Permit Application Status

PRCOM20203380


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20203380
Building Permit - Commercial
Certificate of Occupancy
TI SUMMIT CREST PLAZA LLC
CHANGE OF TENANT
TENANT FINISH FOR DENTIST EXPANDING INTO ADJACENT SPACE
09/29/2020
11/13/2020
12/06/2021
Locations
Contacts
VALENCIA CONST LLC, Address:4729 SW GULL POINT DR, Phone:(816) 537-7482  
DONALDSON MECHANICAL INC, Address:934 SE 7TH TER, Unit B, Phone:(816) 246-9500  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
INTEGRITY PLUMBING SERVICES LLC, Address:405 SW Nelson Dr., Phone:(816) 803-9032  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
greg@valencia-construction.com  
TI SUMMIT CREST PLAZA LLC, Address:7611 STATE LINE RD STE 301  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/22/2020 12/22/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
12/22/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hydrostatic test. Current annual inspection tag required on riser.
Building Plan Review Approved with Conditions 10/08/2020 11/13/2020
Development Center
Misc
Resolved
11/13/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
IBC 1103.1 Where required - accessibility
Corrective Action Required
09/29/2020

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: - Hardware for sliding door 137 to be accessible in open and closed positions. Field verify. - Break room sink/counter to be maximum 34" tall. Field verify. - At least one coat hook to be mounted maximum 48" aff. Field verify.
Licensed Contractors Approved 10/08/2020 11/13/2020
Development Center
LC - General Contractor
Corrective Action Required
09/29/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
09/29/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 10/08/2020 09/29/2020
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
09/29/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Informational Purposes) Any modifications to the fire alarm system, provide electronic PE stamped shop drawings to mike.weissenbach@cityofls.net
Address numbers required
Corrective Action Required
09/29/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior exit doors.
Construction documents - Fire protection systems
Corrective Action Required
09/29/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Informational Purposes) Any modifications to the fire sprinkler system, provide electronic PE stamped shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
09/29/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/29/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Miscellaneous Correction
Corrective Action Required
09/29/2020

(Verified At Inspection) IFC 2018 504.2 The doors being sealed and locked with no entry, provide signage stating "Door Blocked".
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $400.00 $400.00 Paid 11/13/2020
$0.00
7232302-Commercial License Tax Fee $2,827.50 $2,827.50 Paid 09/29/2020
$2,827.50
8331507-Sewer Connection Fee $150.00 $150.00 Paid 11/13/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 12/9/2020 12/9/2020 12/09/2020
Misc
Corrective Action Required
12/09/2020
-12/9/20 - INSPECTED UNDERSLAB PLUMBING FOR DENTAL CHAIR DWV
In-wall Inspection Partial 12/9/2020 12/9/2020 12/09/2020
Misc
Corrective Action Required
12/09/2020
-12/9/20- INSPECTED N SIDE TENANT DEMISING WALL SEPARATING TENANTS, OK TO ROCK PORTION INSPECTED
Underslab Electrical Inspection - Commercial Partial 12/21/2020 12/21/2020 12/21/2020
Misc
Informational
12/21/2020
-INSPECTED UNDERSLAB CONDUIT AT DENTAL OFFICE CHAIRS
In-wall Inspection Failed 1/13/2021 1/13/2021 01/13/2021
Misc
Corrective Action Required
12/09/2020
-12/9/20- INSPECTED N SIDE TENANT DEMISING WALL SEPARATING TENANTS, OK TO ROCK PORTION INSPECTED -1/13/21- SUPPORT VERTICAL DWV 2” OR LESS AT MID POINT
In-wall Inspection Partial 1/14/2021 1/14/2021 01/14/2021
Misc
Corrective Action Required
01/13/2021
-12/9/20- INSPECTED N SIDE TENANT DEMISING WALL SEPARATING TENANTS, OK TO ROCK PORTION INSPECTED
Above Ceiling Inspection Partial 3/5/2021 03/05/2021
Misc
Informational
03/05/2021
3/5/21 - OK FOR ABOVE CEILING AT TENANT ADDITION PHASE
Above Ceiling Inspection Passed 4/27/2021 4/27/2021 04/27/2021
Misc
Resolved
04/27/2021
Underslab Plumbing Inspection - Commercial Passed 05/14/2021
Misc
Resolved
05/14/2021
Underslab Electrical Inspection - Commercial Passed 05/14/2021
Misc
Resolved
05/14/2021
In-wall Inspection Passed 05/14/2021
Misc
Resolved
05/14/2021
Occupancy Inspection - Codes Commercial Temporary C of O 5/17/2021 5/17/2021 05/17/2021
Misc
Corrective Action Required
05/17/2021
-INSTALL MIRROR AT RESTROOM SINK- **OK FOR TCO**
Occupancy Inspection - Fire Passed 5/17/2021 05/17/2021
Occupancy Inspection - Codes Commercial Full C of O 12/6/2021 12/6/2021 12/06/2021
Misc
Resolved
12/06/2021
Documents & Images
Date Uploaded File Type Document Name
09/29/2020 Application Form TLC Permit Application
09/29/2020 Plans TLC_Full-Set_09-29-2020
09/29/2020 Email RE TLC Family Dentistry
09/29/2020 Letter Fire Building Plan Review
10/14/2020 Letter DS P/R Corrections Document
11/13/2020 Receipt Receipt for transaction: 2020-007549
11/13/2020 Letter License Tax Bill
11/13/2020 Application Form lt form
11/13/2020 Approved Plans approved - TLC_Full-Set_09-29-2020
11/13/2020 Letter DS Building Permit
12/09/2020 Letter INSPECTION SUMMARY
12/09/2020 Letter INSPECTION SUMMARY
12/21/2020 Letter INSPECTION SUMMARY
12/22/2020 Letter Fire (Sprinkler) Plan Review
01/13/2021 Letter INSPECTION SUMMARY
01/14/2021 Letter INSPECTION SUMMARY
03/05/2021 Letter INSPECTION SUMMARY
04/27/2021 Letter INSPECTION SUMMARY
05/14/2021 Letter INSPECTION SUMMARY
05/14/2021 Letter INSPECTION SUMMARY
05/14/2021 Letter INSPECTION SUMMARY
05/17/2021 Letter Codes Temporary Certificate of Occupancy
05/17/2021 Letter Fire Loss Reduction Form
12/06/2021 Letter Field Certificate of Occupancy
12/06/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home