Summary
PRCOM20251400
Building Permit - Commercial
Issued
NEW MULTI-FAMILY
THE REUNION AT BLACKWELL - BUILDING 8, TYPE B1 4-PLEX PLAN REVIEW COMPLETED UNDER PRCOM20250089
04/09/2025
06/25/2025
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
RED DOG ELECTRIC SERVICES, Address:PO BOX 1, Phone:(913) 208-4816  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
COLLINS WEBB ARCHITECTURE LLC, Address:307 SW MARKET ST, Unit A, Phone:(816) 249-2270  
Doug Jenson - Avital Homes, Phone:(816) 266-0685  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 04/23/2025 04/09/2025
Mike Weisenborn
Building Plan Review Approved with Conditions 04/14/2025 03/31/2025
Mike Weisenborn
Miscellaneous Correction
Corrective Action Required
04/03/2025

Construction of the attached living unit structure structure has been released. Sanitary and water service connections cannot be made until substantial completion has been issued for the infrastructure.
Licensed Contractors Approved 04/14/2025 03/31/2025
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Water Tap Fee $10,595.00 $10,595.00 Paid 05/22/2025
Water Meter Fee $1,066.76 $1,066.76 Paid 05/22/2025
Sanitary Sewer Development Fee $6,101.00 $6,101.00 Paid 05/22/2025
Residential Excise Tax Fee $2,480.64 $2,480.64 Paid 05/22/2025
Valuation Fee for New 3 or 4 Family $3,998.93 $3,998.93 Paid 05/22/2025
Outstanding Fees Amount Paid Owing Date Paid
Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid
Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid
Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid


$225.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Pending
Piers/Caissons Inspection - Commercial Pending
Rated Assembly Inspection Pending
Misc
Informational
03/05/2026
The following areas inspected -1st layer sheet rock at seperation walls -2nd layer in attic space.
Misc
Informational
03/05/2026
-2nd layer perty fire tape has been inspected ATTIC SPACE 2nd layer screw patern and GB bracing 1st floor
Driveway Inspection Pending 4/2/2026 4/2/2026
Misc
Corrective Action Required
03/26/2026
3/24/26 Tyler S Dw does not have 4" of clean rock. Fail. 3-26-26 Dustin A, Dw has been formed and compacted. Approved to pour This is for 631-625
Footing Inspection - Commercial Partial 6/25/2025 6/25/2025 06/25/2025
Misc
Corrective Action Required
06/25/2025
-footing okay
Footing Inspection - Commercial Partial 7/1/2025 7/1/2025 07/01/2025
Misc
Corrective Action Required
06/25/2025
-footing okay -stem wall okay
Underslab Plumbing Inspection - Commercial Passed 7/23/2025 7/23/2025 07/23/2025
Underslab Electrical Inspection - Commercial Passed 7/23/2025 7/23/2025 07/23/2025
Sewer Service Inspection Passed 7/23/2025 7/23/2025 07/23/2025
Misc
Corrective Action Required
07/23/2025
4-23-25 Dustin A, Sewer connection is installed per city specs
Footing Inspection - Commercial Passed 7/24/2025 7/24/2025 07/24/2025
Misc
Resolved
07/24/2025
-footing okay -stem wall okay -thickened slab areas okay
Water Service Inspection Passed 10/15/2025 10/15/2025
Misc
Corrective Action Required
10/15/2025
10-15-25 Dustin A, Water service is installed up to 10 ft out of the pit.
Rated Assembly Inspection Not Ready 10/15/2025 10/15/2025 10/15/2025
Misc
Corrective Action Required
10/15/2025
-Provide city stamped plans on site -Remove penetrations in fire rated walls -cover truss ends at fire rated walls
Rated Assembly Inspection Partial 10/24/2025 10/24/2025 10/24/2025
Misc
Informational
10/24/2025
exterior sheathing okay to cover
All Rough Inspection - Commercial Failed 12/18/2025 12/18/2025 12/18/2025
Misc
Corrective Action Required
12/18/2025
-nail all double trusses together to plans Check truss bracing 625 -move smoke inside bedroom(cannot be within 3’ of bathroom) 627 -protect all wires within 6’ of attic access -fireblock top of dead space at entry bath -address 2x12 attached to double trusses rear of unit truss FL -remove foam at bedroom bath vanity furr out wall to allow for separation wall sheet rock 629 -missing (6) stud pack NW garage wall -seal top plate penetration for doorbell -remove foam at bedroom bath vanity furr out wall to allow for separation wall sheet rock -bath vent duct may not be secured to separation wall -add scabbed 2x onto FL truss and J2 trusses landing on and not using hangers to plans 631 -protect wires about service panel at top plate -remove foam at top plate for furr out wall at separation wall to allow for sheet rock
All Rough Inspection - Commercial Passed 1/20/2026 1/20/2026 01/20/2026
Misc
Resolved
01/20/2026
-nail all double trusses together to plans Check truss bracing 625 -move smoke inside bedroom(cannot be within 3’ of bathroom) 627 -protect all wires within 6’ of attic access -fireblock top of dead space at entry bath -address 2x12 attached to double trusses rear of unit truss FL -remove foam at bedroom bath vanity furr out wall to allow for separation wall sheet rock 629 -missing (6) stud pack NW garage wall -seal top plate penetration for doorbell -remove foam at bedroom bath vanity furr out wall to allow for separation wall sheet rock -bath vent duct may not be secured to separation wall -add scabbed 2x onto FL truss and J2 trusses landing on and not using hangers to plans 631 -protect wires about service panel at top plate -remove foam at top plate for furr out wall at separation wall to allow for sheet rock
Electrical Service Inspection Failed 1/22/2026 1/22/2026 01/22/2026
Misc
Corrective Action Required
01/22/2026
-no more than one conductor per lug in panel -copper main bonding jumper shall be minimum #4 -remove all bonding screws past main disconnect
Electrical Service Inspection Not Ready 1/23/2026 1/23/2026 01/23/2026
Misc
Corrective Action Required
01/22/2026
-no more than one conductor per lug in panel -copper main bonding jumper shall be minimum #4 -remove all bonding screws past main disconnect
Rated Assembly Inspection Failed 2/10/2026 2/10/2026 02/10/2026
Misc
Corrective Action Required
02/10/2026
Stud spacing above garages grater than 16” OC for separation wall screw pattern
Rated Assembly Inspection Partial 2/12/2026 2/12/2026 02/12/2026
Misc
Informational
02/12/2026
1st layer sheet rock at seperation walls
Electrical Service Inspection Not Ready 2/12/2026 2/12/2026 02/12/2026
Misc
Corrective Action Required
01/23/2026
-remove all bonding screws past main disconnect
Electrical Service Inspection Passed 2/13/2026 2/13/2026 02/13/2026
Misc
Resolved
02/13/2026
-remove all bonding screws past main disconnect
Rated Assembly Inspection Partial 2/17/2026 2/17/2026 02/17/2026
Misc
Informational
02/12/2026
The following areas inspected -1st layer sheet rock at seperation walls -2nd layer in attic space.
Rated Assembly Inspection Partial 2/25/2026 2/25/2026 02/25/2026
Misc
Informational
02/17/2026
The following areas inspected -1st layer sheet rock at seperation walls -2nd layer in attic space.
Misc
Informational
02/25/2026
-2nd layer perty fire tape has been inspected
Rated Assembly Inspection Partial 3/5/2026 3/5/2026 03/05/2026
Misc
Informational
02/25/2026
The following areas inspected -1st layer sheet rock at seperation walls -2nd layer in attic space.
Misc
Informational
02/25/2026
-2nd layer perty fire tape has been inspected ATTIC SPACE 2nd layer screw patern and GB bracing 1st floor
Driveway Inspection Failed 3/24/2026 3/24/2026 03/24/2026
Misc
Corrective Action Required
03/24/2026
3/24/26 Tyler S Dw does not have 4" of clean rock. Fail.
Driveway Inspection Partial 3/26/2026 3/26/2026 03/26/2026
Misc
Corrective Action Required
03/24/2026
3/24/26 Tyler S Dw does not have 4" of clean rock. Fail. 3-26-26 Dustin A, Dw has been formed and compacted. Approved to pour This is for 631-625
Documents & Images
Date Uploaded File Type Document Name
05/22/2025 Receipt Receipt for transaction:2025-003748
05/22/2025 Letter DS Building Permit
06/25/2025 Plans 25-0227_23090 Blackwell_Struct_Rev#3 (Footing Changes)
06/25/2025 Letter 25-0227_Reunion at Blackwell_Struct_Rev#3 Narrative (Footing Change)
06/25/2025 Letter INSPECTION SUMMARY
06/27/2025 Approved Plans Approved struct revisions
03/31/2025 Approved Plans Approved plans V1
07/23/2025 Letter INSPECTION SUMMARY
07/23/2025 Letter INSPECTION SUMMARY
07/23/2025 Letter INSPECTION SUMMARY
07/23/2025 Letter INSPECTION SUMMARY
07/24/2025 Letter INSPECTION SUMMARY
10/15/2025 Letter INSPECTION SUMMARY
10/15/2025 Letter INSPECTION SUMMARY
11/05/2025 Approved Plans Approved G111
11/06/2025 Approved Plans Approved trusses B1
11/17/2025 Approved Plans Truss repair doc
11/21/2025 Approved Plans Approved Trusses B2
12/08/2025 Approved Plans Approved E200 revision
12/18/2025 Letter INSPECTION SUMMARY
12/18/2025 Letter INSPECTION SUMMARY
01/05/2026 Approved Plans Approved - Roof truss fix PRCOM20251400
01/20/2026 Approved Plans Approved truss repairs bldg 8B
01/20/2026 Letter INSPECTION SUMMARY
01/23/2026 Letter INSPECTION SUMMARY
01/23/2026 Letter INSPECTION SUMMARY
02/09/2026 Approved Plans REUNION GRADING PLA
02/10/2026 Letter INSPECTION SUMMARY
02/12/2026 Letter INSPECTION SUMMARY
02/12/2026 Letter INSPECTION SUMMARY
02/17/2026 Letter INSPECTION SUMMARY
02/17/2026 Letter INSPECTION SUMMARY
02/25/2026 Letter INSPECTION SUMMARY
03/24/2026 Letter INSPECTION SUMMARY
03/24/2026 Letter INSPECTION SUMMARY
03/26/2026 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home