Summary
PRCOM20230899
Building Permit - Commercial
Withdrawn
NEW OTHER (COMMERCIAL)
SOUTH RESTROOM BUILDING SERVING SOCCER FIELDS ADJACENT TO FIELD 9
03/03/2023
09/12/2023
Locations
Contacts
FOGEL-ANDERSON CONSTRUCTION CO, Address:1212 E 8TH ST, Phone:(816) 842-6914  
Casey Williams, Address:cwilliams@fogel-anderson.com, Phone:(816) 935-4239  
Finkle + Williams Architecture, Address:8787 Renner Blvd. Suite 100, Phone:(913) 498-1550  
  
  
  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 04/20/2023 07/14/2023
Joe Frogge
Gen - Plan submittals 2018 codes
Resolved
04/14/2023

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Comment is informational. Plans are reviewed and inspected for compliance with 2017 NEC. (2015 shown in Building Summary)
IPC 403.2 Separate facilities
Resolved
07/14/2023

2018 IPC 403.2 Separate Facilities. (As amended by Lee’s Summit Code of Ordinances Section 7-405) Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions: 1. Separate facilities shall not be required for dwelling units and sleeping units. 2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer. 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer. 4. Separate facilities shall not be required in business occupancies in which the maximum occupant load is 25 or fewer. Action required: Provide separated lavatories per gender or apply for Code Modification Request (CMR) to appeal for use of 2021 code cycle. 4/14/23 - CMR submitted and under review.
MISC
Resolved
07/14/2023

Sec. 7-803. - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: Exception: The Building Official may approve a decreased R-Value for building exterior walls provided the space is normally not occupied by employees and is associated with storage/warehouse or manufacturing. A.Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or other openings or approved penetrations nor does it apply to unfinished basement concrete walls. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor 19. Action required: Provide minimum R11 at walls. 4/14/23 - CMR submitted and under review.
Fire Plan Review Approved with Conditions 04/20/2023 04/14/2023
Joe Frogge
Portable fire extinguishers - general
Corrective Action Required
04/14/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Provide a 2A:10B:C fire extinguisher. Verified at inspection.
Licensed Contractors Rejected 04/20/2023 04/14/2023
Joe Frogge
LC - MEP Subs
Corrective Action Required
04/13/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 4/14/2023 - acknowledged in letter.
Fire Plan Review Approved with Conditions 03/17/2023 03/15/2023
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
03/15/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Provide a 2A:10B:C fire extinguisher. Verified at inspection.
Building Plan Review Rejected 03/17/2023 03/14/2023
Joe Frogge
Gen - Plan submittals 2018 codes
Corrective Action Required
03/14/2023

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Comment is informational. Plans are reviewed and inspected for compliance with 2017 NEC. (2015 shown in Building Summary)
IPC 403.2 Separate facilities
Corrective Action Required
03/14/2023

2018 IPC 403.2 Separate Facilities. (As amended by Lee’s Summit Code of Ordinances Section 7-405) Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions: 1. Separate facilities shall not be required for dwelling units and sleeping units. 2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer. 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer. 4. Separate facilities shall not be required in business occupancies in which the maximum occupant load is 25 or fewer. Action required: Provide separated lavatories per gender or apply for Code Modification Request (CMR) to appeal for use of 2021 code cycle.
Misc
Corrective Action Required
03/14/2023

Sec. 7-803. - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: Exception: The Building Official may approve a decreased R-Value for building exterior walls provided the space is normally not occupied by employees and is associated with storage/warehouse or manufacturing. A.Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or other openings or approved penetrations nor does it apply to unfinished basement concrete walls. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor 19. Action required: Provide minimum R11 at walls.
Final Development Plan Review Approved 03/17/2023 03/14/2023
Joe Frogge
Licensed Contractors Rejected 03/17/2023 03/14/2023
Joe Frogge
LC - MEP Subs
Corrective Action Required
03/14/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Inspections

There are no inspections for this permit application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents