Permit Application Status

PRCOM20213799


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20213799
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW TENANT FINISH
TENANT FINISH FOR STRETCHING CLINIC
07/22/2021
08/25/2021
02/15/2022
09/16/2021
Locations
Contacts
JTI Construction LLC, Address:513 S Persimmon Dr  
jt@jticonstructionkc.net, Address:jt@jticonstructionkc.net  
On Demand Mechanical LLC, Address:PO Box 379  
CRH ELECTRIC INC, Address:4020 E 137TH TER, Phone:(816) 761-1433  
PLUMBING PLUS INC, Address:13117 S 71 HWY, Phone:(816) 761-5757  
JOE STEWART, Address:125 HIGHLAND PARK AVE, Phone:(816) 830-2754  
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 08/23/2021 08/24/2021
Joe Frogge
Misc
Resolved
08/18/2021

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
IBC 1004.5.1 Increase occupant load
Resolved
08/24/2021

2018 IBC 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Update occupant load to more accurately represent use of space. With 5 work stations we would expect a minimum occupant load of 10 plus staff and waiting customers. 8/19/21 - Occupant load still under represented. Calcs are by use and potential use, not business plan. Please call to discuss
NEC Article 517.13 Grounding of receptacles patient care
Resolved
08/19/2021

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Licensed Contractors Approved 08/23/2021 08/18/2021
Joe Frogge
LC - MEP Subs
Resolved
08/18/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - General Contractor
Resolved
08/18/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
Fire Plan Review Approved with Conditions 08/23/2021 08/16/2021
Michael Weissenbach
Construction documents for fire alarm systems
Resolved
08/16/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Resolved
08/16/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
08/16/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/16/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Alarm Plan Review Released for Construction 08/11/2021 08/11/2021
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
08/11/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a test.
Sprinkler Plan Review Released for Construction 08/09/2021 08/09/2021
Michael Weissenbach
Building Plan Review Rejected 08/03/2021 07/23/2021
Joe Frogge
Misc
Corrective Action Required
07/23/2021

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
IBC 1004.5.1 Increase occupant load
Corrective Action Required
07/23/2021

2018 IBC 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Update occupant load to more accurately represent use of space. With 5 work stations we would expect a minimum occupant load of 10 plus staff and waiting customers.
NEC Article 517.13 Grounding of receptacles patient care
Corrective Action Required
07/23/2021

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Licensed Contractors Rejected 08/03/2021 07/23/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
07/23/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - General Contractor
Corrective Action Required
07/23/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
Fire Plan Review Approved with Conditions 08/03/2021 07/22/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
07/22/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
07/22/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
07/22/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/22/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide one 2A10BC Fire Extinguisher.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $94.00 $94.00 Paid 08/24/2021
8331507-Sewer Connection Fee $90.00 $90.00 Paid 08/24/2021
7232302-Commercial License Tax Fee $2,272.50 $2,272.50 Paid 08/24/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 8/26/2021 8/26/2021 08/26/2021
Misc
Corrective Action Required
08/26/2021
Provide midpoint support vertical 2" & smaller DWV Provide redundant grounding ( green mc cable ) in patient treatment area Fire caulk floor penetrations
In-wall Inspection Passed 8/27/2021 8/27/2021 08/27/2021
Misc
Resolved
08/27/2021
Above Ceiling Inspection Failed 9/10/2021 9/10/2021 09/10/2021
Miscellaneous Correction
Corrective Action Required
09/10/2021
FIRE CAULK PENETRATIONS IN 1 HOUR DEMISING WALLS
Above Ceiling Inspection Passed 9/13/2021 9/13/2021 09/13/2021
Miscellaneous Correction
Resolved
09/13/2021
Alarm Test Passed 9/14/2021 09/14/2021
Occupancy Inspection - Codes Commercial Full C of O 9/16/2021 9/16/2021 09/16/2021
Occupancy Inspection - Fire Passed 9/16/2021 9/16/2021 09/16/2021
Documents & Images
Date Uploaded File Type Document Name
07/22/2021 Application Form 21.192.02 Stretchzone . LS . Commercial Permit Application
07/22/2021 Plans 21_192_02 Stretchzone _ LS _ 210720 Permit Set
07/22/2021 Letter Fire Building Plan Review
07/23/2021 Letter DS P/R Corrections Document
08/02/2021 Letter 21_192_02 210728 PlanRevResponse
08/02/2021 Plans 21_192_02 Stretchzone _ LS _210701 rev1
08/09/2021 Stretch Zone Fire Sprinkler Plans
08/09/2021 Letter Fire (Sprinkler) Plan Review
08/11/2021 Engineer Report/Study ProjectReports -Summit at W.Pryor - Retail A-D Tenant Finish-2021-08-11
08/11/2021 Engineer Report/Study Stretchzone Battery Calc FACP
08/11/2021 Engineer Report/Study Stretchzone Battery Calc NAC
08/11/2021 Drawing Stretchzone FA 8 10 21 PE Stamp
08/11/2021 Letter Fire (Alarm) Plan Review Notice
08/16/2021 Application Form License_Tax_Application
08/16/2021 Letter License Tax Bill
08/16/2021 Letter Fire Building Plan Review
08/19/2021 Letter DS P/R Corrections Document
08/24/2021 Approved Plans approved - 21_192_02 Stretchzone _ LS _210701 rev1
08/24/2021 Email RE_ PRCOM20213799
08/24/2021 Receipt Receipt for transaction:2021-006780
08/25/2021 Letter DS Building Permit
08/26/2021 Letter INSPECTION SUMMARY
08/27/2021 Letter INSPECTION SUMMARY
08/27/2021 Letter INSPECTION SUMMARY
09/10/2021 Letter INSPECTION SUMMARY
09/15/2021 Letter Fire Loss Reduction Form
09/14/2021 Letter Fire Loss Reduction Form
09/16/2021 Letter Field Certificate of Occupancy
09/16/2021 Letter Codes Final Certificate of Occupancy
09/16/2021 Letter Fire Loss Reduction Form
09/28/2021 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home