Permit Application Status

PRCOM20211100


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20211100
Building Permit - Commercial
Certificate of Occupancy
LS RETAIL LLC
CHANGE OF TENANT
TENANT FINISH FOR PHYSICAL THERAPY
03/11/2021
03/29/2021
09/11/2021
05/13/2021
Locations
Contacts
MUDLOFF CONSTRUCTION LLC, Address:1917 E SPRUCE ST, Phone:(913) 393-0737  
PLUMBING PLUS INC, Address:13117 S 71 HWY, Phone:(816) 761-5757  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
LAKE ELECTRIC LLC, Address:1917 SPRUCE ST, Phone:(913) 490-8377  
JOE STEWART ARCHITECT, Address:4731 NORTH CLEVELAND AVE, Phone:(816) 830-2754  
justin@mudloff.com  
LS RETAIL LLC, Address:1801 SANDY CREEK LN STE # 102  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 03/26/2021 03/29/2021
Brandon Kalwei
LC - General Contractor
Corrective Action Required
03/19/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact. 3/19/21 - Acknowledged in letter.
LC - MEP Subs
Corrective Action Required
03/19/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/19/21 - Acknowledged in letter.
Fire Plan Review Approved with Conditions 03/26/2021 03/19/2021
Joe Frogge
Address numbers required
Corrective Action Required
03/19/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exterior doors.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
03/19/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Building Plan Review Approved 03/26/2021 03/19/2021
Joe Frogge
IBC 1209.2 Finish materials
Resolved
03/19/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall and floor finish materials at mop sink and toilets.
Code analysis required
Resolved
03/19/2021

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Include occupant load in Project Code Data.
Building Plan Review Rejected 03/23/2021 03/15/2021
Joe Frogge
IBC 1209.2 Finish materials
Corrective Action Required
03/15/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall and floor finish materials at mop sink and toilets.
Code analysis required
Corrective Action Required
03/15/2021

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Include occupant load in Project Code Data.
Licensed Contractors Rejected 03/23/2021 03/15/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
03/15/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Corrective Action Required
03/15/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 03/23/2021 03/15/2021
Michael Weissenbach
Address numbers required
Corrective Action Required
03/15/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exterior doors.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
03/15/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $232.00 $232.00 Paid 03/29/2021
$0.00
7232302-Commercial License Tax Fee $4,297.50 $4,297.50 Paid 03/15/2021
$4,297.50
8331507-Sewer Connection Fee $210.00 $210.00 Paid 03/29/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 4/9/2021 4/9/2021 04/09/2021
Misc
Informational
04/09/2021
-DWV for bathrooms 107,109 and laundry 108
In-wall Inspection Failed 4/16/2021 4/16/2021 04/16/2021
Misc
Corrective Action Required
04/16/2021
--- ON SHELL PLANS UL DESIGN U419 2 LAYERS 5/8" IS REQUIRED ON BOTH SIDES OF WALL. INCLUDING THE LABELING OF THE WALL. THIS WAS AGREED TO BE COMPLETED UPON TENANT INFILL. PLANS FOR TENANT DO NOT SHOW DEMISING WALL AS RATED AND ONLY INCLUDE 1 LAYER 5/8" ROCK. ---
Rated Assembly Inspection Partial 4/19/2021 4/19/2021 04/19/2021
Misc
Informational
04/19/2021
- 4/19/21 - 1st layer rock inspected on demising wall
In-wall Inspection Passed 4/19/2021 4/19/2021 04/19/2021
Rated Assembly Inspection Partial 4/21/2021 4/21/2021 04/21/2021
Misc
Informational
04/19/2021
- 4/19/21 - 1st layer rock inspected on demising wall -4/21/21 - 2nd layer rock inspected on demising wall **Firecaulk all penetrations in assembly and along roof deck/sheetrock gaps** **Mark firewall per 703.7, min 3" letters located within 15' of ends of walls and intervals not exceeding 30' horizontally along wall**
Above Ceiling Inspection Failed 5/4/2021 5/4/2021 05/04/2021
Misc
Corrective Action Required
05/04/2021
-Mark firewall per 703.7, min 3" letters located within 15' of ends of walls and intervals not exceeding 30' horizontally along wall- example "fire barrier, protect all openings" -Fire caulk at dryer duct penetration on demising wall -Remove all extension cords and work lights from above ceiling -1" MC on east (demising) wall with fish line through, complete
Above Ceiling Inspection Passed 5/5/2021 5/5/2021 05/05/2021
Misc
Resolved
05/05/2021
Rated Assembly Inspection Passed 5/5/2021 05/05/2021
Misc
Informational
04/21/2021
- 4/19/21 - 1st layer rock inspected on demising wall -4/21/21 - 2nd layer rock inspected on demising wall
Occupancy Inspection - Fire Passed 5/12/2021 05/12/2021
Occupancy Inspection - Codes Commercial Failed 5/12/2021 5/12/2021 05/12/2021
Misc
Corrective Action Required
05/12/2021
-cover plate on receptacle at mech/laundry for data -cover plate at data box at laundry wall -firecaulk at plumbing wall penetrations in laundry rated wall -GFCI at sink receptacle - emergency exterior illumination not lighting on backup as required **OK TO STOCK AND TRAIN**
Occupancy Inspection - Codes Commercial Full C of O 5/13/2021 5/13/2021 05/13/2021
Misc
Resolved
05/13/2021
Documents & Images
Date Uploaded File Type Document Name
03/12/2021 Application Form 21.112.32 Athletico . LS . Commercial Permit Application
03/12/2021 Application Form LICENSE TAX
03/12/2021 Plans 21_112_32 Athletico _Lees Summit 210311
03/15/2021 Letter Fire Building Plan Review
03/15/2021 Letter DS P/R Corrections Document
03/19/2021 Letter 21_112_32 Athletico Lees Summit PlanRevResp 210319
03/19/2021 Plans 21_112_32 Athletico Lees Summit Rev1 210319
03/19/2021 Approved Plans approved - 21_112_32 Athletico Lees Summit Rev1 210319
03/29/2021 Receipt Receipt for transaction: 2021-001572
03/29/2021 Letter DS Building Permit
04/09/2021 Letter INSPECTION SUMMARY
04/16/2021 Letter INSPECTION SUMMARY
04/19/2021 Letter INSPECTION SUMMARY
04/19/2021 Letter INSPECTION SUMMARY
04/21/2021 Letter INSPECTION SUMMARY
05/04/2021 Letter INSPECTION SUMMARY
05/05/2021 Letter INSPECTION SUMMARY
05/05/2021 Letter INSPECTION SUMMARY
05/12/2021 Letter Fire Loss Reduction Form
05/12/2021 Letter INSPECTION SUMMARY
05/13/2021 Letter Field Certificate of Occupancy
05/13/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home