Summary
PRCOM20212416
Building Permit - Commercial
Closed
WELLS REALTY LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR RETAIL SALES OF GAMES AND COLLECTABLES - INCLUDES SPACES FOR PUBLIC GAME PLAY - ONLY CONSTRUCTION IS EMERGENCY LIGHTING AND EXIT SIGNS**' *** No inspections * Permit CLOSED
05/12/2021
01/11/2022
11/08/2021
04/02/2024
Locations
Contacts
Mindgames and Magic, LLC, Address:206 SE 2ND ST, Phone:(816) 308-3815  
WELLS REALTY LLC, Address:211 SE GRAND ST D  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 12/08/2021 12/06/2021
Joe Frogge
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
12/01/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Show locations of emergency lights. If not there, they will need to be installed in all required locations by a licensed electrical contractor. 12/6/21 - field verify
IBC 1013.1 Where required - exit sign
Corrective Action Required
12/01/2021

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Update drawing to show locations of exit signage. If not existing they will need to be installed at front door, rear door, and at opening between game room and retail. Exit sign at game room/retail opening to be positioned such that occupants are led out of game room. 12/6/21 - field verify
Licensed Contractors Approved 12/08/2021 12/06/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
12/06/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: Comment is for informational purposes. If electrical work is required as result of inspections the work performed must be by an electrician licensed to work in Lee's Summit.
Fire Plan Review Approved with Conditions 12/08/2021 12/01/2021
Michael Weissenbach
Portable fire extinguishers - conspicuous locations
Corrective Action Required
12/01/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide and mount one 2A10BC Fire Extinguisher. 12/01/2021 (Verified At Inspection)
Illumination required
Corrective Action Required
12/01/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Show existing emergency/exit lighting in the space. If not existing add emergency/exit lighting over exit doors and include exterior emergency lighting. Add additional emergency lighting throughout the space. 12/01/2021 (Verified At Inspection) Add exterior emergency lighting.
Building Plan Review Rejected 05/24/2021 05/12/2021
Joe Frogge
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
05/12/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Show locations of emergency lights. If not there, they will need to be installed in all required locations by a licensed electrical contractor.
IBC 1013.1 Where required - exit sign
Corrective Action Required
05/12/2021

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Update drawing to show locations of exit signage. If not existing they will need to be installed at front door, rear door, and at opening between game room and retail. Exit sign at game room/retail opening to be positioned such that occupants are led out of game room.
Licensed Contractors Approved 05/12/2021 05/12/2021
Joe Frogge
Fire Plan Review Rejected 05/24/2021 05/12/2021
Michael Weissenbach
Portable fire extinguishers - conspicuous locations
Corrective Action Required
05/12/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide and mount one 2A10BC Fire Extinguisher.
Illumination required
Corrective Action Required
05/12/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Show existing emergency/exit lighting in the space. If not existing add emergency/exit lighting over exit doors and include exterior emergency lighting. Add additional emergency lighting throughout the space.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $50.00 $50.00 Paid 01/11/2022
7232302-Commercial Excise Tax Fee $5,925.00 $5,925.00 Paid 01/11/2022
$5,310.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
05/12/2021 Application Form Permit App Page 1
05/12/2021 Application Form Excise Tax Page 1
05/12/2021 Drawing mind games floor plan
05/12/2021 Letter Fire Building Plan Review
05/12/2021 Letter DS P/R Corrections Document
12/01/2021 Drawing image0
12/01/2021 Letter License Tax Bill
12/01/2021 Letter Fire Building Plan Review
12/06/2021 Approved Plans mindgames
01/11/2022 Receipt Receipt for transaction:2022-000209
01/11/2022 Letter DS Building Permit
02/23/2022 Letter DS Building Permit
08/30/2022 Letter Codes 180 Day Letter
01/17/2023 Letter Codes 140 Day Letter
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home