Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
04/13/2023
|
04/07/2023
|
|
Jim Eden
|
|
Address numbers required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required- The business shall use one address. All front ant rear doors shall be marked accordingly. Verified at inspection.
|
|
Portable fire extinguishers - general
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide a minimum of one, 2A:10B:C fire extinguisher in the space.
|
|
Direction of swing
2018 IFC 1010.1.2.1 Direction of swing. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Action required- If left, the front door shall swing outward.
|
|
Miscellaneous Correction
Provide Exit lighting over the cased opening from the new to the existing space.
|
|
Miscellaneous Correction
Provide a Code Analysis for the project including the existing space.
|
|
Miscellaneous Correction
What is the width of the new cased opening and what is the exiting capacity of the existing space? The exit on the front of the existing space is not shown.
For information only- Verified at inspection.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
Action required- The fire alarm and fire sprinkler system shall have documentation of a current annual inspection. Verified at inspection.
|
|
|
Building Plan Review
|
Approved with Conditions
|
04/13/2023
|
04/06/2023
|
|
Joe Frogge
|
|
Code analysis required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Actions required:
-
- Include entire suite in occupancy calculations so we can verify restroom fixture quantities. Also, show existing restroom fixtures. (existing bar has occupant load of 104 - total will be 176)
|
|
IBC 1010.1.2 Door swing - direction of swing egress travel
2018 IBC 1010.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.)
2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Action required: Rear door must swing outwards.
|
|
Suite address
This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located.
Action required: Update records to show correct address which is 3512.
|
|
IBC 1013.1 Where required - exit sign
Corrective Action Required
2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions)
Action required: Provide exit and emergency lighting.
4/6/23 - field verify
|
|
Misc
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted.
Action require: Comment is for informational purposes. After credit for previous office occupant the fee will be $14,990.25
4/6/23 - aknowledged in letter
|
|
|
Licensed Contractors
|
Approved
|
04/13/2023
|
04/06/2023
|
|
Joe Frogge
|
|
|
Licensed Contractors
|
Approved
|
03/30/2023
|
03/30/2023
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Rejected
|
03/30/2023
|
03/29/2023
|
|
Jim Eden
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required- The business shall use one address. All front ant rear doors shall be marked accordingly. Verified at inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide a minimum of one, 2A:10B:C fire extinguisher in the space.
|
|
Direction of swing
Corrective Action Required
2018 IFC 1010.1.2.1 Direction of swing. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Action required- If left, the front door shall swing outward.
|
|
Miscellaneous Correction
Corrective Action Required
Provide Exit lighting over the cased opening from the new to the existing space.
|
|
Miscellaneous Correction
Corrective Action Required
Provide a Code Analysis for the project including the existing space.
|
|
Miscellaneous Correction
Corrective Action Required
What is the width of the new cased opening and what is the exiting capacity of the existing space? The exit on the front of the existing space is not shown.
For information only- Verified at inspection.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
Action required- The fire alarm and fire sprinkler system shall have documentation of a current annual inspection. Verified at inspection.
|
|
|
Building Plan Review
|
Rejected
|
03/30/2023
|
03/24/2023
|
|
Joe Frogge
|
|
Code analysis required
Corrective Action Required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Actions required:
- Updated Code Information with correct construction type which is 5B.
- Include entire suite in occupancy calculations so we can verify restroom fixture quantities. Also, show existing restroom fixtures. (existing bar has occupant load of 104 - total will be 176)
|
|
IBC 1010.1.2 Door swing - direction of swing egress travel
Corrective Action Required
2018 IBC 1010.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.)
2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Action required: Rear door must swing outwards.
|
|
Suite address
Corrective Action Required
This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located.
Action required: Update records to show correct address which is 3512.
|
|
IBC 1013.1 Where required - exit sign
Corrective Action Required
2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions)
Action required: Provide exit and emergency lighting.
|
|
Misc
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted.
Action require: Comment is for informational purposes. After credit for previous office occupant the fee will be $14,990.25
|
|
|
Zoning Review
|
Approved
|
03/30/2023
|
03/20/2023
|
|
Joe Frogge
|
|
|