Permit Application Status

PRCOM20251309


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20251309
Building Permit - Commercial
Issued
REORGANIZED SCHOOL DIST NO 7
NEW OTHER (COMMERCIAL)
MOBILE CLASSROOM
04/04/2025
07/01/2025
10/15/2025
Locations
Contacts
PALOMAR MODULAR BUILDINGS LLC, Address:P O BOX 909, Phone:(469) 727-0727  
Kent Anderson, Address:Lee's Summit R-7 School District, Phone:(816) 986-2431  
LEES SUMMIT SCHOOL DIST R 7, Address:600 MILLER  
REORGANIZED SCHOOL DIST NO 7, Address:600 SE MILLER ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 06/04/2025 06/04/2025
Craig Hill
Access roads required for building and facilities
Resolved
06/04/2025

2018 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. The unit shall be relocated to be within 150 of an approved fire lane.
Hydrant required
Resolved
06/04/2025

2018 IFC 508.5.1 -Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Exceptions: 1. For Group R-3 and Group U occupancies, the distance requirement shall be 600 feet (183 m). The unit shall be relocated to be within 300 feet of a hydrant.
Miscellaneous Correction
Corrective Action Required
05/28/2025

The fire alarm in the unit shall be connected to the building's fire alarm system. Call (816) 969-1300 to schedule testing.
Building Plan Review Approved 06/04/2025 05/30/2025
Joe Frogge
Licensed Contractors Approved 06/04/2025 05/30/2025
Joe Frogge
LC - General Contractor
Resolved
05/30/2025

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact.
Fire Plan Review Rejected 04/18/2025 04/18/2025
Jim Eden
Access roads required for building and facilities
Corrective Action Required
04/18/2025

2018 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. The unit shall be relocated to be within 150 of an approved fire lane.
Hydrant required
Corrective Action Required
04/18/2025

2018 IFC 508.5.1 -Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Exceptions: 1. For Group R-3 and Group U occupancies, the distance requirement shall be 600 feet (183 m). The unit shall be relocated to be within 300 feet of a hydrant.
Miscellaneous Correction
Corrective Action Required
04/18/2025

The fire alarm in the unit shall be connected to the building's fire alarm system.
Building Plan Review Approved 04/18/2025 04/14/2025
Joe Frogge
Licensed Contractors Rejected 04/18/2025 04/14/2025
Joe Frogge
LC - General Contractor
Corrective Action Required
04/14/2025

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Other $90.00 $90.00 Paid 07/01/2025
$0.00
Commercial Excise Tax Fee $2,219.25 $2,219.25 Paid 04/04/2025
$2,219.25
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Commercial Pending
Rough Electrical Inspection - Commercial Pending
Piers/Caissons Inspection - Commercial Pending
Foundation Inspection - Commercial Pending
Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home