Building Permit - Commercial
Approved
NEW OTHER (COMMERCIAL)
NEW POOL AND SPA SERVING NEW APARTMENT COMPLEX
08/13/2024
02/23/2025
Locations
Contacts
Streamline General Contractors, Address:5 4TH ST SW  
scott@griffinriley.com  
KDM ELECTRICAL CONTRACTORS, Address:1103 NW CASEY BLVD STE C, Phone:(816) 443-5694  
B+A Architecture, Address:600 Broadway Blvd, Suite 290, Phone:(816) 753-6100  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 09/12/2024 09/10/2024
Craig Hill
Building Plan Review Approved with Conditions 09/12/2024 09/09/2024
Joe Frogge
Health Dept Review (aquatic)
Resolved
09/09/2024

For the Health Department review of public pools contact Casey Elledge with the Jackson County Public Works Department, Environmental Services Division, at (816) 223-9769. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection (aquatic)
Corrective Action Required
09/05/2024

For the Health Department inspection of public pools contact Casey Elledge with the Jackson County Public Works Department, Environmental Health Division at (816) 223-9769. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 9/9/24 - Acknowledged in letter.
IBC 1011.11 Handrails - handrails at stairways
Resolved
09/09/2024

City of Lee's Summit Code of Ordinances Sec. 7-1010. - steps or ladders. Two (2) or more means of egress in the form of steps or ladders shall be provided for all swimming pools. At least one such means of egress shall be located on a side of the pool at both the deep end and shallow end of the pool. Treads of steps and ladders shall be constructed of nonslip material and at least three (3) inches wide for their full length. Steps and ladders shall have a handrail on both sides. Action required: Provide handrails at both sides of stairs.
Health Department Review Approved 09/09/2024
Joe Frogge
Licensed Contractors Approved 09/12/2024 09/09/2024
Joe Frogge
Fire Plan Review Rejected 08/27/2024 08/27/2024
Joe Frogge
Miscellaneous Correction
Corrective Action Required
08/27/2024

[BE] 1010.1.10 Panic and fire exit hardware. Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware. Action required: Provide panic hardware on the gates exiting the pool deck.
r
Building Plan Review Rejected 08/27/2024 08/27/2024
Joe Frogge
Health Dept Review (aquatic)
Corrective Action Required
08/27/2024

For the Health Department review of public pools contact Casey Elledge with the Jackson County Public Works Department, Environmental Services Division, at (816) 223-9769. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection (aquatic)
Corrective Action Required
08/27/2024

For the Health Department inspection of public pools contact Casey Elledge with the Jackson County Public Works Department, Environmental Health Division at (816) 223-9769. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IBC 1011.11 Handrails - handrails at stairways
Corrective Action Required
08/27/2024

City of Lee's Summit Code of Ordinances Sec. 7-1010. - steps or ladders. Two (2) or more means of egress in the form of steps or ladders shall be provided for all swimming pools. At least one such means of egress shall be located on a side of the pool at both the deep end and shallow end of the pool. Treads of steps and ladders shall be constructed of nonslip material and at least three (3) inches wide for their full length. Steps and ladders shall have a handrail on both sides. Action required: Provide handrails at both sides of stairs.
Fire Plan Review Rejected 08/27/2024 08/26/2024
Craig Hill
Miscellaneous Correction
Corrective Action Required
08/26/2024

[BE] 1010.1.10 Panic and fire exit hardware. Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware. Action required: Provide panic hardware on the gates exiting the pool deck.
Building Plan Review Rejected 08/27/2024 08/21/2024
Joe Frogge
Health Dept Review (aquatic)
Corrective Action Required
08/21/2024

For the Health Department review of public pools contact Casey Elledge with the Jackson County Public Works Department, Environmental Services Division, at (816) 223-9769. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection (aquatic)
Corrective Action Required
08/21/2024

For the Health Department inspection of public pools contact Casey Elledge with the Jackson County Public Works Department, Environmental Health Division at (816) 223-9769. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IBC 1011.11 Handrails - handrails at stairways
Corrective Action Required
08/21/2024

City of Lee's Summit Code of Ordinances Sec. 7-1010. - steps or ladders. Two (2) or more means of egress in the form of steps or ladders shall be provided for all swimming pools. At least one such means of egress shall be located on a side of the pool at both the deep end and shallow end of the pool. Treads of steps and ladders shall be constructed of nonslip material and at least three (3) inches wide for their full length. Steps and ladders shall have a handrail on both sides. Action required: Provide handrails at both sides of stairs.
Final Development Plan Review Approved 08/27/2024 08/13/2024
Joe Frogge
Licensed Contractors Approved 08/27/2024 08/13/2024
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
None $0.00 $0.00 $0.00
Outstanding Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $2,182.50 $0.00 $2,182.50 Not Paid


$2,182.50    Add Fees to My Cart
Inspections

There are no inspections for this permit application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home