Summary
PRCOM20225518
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
TENANT FINISH FOR REAL ESTATE OFFICE STOP WORK ORDER generated on 11/16/2022 12:00 AM by username 'Sara Beck'. STOP WORK ORDER removed on 11/16/2022 12:00 AM by username 'Sara Beck'.
11/02/2022
11/16/2022
12/09/2022
Locations
Contacts
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
PACT CONSTRUCTION SERVICES, Address:1280 NE DELTA SCHOOL RD, Phone:(816) 287-3030  
JEREMY@PACTKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 11/14/2022 11/09/2022
Joe Frogge
Fire Plan Review Approved with Conditions 11/14/2022 11/07/2022
Jim Eden
Address numbers required
Corrective Action Required
11/07/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The address (numbers) shall be posted on the front and rear doors. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
11/07/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one, 2A-10B-C fire extinguisher at a conspicuous location in a normal path of travel. Verified at inspection.
Misc
Corrective Action Required
11/07/2022

All existing conditions i.e. locks, exits signs and emergency lighting will be verified at inspection.
Licensed Contractors Approved 11/14/2022 11/02/2022
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $50.00 $50.00 Paid 11/16/2022
7232302-Commercial License Tax Fee $2,623.50 $2,623.50 Paid 12/12/2022
$643.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 11/18/2022 11/18/2022 11/18/2022
Misc
Corrective Action Required
11/18/2022
NO ACCESS CALLED MICAH NO ANSWERCELL & WEBEX Michael Harkins 11/18/2022 10:06 AM
In-wall Inspection Passed 11/21/2022 11/21/2022 11/21/2022
Misc
Corrective Action Required
11/18/2022
NO ACCESS CALLED MICAH NO ANSWERCELL & WEBEX Michael Harkins 11/18/2022 10:06 AM
Occupancy Inspection - Codes Commercial Failed 12/13/2022 12/13/2022 12/13/2022
Miscellaneous Correction
Corrective Action Required
12/13/2022
-Complete all corrections for LSFD -Provide 36” working space at electrical panel-Unable to inspect panel at this time, ensure schedule is in place and up to date -Provide restroom signage -Mirror to be max 40” aff to reflective surface -Provide 18” vertical grab bar -Provide open face toilet seat -Provide plumbing protection at sink
Occupancy Inspection - Fire Failed 12/13/2022 12/13/2022 12/13/2022
Corrective Action Required
12/13/2022
Electrical panel was blocked. 36” clearance is required in front of the panel. No fire extinguisher. Rear exit light did not operate properly.
Occupancy Inspection - Codes Commercial Full C of O 12/15/2022 12/15/2022 12/15/2022
Miscellaneous Correction
Resolved
12/15/2022
-Complete all corrections for LSFD -Provide 36” working space at electrical panel-Unable to inspect panel at this time, ensure schedule is in place and up to date -Provide restroom signage -Mirror to be max 40” aff to reflective surface -Provide 18” vertical grab bar -Provide open face toilet seat -Provide plumbing protection at sink
Occupancy Inspection - Fire Passed 12/15/2022 12/15/2022 12/15/2022
Documents & Images
Date Uploaded File Type Document Name
11/02/2022 Application Form DETAIL SHEET
11/02/2022 Application Form APPLICATION
11/02/2022 Drawing DRAWING
11/02/2022 Letter License Tax Bill
11/04/2022 Email architect waiver
11/09/2022 Approved Plans approved - DRAWING
11/16/2022 Receipt Receipt for transaction: 2022-008985
11/16/2022 Letter DS Building Permit
11/21/2022 Letter INSPECTION SUMMARY
12/12/2022 Receipt Receipt for transaction: 2022-009424
12/13/2022 Letter INSPECTION SUMMARY
12/13/2022 Letter INSPECTION SUMMARY
12/15/2022 Letter Codes Final Certificate of Occupancy
12/15/2022 Letter Field Certificate of Occupancy
12/15/2022 Letter Fire Loss Reduction Form
12/15/2022 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home