Permit Application Status

PRCOM20231468


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20231468
Building Permit - Commercial
Expired
DH4 HOLDINGS LLC
ALTERATION COMMERCIAL
ROOF MOUNTED SOLAR - 99.62 KW
04/05/2023
05/30/2023
Locations
Contacts
DH4 HOLDINGS LLC, Address:10624 S EASTERN AVE STE A-975  
Midwest Karting LLC, Address:2911 INDEPENDENCE AVE NE  
DEBBIE.HILL@MIDWESTKARTING.COM  
SUN SOLAR, Address:6724 HWY 63, Phone:(417) 413-1786  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 05/15/2023 05/18/2023
Andrea Sessler
Fire Plan Review Approved 05/15/2023 05/16/2023
Jim Eden
Licensed Contractors Approved 05/03/2023
Andrea Sessler
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $600.30 $600.30 Paid 05/22/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Electrical Inspection - Commercial Pending
Misc
Corrective Action Required
08/14/2023
-Provide permanent plaque required per NEC 705 -Provide PV warning labels for DC raceway at maximum 10 ft interval -Provide all required labels per plan -Provide proper bonding connection at AC disconnect. Either remove enamel between lug and disconnect enclosure for direct metal-metal contact or install proper bonding screw, not sheet metal screw
Miscellaneous Inspection Pending
Final Inspection - Commercial Pending
Electrical Service Inspection Pending 10/4/2023
Misc
Corrective Action Required
08/14/2023
**See Final Electrical inspection
Sidewalk Inspection Partial 06/08/2023
Misc
Corrective Action Required
06/08/2023
6-6-23 NS Sidewalk was poured with out a pre-pour inspection. Once the concrete has been cured and do a final inspection.
Sidewalk Inspection Failed 6/8/2023 6/8/2023 06/08/2023
Misc
Corrective Action Required
06/08/2023
6-6-23 NS Sidewalk was poured with out a pre-pour inspection. Once the concrete has been cured and do a final inspection. 6-8-23 NS Site visited Sidewalk ramp did not pass ADA. There is no 5 foot turn around for a person that is in a wheel chair. This will need to be tore out and replaced to meet ADA standards. Please call me Nick Scott at 816-977-5652 to meet up and I can explain what needs to change.
Sidewalk Inspection Passed 08/14/2023
Misc
Resolved
08/14/2023
Final Electrical Inspection - Commercial Failed 8/14/2023 8/14/2023 08/14/2023
Misc
Corrective Action Required
08/14/2023
-Provide permanent plaque required per NEC 705 -Provide PV warning labels for DC raceway at maximum 10 ft interval -Provide all required labels per plan -Submit revised plan on DC raceway and correct DC conductors size -Provide proper bonding connection at AC disconnect. Either remove enamel between lug and disconnect enclosure for direct metal-metal contact or install proper bonding screw, not sheet metal screw
Electrical Service Inspection Failed 8/14/2023 8/14/2023 08/14/2023
Misc
Corrective Action Required
08/14/2023
**See Final Electrical inspection
Fire Department Solar Inspection Passed 8/14/2023 8/14/2023 08/16/2023
Miscellaneous Inspection Failed 4/4/2024 04/04/2024
Informational
04/04/2024
4/4/24-Left a msg about the expired permit
Documents & Images
Date Uploaded File Type Document Name
04/05/2023 Application Form Lees Summit Photovoltaic System Permit Application Complete
05/15/2023 Plans MidWest Karting stamped CL and PS
05/18/2023 Approved Plans approved - MidWest Karting stamped CL and PS
05/22/2023 Receipt Receipt for transaction:2023-003522
06/01/2023 Letter DS Building Permit
06/08/2023 Letter INSPECTION SUMMARY
06/08/2023 Letter INSPECTION SUMMARY
08/14/2023 Letter INSPECTION SUMMARY
08/14/2023 Letter INSPECTION SUMMARY
08/14/2023 Letter INSPECTION SUMMARY
08/21/2023 Approved Plans approved - As Built for City Inspection
09/19/2023 Letter INSPECTION SUMMARY
01/03/2024 Letter Codes 140 Day Letter
02/12/2024 Letter Codes 180 Day Letter
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home