Review Type |
Outcome |
Est. Completion Date |
Completed |
Building Plan Review
|
Approved with Conditions
|
09/08/2022
|
09/15/2022
|
|
Mike Weisenborn
|
|
Final Development Plan
The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan.
Action required: Comment is for informational purposes.
8/22/22 - not addressed
9/1/22 - acknowledged in letter
|
|
Health Dept Inspection
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
8/22/22 - not addressed
9/1/22 - acknowledged in letter
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required: Provide complete truss package or request deferral. (must be approved by architect before submitting to us)
8/22/22 - not addressed
9/1/22 - deferred per request
|
|
IBC 1103.1 Where required - accessibility
2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities.
2018 IBC 1103.2.2 Employee work areas. Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.1, 1009 and 1104.3.1 and shall be designed and constructed so that individual with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, other than raised courtroom stations in accordance with Section 1108.4.1.4, that are less than 300 square feet in area and located 7 inches or more above or below the ground or finished floor where the change in elevation is essential to the function of the space shall be exempt from all requirements.
(see code for additional exemptions)
Action required: Swinging door into employee work area not compliant in that it does not have the minimum 18" clearance at the latch side per ICC A117.1-2009 Section 404.2.3.2.
8/22/22 - not addressed
|
|
Miscellaneous Correction
Inadequate information to complete review:
Provide the following:
- Provide complete roof access details including ladder, roof hatch, and 30" side rail ladder extension. Reflected ceiling plan and truss plans also affected.
8/22/22 - not addressed
- Furnace installation details. (truss mounted? Is this unit rated to be installed for horizontal flow? Looks like an upflow unit.)
8/22/22 - not addressed
- Furnace flue complete design.
8/22/22 - not addressed
|
|
IPC 802.1 Indirect/special waste
2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dishwashing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7.
Action required: Provide floor sink at 3 compartment sink to facilitate indirect drain.
8/22/22 - not addressed
|
|
IPC 708.1 Cleanouts required
2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11.
2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access.
action required: Provide cleanout near where sanitary leaves foundation.
8/22/22 - not addressed
|
|
|
Final Development Plan Review
|
Approved
|
10/07/2022
|
09/15/2022
|
|
Mike Weisenborn
|
|
GROUND ROOTS COFFEE
|
Licensed Contractors
|
Approved
|
09/08/2022
|
09/01/2022
|
|
Joe Frogge
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. (Dye Electric not licensed with us)
9/1/22 - Dye Electric still not licensed with us
|
|
|
Fire Plan Review
|
Approved
|
09/08/2022
|
09/01/2022
|
|
Joe Frogge
|
|
Illumination required
[BE] 1008.3.2 Buildings. In the event of power supply
failure, in buildings that require two or more means of
egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Interior exit access stairways and ramps
2. Interior and exterior exit stairways and ramps.
3. Exit passageways.
4. Vestibules and areas on the level of discharge used
for exit discharge in accordance with Section
1028.1.
5. Exterior landings as required by Section 1010.1.6
for exit doorways that lead directly to the exit discharge.
Action required- Provide emergency power for illumination of the exit discharge.
|
|
|
Building Plan Review
|
Rejected
|
08/26/2022
|
08/22/2022
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan.
Action required: Comment is for informational purposes.
8/22/22 - not addressed
|
|
Health Dept Review
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
8/22/22 - not addressed
|
|
Code analysis required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Actions required:
- Modify Code Review to show correct occupancy classification which is B. (see 2018 IBC 303.1.1)
- Modify Code Review to show correct occupant load calculations. Sales area (1:60) is restricted to area north of counter with product displays. Area with seating to be calculated as Loose Tables & Chairs (1:15)
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required: Provide complete truss package or request deferral. (must be approved by architect before submitting to us)
8/22/22 - not addressed
|
|
IBC 1103.1 Where required - accessibility
Corrective Action Required
2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities.
2018 IBC 1103.2.2 Employee work areas. Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.1, 1009 and 1104.3.1 and shall be designed and constructed so that individual with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, other than raised courtroom stations in accordance with Section 1108.4.1.4, that are less than 300 square feet in area and located 7 inches or more above or below the ground or finished floor where the change in elevation is essential to the function of the space shall be exempt from all requirements.
(see code for additional exemptions)
Action required: Swinging door into employee work area not compliant in that it does not have the minimum 18" clearance at the latch side per ICC A117.1-2009 Section 404.2.3.2.
8/22/22 - not addressed
|
|
Miscellaneous Correction
Corrective Action Required
Inadequate information to complete review:
Provide the following:
- Provide complete roof access details including ladder, roof hatch, and 30" side rail ladder extension. Reflected ceiling plan and truss plans also affected.
8/22/22 - not addressed
- Furnace installation details. (truss mounted? Is this unit rated to be installed for horizontal flow? Looks like an upflow unit.)
8/22/22 - not addressed
- Furnace flue complete design.
8/22/22 - not addressed
|
|
IPC 802.1 Indirect/special waste
Corrective Action Required
2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dishwashing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7.
Action required: Provide floor sink at 3 compartment sink to facilitate indirect drain.
8/22/22 - not addressed
|
|
IPC 708.1 Cleanouts required
Corrective Action Required
2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11.
2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access.
action required: Provide cleanout near where sanitary leaves foundation.
8/22/22 - not addressed
|
|
|
Fire Plan Review
|
Rejected
|
08/26/2022
|
08/22/2022
|
|
Joe Frogge
|
|
Illumination required
Corrective Action Required
[BE] 1008.3.2 Buildings. In the event of power supply
failure, in buildings that require two or more means of
egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Interior exit access stairways and ramps
2. Interior and exterior exit stairways and ramps.
3. Exit passageways.
4. Vestibules and areas on the level of discharge used
for exit discharge in accordance with Section
1028.1.
5. Exterior landings as required by Section 1010.1.6
for exit doorways that lead directly to the exit discharge.
Action required- Provide emergency power for illumination of the exit discharge.
|
|
|
Licensed Contractors
|
Rejected
|
08/26/2022
|
08/22/2022
|
|
Joe Frogge
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. (Dye Electric not licensed with us)
|
|
|
Health Department Review
|
Approved
|
|
08/19/2022
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
06/30/2022
|
06/27/2022
|
|
Jim Eden
|
|
Illumination required
Corrective Action Required
[BE] 1008.3.2 Buildings. In the event of power supply
failure, in buildings that require two or more means of
egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Interior exit access stairways and ramps
2. Interior and exterior exit stairways and ramps.
3. Exit passageways.
4. Vestibules and areas on the level of discharge used
for exit discharge in accordance with Section
1028.1.
5. Exterior landings as required by Section 1010.1.6
for exit doorways that lead directly to the exit discharge.
Action required- Provide emergency power for illumination of the exit discharge.
|
|
|
Building Plan Review
|
Rejected
|
06/30/2022
|
06/27/2022
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan.
Action required: Comment is for informational purposes.
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Code analysis required
Corrective Action Required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Actions required:
- Modify Code Review to show correct occupancy classification which is B. (see 2018 IBC 303.1.1)
- Modify Code Review to show correct occupant load calculations. Sales area (1:60) is restricted to area north of counter with product displays. Area with seating to be calculated as Loose Tables & Chairs (1:15)
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required: Provide complete truss package or request deferral. (must be approved by architect before submitting to us)
|
|
IBC 1103.1 Where required - accessibility
Corrective Action Required
2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities.
2018 IBC 1103.2.2 Employee work areas. Spaces and elements within employee work areas shall only be required to comply with Sections 907.5.2.3.1, 1009 and 1104.3.1 and shall be designed and constructed so that individual with disabilities can approach, enter and exit the work area. Work areas, or portions of work areas, other than raised courtroom stations in accordance with Section 1108.4.1.4, that are less than 300 square feet in area and located 7 inches or more above or below the ground or finished floor where the change in elevation is essential to the function of the space shall be exempt from all requirements.
(see code for additional exemptions)
Action required: Swinging door into employee work area not compliant in that it does not have the minimum 18" clearance at the latch side per ICC A117.1-2009 Section 404.2.3.2.
|
|
Miscellaneous Correction
Corrective Action Required
Inadequate information to complete review:
Provide the following:
- Provide complete roof access details including ladder, roof hatch, and 30" side rail ladder extension. Reflected ceiling plan and truss plans also affected.
- Furnace installation details. (truss mounted? Is this unit rated to be installed for horizontal flow? Looks like an upflow unit.)
- Furnace flue complete design.
|
|
IPC 802.1 Indirect/special waste
Corrective Action Required
2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dishwashing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7.
Action required: Provide floor sink at 3 compartment sink to facilitate indirect drain.
|
|
IPC 708.1 Cleanouts required
Corrective Action Required
2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11.
2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access.
action required: Provide cleanout near where sanitary leaves foundation.
|
|
|
Licensed Contractors
|
Rejected
|
06/30/2022
|
06/27/2022
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|