Permit Application Status

PRCOM20201154


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20201154
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
TENANT FINISH FOR MUSIC TEACHING STUDIOS **drawing is in permit file
05/06/2020
05/28/2020
08/28/2020
Locations
Contacts
PACT CONSTRUCTION SERVICES, Address:1280 NE DELTA SCHOOL RD, Phone:(816) 287-3030  
THREE TRAILS HEATING COOLING, Address:13223 S 71 HWY, Phone:(816) 701-6377  
PREMIER ELECTRIC & LIGHTING DESIGN, Address:PO BOX 1311, Phone:(816) 564-7660  
COLLINS|WEBB ARCHITECTURE, Address:13A SW 3RD STREET, Phone:(816) 249-2270  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 05/18/2020 06/26/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
06/26/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a Hydrostatic Test.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/26/2020

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. (Informational Purposes) Maintain operation of existing sprinkler system during the addition.
Alarm Plan Review Released for Construction 05/18/2020 06/25/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
06/25/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing
Licensed Contractors Approved 05/18/2020 05/28/2020
Joe Frogge
LC - General Contractor
Resolved
05/28/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Building Plan Review Approved with Conditions 05/18/2020 05/11/2020
Joe Frogge
Miscellaneous Correction
Corrective Action Required
05/07/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Gen - Plan submittals 2018 codes
Corrective Action Required
05/07/2020

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Comment is for informational purposes. We have reverted back to enforcing ICC/ANSI A117.1-2009.
Fire Plan Review Approved with Conditions 05/18/2020 05/07/2020
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
05/07/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Address numbers required
Corrective Action Required
05/07/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
05/07/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
05/07/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $260.00 $260.00 Paid 05/28/2020
7232302-Commercial License Tax Fee $2,265.00 $2,265.00 Paid 05/28/2020
$2,265.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 6/24/2020 6/24/2020 06/24/2020
LOWER LEVEL
Corrective Action Required
06/24/2020
lower level-walls ok
All Rough Inspection - Commercial Passed 7/17/2020 7/17/2020 07/17/2020
LOWER LEVEL
Resolved
07/17/2020
lower level-walls ok
Above Ceiling Inspection Partial 8/5/2020 8/5/2020 08/05/2020
Misc
Corrective Action Required
08/05/2020
MISSING COVER PLATES IN ROOMS 1 & 4 TIE LIGHTS IN ROOM 8
Above Ceiling Inspection Passed 8/7/2020 8/7/2020 08/07/2020
Misc
Resolved
08/07/2020
MISSING COVER PLATES IN ROOMS 1 & 4 TIE LIGHTS IN ROOM 7 & 8
Sprinkler - Hydrostatic Test Passed 8/13/2020 08/13/2020
Alarm Test Passed 8/18/2020 08/18/2020
Occupancy Inspection - Fire Passed 8/28/2020 8/28/2020 08/28/2020
Occupancy Inspection - Codes Commercial Full C of O 8/28/2020 8/28/2020 08/28/2020
Documents & Images
Date Uploaded File Type Document Name
05/06/2020 Application Form Commercial Permit Application - 200506 Shining Light Music
05/07/2020 Plans 20027_R18_ShiningLightMusic_200506_PERMIT SET
05/07/2020 Letter Fire Building Plan Review
05/11/2020 Plans Approved_PERMIT SET
05/11/2020 Email LT Info
05/28/2020 Letter LT form
05/28/2020 Letter License Tax Bill
05/28/2020 Receipt Receipt for transaction:2020-002459
05/28/2020 Letter DS Building Permit
06/25/2020 Letter Fire (Alarm) Plan Review Notice
06/25/2020 20512FA-1
06/26/2020 Letter Fire (Sprinkler) Plan Review
07/17/2020 Letter INSPECTION SUMMARY
08/05/2020 Letter INSPECTION SUMMARY
08/07/2020 Letter INSPECTION SUMMARY
08/28/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home