commercial Temporary C of O 2/25/2022 2/25/2022 02/25/2022
Miscellaneous Correction
Corrective Action Required
02/25/2022
PROVIDE 18" VERTICAL GRAB BAR RESTROOM PER PLAN INSULATE PLUMBING UNDER RESTROOM VANITY PER PLAN 40' MAX HEIGHT TO REFLECTIVE SURFACE RESTROOM MIRROR PER PLAN REPLACE SECURITY LIGHT ABOVE FRONT ENTRY DOOR PER LS FIRE
Occupancy Inspection - Fire Passed 3/7/2022 3/7/2022 03/07/2022
Occupancy Inspection - Codes Commercial Full C of O 3/7/2022 3/7/2022 03/07/2022
Miscellaneous Correction
Resolved
03/07/2022
Documents & Images
Date Uploaded File Type Document Name
10/01/2021 Application Form App
10/01/2021 Application Form LT
10/14/2021 Engineer Report/Study _Electrical Comcheck
10/14/2021 Engineer Report/Study _Mechanical Comcheck
10/14/2021 Plans 2021-10-14-Dripbar-Lees Summit,MO- Permit set
10/14/2021 Letter Fire Building Plan Review
10/18/2021 Letter DS P/R Corrections Document
10/27/2021 Letter 2021-10-27- Response letter
10/27/2021 Engineer Report/Study 2021-10-14_Dripbar - Lees Summit MO_MEP Permit Set_Mechanical Comcheck
10/27/2021 Engineer Report/Study 2021-08-24_Dripbar - Lees Summit MO_MEP Check Set_Electrical Comcheck
10/27/2021 Plans 2021-10-27-Dripbar- Lees Summit, MO- Rev 1 & 2
10/28/2021 Letter Fire Building Plan Review
10/28/2021 Letter DS P/R Corrections Document
11/02/2021 Letter Fire (Alarm) Plan Review Notice
11/02/2021 Letter Dripbar Lees Summit MO Revision 3- Response Letter
11/02/2021 Plans 2021-11-02-Dripbar- Lees Summit, MO- Revised permit
11/04/2021 Email FW_ DRIPBaR_pdf
11/11/2021 Email Re_ Updated floor plan
11/11/2021 Approved Plans approved Dripbar- Lees Summit, MO- Revised permit
11/11/2021 Receipt Receipt for transaction:2021-008706
12/03/2021 Letter DS Building Permit
12/20/2021 Letter INSPECTION SUMMARY
12/20/2021 Letter INSPECTION SUMMARY
12/20/2021 Letter INSPECTION SUMMARY
12/21/2021 Letter INSPECTION SUMMARY
12/21/2021 Letter INSPECTION SUMMARY
12/21/2021 Letter INSPECTION SUMMARY
12/29/2021 Letter Fire (Sprinkler) Plan Review
02/25/2022 Letter Fire Loss Reduction Form
02/25/2022 Letter INSPECTION SUMMARY
02/25/2022 Letter Codes Temporary Certificate of Occupancy
02/25/2022 Letter Codes Temporary Certificate of Occupancy
03/07/2022 Letter Fire Loss Reduction Form
03/07/2022 Letter Codes Final Certificate of Occupancy
03/28/2022 Letter Codes Temporary Certificate of Occupancy
03/28/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home