Permit Application Status

PRCOM20213473


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20213473
Building Permit - Commercial
Certificate of Occupancy
PINE TREE PLAZA LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR BREWERY AND TAP ROOM WITH SOME RETAIL
07/07/2021
09/01/2021
02/14/2022
04/02/2024
Locations
Contacts
VERITASI DESIGN + BUILD, Address:4 SW 3RD ST, Phone:(816) 838-0100  
INSIGHT MECHANICAL CONTRACTORS, Address:9204 E 350 HWY, Phone:(816) 353-3533  
C H ELECTRIC & TECHNOLOGY, Address:PO BOX 1984, Phone:(816) 365-7650  
CL HOWERTON ENTERPRISES LLC, Address:224 NW AA HWY, Phone:(816) 237-6338  
MAC LAMKEN, Phone:(816) 726-1513  
sales@grainsandtaps.com, Address:sales@grainsandtaps.com  
PINE TREE PLAZA LLC, Address:601 E SOUTH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Health Department Review Approved 08/30/2021
Joe Frogge
Building Plan Review Approved with Conditions 08/27/2021 08/30/2021
Joe Frogge
Health Dept Review
Resolved
08/30/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 8/18/21 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
08/20/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 8/18/21 - acknowledged in letter
IBC 602.1 Type of Construction - general
Resolved
08/23/2021

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update all drawings to show correct building type which is 2B. 8/18/21 - Several places still show VB.
IBC 1209.2 Finish materials
Resolved
08/23/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish at mop/utility sink. If paint is used it must be epoxy based. 8/18/21 - Note added for "existing" mop sink but isn't this one new? Also, we need an actual product or design specified.
IBC 1607.3 Uniform live loads - structural
Corrective Action Required
08/20/2021

2018 IBC 1609.1 Applications. Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads prescribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures. Action required: Comment is for informational purposes. Overhead door into Taproom must meet minimum wind load ratings. (to be field verified) 8/18/21 - acknowledged in letter
IBC 1013.1 Where required - exit sign
Corrective Action Required
08/20/2021

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit signage out of Taproom. (not to be directed through production area) 8/18/21 - Exit signage (not just emergency lighting) required to lead occupants out of tap room. This includes the new exit. 8/23/21 - noted on architectural but not clear on electrical. Field verify.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
08/20/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting in taproom and at exterior side of exits. 8/18/21 - code section noted but not specifically shown as emergency fixture. To be field verified.
IBC 711.2.3 Fire and Smoke Protection - fire rating of supporting construction
Resolved
08/23/2021

8/18/21 - Comment added as result of new designs. 2018 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance Sections 714 and 715, respectively. 2018 IBC 703.7 Marking and identification. Where there is an accessible concealed floor, floor-ceiling or attic space, fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other wall required to have protected openings or penetrations shall be effectively and permanently identified with signs or stenciling in the concealed space. Such identification shall: 1. Be located within 15 feet of the end of each wall and at intervals not exceeding 30 feet measured horizontally along the wall or partition. 2. Include lettering not less than 3 inches in height with a minimum 3/8 inch stroke in a contrasting color incorporating the suggested working, “FIRE AND/OR SMOKE BARRIER – PROTECT ALL OPENINGS,” or other wording. Action required: If new walls are to be fire rated we must have complete assembly designs including stud spacing, nail/screw patterns, penetration remediation, connection to deck, etc. (interior walls not required to be fire rated only those that surround the space. recommend non-rated construction)
Licensed Contractors Approved 08/27/2021 08/23/2021
Joe Frogge
Fire Plan Review Approved with Conditions 08/27/2021 08/20/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
08/20/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load at 93.
Illumination required
Resolved
08/20/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide a plan with exit/emergency lighting including emergency exterior illumination. 8/16/2021 Provide exit and emergency lighting out of production area.
Miscellaneous Correction
Corrective Action Required
08/20/2021

(Action Required) IFC 2018 5307.4 If more than 100 pounds of Carbon Dioxide is on site, refer to 5307.4.1 through 5307.4.7. Documentation and gas detection will be required. 8/20/21 Owner to be responsible for CO detection. To be verified at inspection. If needed the detection will have to be in place before occupancy can occur.
Building Plan Review Rejected 08/18/2021 08/18/2021
Joe Frogge
IBC 1103.1 Where required - accessibility
Resolved
08/18/2021

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Staff Bath must be fully accessible including, but not limited to, 60" clearance behind water closet, fixture heights, grab bars (shower and water closet), turning space, minimum fixture access clearances, etc.
Health Dept Review
Corrective Action Required
08/11/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 8/18/21 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
08/11/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 8/18/21 - acknowledged in letter
IBC 602.1 Type of Construction - general
Corrective Action Required
08/18/2021

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update all drawings to show correct building type which is 2B. 8/18/21 - Several places still show VB.
IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance
Resolved
08/18/2021

2018 IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1. The cumulative occupant load from adjacent rooms, areas or spaces shall be determined in accordance with Section 1004.2. (see code for special requirements for foyers, lobbies, vestibules, and care suites in I-2 occupancies) Action required: Provide additional exit out of Taproom. Exits must be spaced minimum 1/2 distance of diagonal per IBC 1007.1.1. Exit not allowed to pass through Production Area.
IBC 903.2.9 Fire Protection - S-1 sprinkler
Resolved
08/18/2021

2018 IBC 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing group A-2 occupancies and throughout all stories from the group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists. 1. The fire area exceeds 5,000 square feet. 2. The fire area has an occupant load of 100 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Action required: Provide fire suppression sprinkler system or provide verification that this space is surrounded by fire rated barriers. (see definition of "fire area" in IBC)
IBC 1209.2 Finish materials
Corrective Action Required
08/11/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish at mop/utility sink. If paint is used it must be epoxy based. 8/18/21 - Note added for "existing" mop sink but isn't this one new? Also, we need an actual product or design specified.
IBC 2902.3 Employee and public toilet facilities - access to public toilet
Resolved
08/18/2021

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Exception: Public toilet facilities shall not be required for: 1. Parking garages where operated without parking attendants. 2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet.
Miscellaneous Correction
Resolved
08/18/2021

2018 IBC 2902.3.2 Prohibited toilet room location. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public. Action required: Relocate or eliminate staff restroom. (we acknowledge that the code references food, not specifically drinks, but upon referencing the Code Commentary published by ICC we have determined that this section does apply)
IBC 603.1 Type of Construction - Allowable Materials
Resolved
08/18/2021

2018 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Wood is not an allowable construction material in this building. Modify designs to comply.
IBC 1607.3 Uniform live loads - structural
Corrective Action Required
08/11/2021

2018 IBC 1609.1 Applications. Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads prescribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures. Action required: Comment is for informational purposes. Overhead door into Taproom must meet minimum wind load ratings. (to be field verified) 8/18/21 - acknowledged in letter
IFGC 501.2 Combustion air discharge
Resolved
08/18/2021

2018 IFGC 501.2 General. Every appliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Action required: Provide design for water heater flues.
IBC 1013.1 Where required - exit sign
Corrective Action Required
08/11/2021

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit signage out of Taproom. (not to be directed through production area) 8/18/21 - Exit signage (not just emergency lighting) required to lead occupants out of tap room. This includes the new exit.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
08/18/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting in taproom and at exterior side of exits. 8/18/21 - code section noted but not specifically shown as emergency fixture. To be field verified.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
08/18/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door out of Office.
IBC 711.2.3 Fire and Smoke Protection - fire rating of supporting construction
Corrective Action Required
08/18/2021

8/18/21 - Comment added as result of new designs. 2018 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance Sections 714 and 715, respectively. 2018 IBC 703.7 Marking and identification. Where there is an accessible concealed floor, floor-ceiling or attic space, fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions or any other wall required to have protected openings or penetrations shall be effectively and permanently identified with signs or stenciling in the concealed space. Such identification shall: 1. Be located within 15 feet of the end of each wall and at intervals not exceeding 30 feet measured horizontally along the wall or partition. 2. Include lettering not less than 3 inches in height with a minimum 3/8 inch stroke in a contrasting color incorporating the suggested working, “FIRE AND/OR SMOKE BARRIER – PROTECT ALL OPENINGS,” or other wording. Action required: If new walls are to be fire rated we must have complete assembly designs including stud spacing, nail/screw patterns, penetration remediation, connection to deck, etc. (interior walls not required to be fire rated only those that surround the space. recommend non-rated construction)
Licensed Contractors Approved 08/11/2021 08/18/2021
Joe Frogge
LC - MEP Subs
Resolved
08/18/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 08/18/2021 08/16/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
08/11/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load at 93.
Miscellaneous Correction
Resolved
08/16/2021

(Action Required) 1. Add additional exit in assembly area. Occupant load over 50. 2. Provide documentation that the space meets fire area requirements.
Illumination required
Corrective Action Required
08/11/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide a plan with exit/emergency lighting including emergency exterior illumination. 8/16/2021 Provide exit and emergency lighting out of production area.
Miscellaneous Correction
Corrective Action Required
08/16/2021

(Action Required) IFC 2018 5307.4 If more than 100 pounds of Carbon Dioxide is on site, refer to 5307.4.1 through 5307.4.7. Documentation and gas detection will be required.
Building Plan Review Rejected 07/23/2021 07/14/2021
Joe Frogge
IBC 1103.1 Where required - accessibility
Corrective Action Required
07/14/2021

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Staff Bath must be fully accessible including, but not limited to, 60" clearance behind water closet, fixture heights, grab bars (shower and water closet), turning space, minimum fixture access clearances, etc.
Health Dept Review
Corrective Action Required
07/14/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
07/14/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
IBC 602.1 Type of Construction - general
Corrective Action Required
07/14/2021

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update all drawings to show correct building type which is 2B.
IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance
Corrective Action Required
07/14/2021

2018 IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1. The cumulative occupant load from adjacent rooms, areas or spaces shall be determined in accordance with Section 1004.2. (see code for special requirements for foyers, lobbies, vestibules, and care suites in I-2 occupancies) Action required: Provide additional exit out of Taproom. Exits must be spaced minimum 1/2 distance of diagonal per IBC 1007.1.1. Exit not allowed to pass through Production Area.
IBC 903.2.9 Fire Protection - S-1 sprinkler
Corrective Action Required
07/14/2021

2018 IBC 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing group A-2 occupancies and throughout all stories from the group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists. 1. The fire area exceeds 5,000 square feet. 2. The fire area has an occupant load of 100 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Action required: Provide fire suppression sprinkler system or provide verification that this space is surrounded by fire rated barriers. (see definition of "fire area" in IBC)
IBC 1209.2 Finish materials
Corrective Action Required
07/14/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish at mop/utility sink. If paint is used it must be epoxy based.
IBC 2902.3 Employee and public toilet facilities - access to public toilet
Corrective Action Required
07/14/2021

2018 IBC 2902.3 Employee and public toilet facilities. For structures and tenant spaces intended for public utilization, customers, patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902 for all users. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Exception: Public toilet facilities shall not be required for: 1. Parking garages where operated without parking attendants. 2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet.
Miscellaneous Correction
Corrective Action Required
07/14/2021

2018 IBC 2902.3.2 Prohibited toilet room location. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public. Action required: Relocate or eliminate staff restroom. (we acknowledge that the code references food, not specifically drinks, but upon referencing the Code Commentary published by ICC we have determined that this section does apply)
IBC 603.1 Type of Construction - Allowable Materials
Corrective Action Required
07/14/2021

2018 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Wood is not an allowable construction material in this building. Modify designs to comply.
IBC 1607.3 Uniform live loads - structural
Corrective Action Required
07/14/2021

2018 IBC 1609.1 Applications. Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads prescribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures. Action required: Comment is for informational purposes. Overhead door into Taproom must meet minimum wind load ratings. (to be field verified)
IFGC 501.2 Combustion air discharge
Corrective Action Required
07/14/2021

2018 IFGC 501.2 General. Every appliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Action required: Provide design for water heater flues.
IBC 1013.1 Where required - exit sign
Corrective Action Required
07/14/2021

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit signage out of Taproom. (not to be directed through production area)
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
07/14/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting in taproom and at exterior side of exits.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
07/14/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door out of Office.
Licensed Contractors Rejected 07/14/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
07/14/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 07/23/2021 07/14/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
07/14/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection)
Miscellaneous Correction
Corrective Action Required
07/14/2021

(Action Required) 1. Add additional exit in assembly area. Occupant load over 50. 2. Provide documentation that the space meets fire area requirements.
Illumination required
Corrective Action Required
07/14/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide a plan with exit/emergency lighting including emergency exterior illumination.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $300.00 $300.00 Paid 08/30/2021
$19,665.00
8331507-Sewer Connection Fee $330.00 $330.00 Paid 08/30/2021
7232302-Commercial License Tax Fee $19,920.00 $19,920.00 Paid 01/05/2022
$9,832.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 10/19/2021 10/19/2021
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/19/2021
- RESTROOMS, VANITES,SINKS,FLOOR DRAINS, - - NEED TO LOOK AT TRENCH DRAINS WHEN COMPLETE -
In-wall Inspection Partial 10/19/2021 10/19/2021 10/19/2021
Misc
Informational
10/19/2021
THE FOLLOWING AREAS ARE APPROVED - RETAIL AREA METAL STUD FRAMING & ELECTRICAL OK TO COVER -
Underslab Plumbing Inspection - Commercial Passed 10/27/2021 10/27/2021 10/27/2021
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/19/2021
- RESTROOMS, VANITES,SINKS,FLOOR DRAINS, - - TRENCH DRAINS COMPLETE APPROVED -
In-wall Inspection Partial 11/29/2021 11/29/2021
Misc
Informational
10/19/2021
THE FOLLOWING AREAS ARE APPROVED - RETAIL AREA METAL STUD FRAMING & ELECTRICAL OK TO COVER - -RESTROOMS & REAR HALLWAY OK TO COVER -
Occupancy Inspection - Fire Partial 1/10/2022 1/10/2022 01/10/2022
Corrective Action Required
01/10/2022
Address back door. Emergency exterior illumination for back door
Occupancy Inspection - Codes Commercial Failed 1/10/2022 1/10/2022 01/10/2022
Miscellaneous Correction
Corrective Action Required
01/10/2022
INSULATE PLUMBING RESTROOM SINKS PROVIDE TEMPORARY BARRICADE BETWEEN CONSTRUCTION / RETAIL SPACE PROVIDE CORRECT ADDRESS REAR DOOR THE MEANS OF EGRESS SHALL BE ILLUMINATED IN ACCORDENCE WITH SECTION 1008.1 2018 IBC
Occupancy Inspection - Codes Commercial Failed 1/18/2022 1/18/2022 01/18/2022
Misc
Informational
01/18/2022
RETAIL SPACE ONLY APPROVED FOR OCCUPANCY
In-wall Inspection Partial 2/28/2022 2/28/2022 02/28/2022
Misc
Informational
11/29/2021
THE FOLLOWING AREAS ARE APPROVED - RETAIL AREA METAL STUD FRAMING & ELECTRICAL OK TO COVER - -RESTROOMS & REAR HALLWAY OK TO COVER - - 2/28/22 IN WALL ELECTRICAL OK TO COVER, COMPLETE SURFACE MOUNTED PLUMBING IN PRODUCTION AREA COOLER TO WINE ROOM & BEHIND BAR UNDER COUNTER -
Gas Service Inspection - Commercial Passed 4/21/2022 4/21/2022 04/21/2022
In-wall Inspection Passed 5/18/2022 05/18/2022
Misc
Informational
02/28/2022
THE FOLLOWING AREAS ARE APPROVED - RETAIL AREA METAL STUD FRAMING & ELECTRICAL OK TO COVER - -RESTROOMS & REAR HALLWAY OK TO COVER - - 2/28/22 IN WALL ELECTRICAL OK TO COVER, - SURFACE MOUNTED PLUMBING IN PRODUCTION AREA COOLER TO WINE ROOM & BEHIND BAR UNDER COUNTER -
Above Ceiling Inspection Passed 5/18/2022 05/18/2022
Occupancy Inspection - Codes Commercial Failed 5/18/2022 5/18/2022 05/18/2022
Misc
Informational
01/18/2022
RETAIL SPACE ONLY APPROVED FOR OCCUPANCY
Miscellaneous Correction
Corrective Action Required
05/18/2022
Upload health dept inspection to permit on city portal Provide hammer arrestors washing machine Exit sign in brewery test button upside down Anti siphon device at mop sink Ok to Stock & Train
Occupancy Inspection - Fire Passed 5/18/2022 5/18/2022 05/18/2022
Corrective Action Required
05/18/2022
All life safety was appropriate. Okay to occupy with approval form codes.
Occupancy Inspection - Codes Commercial Failed 6/3/2022 6/3/2022 06/03/2022
Misc
Informational
05/18/2022
APPROVED FOR OCCUPANCY
Miscellaneous Correction
Corrective Action Required
05/18/2022
-Final completion pending completion of exterior patio.
Occupancy Inspection - Codes Commercial Full C of O 04/02/2024
Misc
Informational
06/03/2022
APPROVED FOR OCCUPANCY
Miscellaneous Correction
Informational
04/02/2024
-Final completion pending completion of exterior patio.
Documents & Images
Date Uploaded File Type Document Name
07/07/2021 Application Form 310SWBluePkwyPermitApp
07/07/2021 Application Form StreetTaxApp
07/13/2021 Plans Drawing Set 310SWBluePkwy
07/13/2021 Letter License Tax Bill
07/14/2021 Letter Fire Building Plan Review
07/14/2021 Letter DS P/R Corrections Document
08/11/2021 Letter Comment Response Letter - G&T
08/11/2021 Plans Drawing Set - 08082021
08/16/2021 Letter Fire Building Plan Review
08/18/2021 Letter DS P/R Corrections Document
08/20/2021 Plans Drawing Set - 08192021 (3)
08/20/2021 Letter Comment Response Letter - G&T - 08202021
08/20/2021 Letter Fire Building Plan Review
08/23/2021 Approved Plans approved - Drawing Set - 08192021 (3)
08/29/2021 Email Food Establishment Plan approved
08/30/2021 Receipt Receipt for transaction:2021-006922
09/01/2021 Letter DS Building Permit
10/19/2021 Letter INSPECTION SUMMARY
10/19/2021 Letter INSPECTION SUMMARY
10/27/2021 Letter INSPECTION SUMMARY
11/29/2021 Letter INSPECTION SUMMARY
12/10/2021 Letter 106_1_behr_epd_pre-catalyzed-waterborne-epoxy
12/15/2021 Co2 Detection Package
01/05/2022 Receipt Receipt for transaction: 2022-000084
01/10/2022 Letter INSPECTION SUMMARY
01/10/2022 Letter Fire Loss Reduction Form
01/18/2022 Letter INSPECTION SUMMARY
02/28/2022 Letter INSPECTION SUMMARY
04/21/2022 Letter INSPECTION SUMMARY
05/18/2022 Letter INSPECTION SUMMARY
05/18/2022 Letter INSPECTION SUMMARY
05/18/2022 Letter INSPECTION SUMMARY
05/18/2022 Letter Fire Loss Reduction Form
06/02/2022 IMG_0731
06/03/2022 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home