Permit Application Status

PRCOM20201063


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20201063
Building Permit - Commercial
Certificate of Occupancy
WARNING TERRI SUE TRUSTEE &
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO EXISTING RESTAURANT
04/28/2020
07/29/2020
10/28/2020
12/09/2020
Locations
Contacts
J E HEFNER COMPANY, Address:2614 MURPHY SCHOOL RD, Phone:(816) 690-7010  
HEART OF AMERICA SERVICE CO LLC, Address:8347 MONTICELLO RD, Phone:(913) 441-2772  
GENESIS 1 ELECTRIC INC, Address:4609 E 205TH ST, Phone:(816) 309-3975  
IPLUMBKC LLC, Address:34108 E TRUMAN RD, Phone:(833) 758-6252  
EBI Consulting, Address:21 B Street, Phone:(707) 328-3731  
WARNING TERRI SUE TRUSTEE &, Address:25525 WILDCAT LANE  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 07/08/2020 07/08/2020
Joe Frogge
Building Plan Review Approved with Conditions 07/15/2020 07/08/2020
Joe Frogge
Health Dept Inspection
Corrective Action Required
07/08/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Fire Plan Review Approved with Conditions 07/15/2020 07/08/2020
Joe Frogge
Posting of occupant load
Corrective Action Required
07/08/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified At Inspection) Post occupant load signage at 90
Construction documents for fire alarm systems
Corrective Action Required
07/08/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
07/08/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Type I hood - Where required
Corrective Action Required
07/08/2020

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Verified At Inspection) Hood system to have a current inspection tag.
Construction documents - Fire protection systems
Corrective Action Required
07/08/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
07/08/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
07/08/2020

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Verified At Inspection) K-Class extinguisher to have a current annual tag.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/08/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide 2 2A10BC fire extinguishers.
Illumination required
Corrective Action Required
07/08/2020

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at the exit doors.
Licensed Contractors Approved 05/08/2020 07/08/2020
Joe Frogge
LC - General Contractor
Resolved
07/07/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
07/08/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 05/08/2020 05/05/2020
Joe Frogge
Project cost
Resolved
05/05/2020

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
05/01/2020

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
04/28/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Department Review Approved 05/01/2020
Joe Frogge
Fire Plan Review Approved with Conditions 05/08/2020 04/29/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
04/29/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified At Inspection) Post occupant load signage at 90
Construction documents for fire alarm systems
Corrective Action Required
04/29/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm, provide three sets of PE stamped shop drawings.
Address numbers required
Corrective Action Required
04/29/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Type I hood - Where required
Corrective Action Required
04/29/2020

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. (Verified At Inspection) Hood system to have a current inspection tag.
Construction documents - Fire protection systems
Corrective Action Required
04/29/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
04/29/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
04/29/2020

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. (Verified At Inspection) K-Class extinguisher to have a current annual tag.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
04/29/2020

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide 2 2A10BC fire extinguishers.
Illumination required
Corrective Action Required
04/29/2020

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at the exit doors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,000.00 $1,000.00 Paid 07/29/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 8/4/2020 8/4/2020 at 2:05 PM 08/04/2020
Misc
Partial Correction
08/04/2020
IN-WALL OK TO COVER: BACK WALL AT SERVICE AREA
Above Ceiling Inspection Partial 8/5/2020 8/5/2020 08/05/2020
Misc
Partial Correction
08/05/2020
Above-ceiling OK: restroom area
Above Ceiling Inspection Partial 8/6/2020 8/6/2020 08/06/2020
Misc
Partial Correction
08/05/2020
Above-ceiling OK: restroom area; two vestibules
Underslab Electrical Inspection - Commercial Passed 8/6/2020 8/6/2020 08/06/2020
Above Ceiling Inspection Partial 8/17/2020 8/17/2020 at 10:05 AM 08/17/2020
Misc
Partial Correction
08/06/2020
Above-ceiling OK: restroom area; two vestibules; eating area
In-wall Inspection Passed 08/25/2020
Misc
Resolved
08/25/2020
IN-WALL OK TO COVER: BACK WALL AT SERVICE AREA
Above Ceiling Inspection Passed 08/25/2020
Misc
Resolved
08/25/2020
Above-ceiling OK: restroom area; two vestibules; eating area
Occupancy Inspection - Codes Commercial Temporary C of O 8/25/2020 8/25/2020 08/25/2020
Miscellaneous Correction
Corrective Action Required
08/25/2020
Fire Department approval required
Occupancy Inspection - Fire Failed 8/25/2020 08/25/2020
Occupancy Inspection - Fire Passed 9/9/2020 09/17/2020
Occupancy Inspection - Codes Commercial Full C of O 12/10/2020 12/10/2020 12/09/2020
Miscellaneous Correction
Resolved
12/09/2020
Fire Department approval required
Documents & Images
Date Uploaded File Type Document Name
04/28/2020 Application Form McD_Lee's Summit, MO_Building Permit Application
04/28/2020 Plans 024-1174_Lee's Summit MO_NSN 33308_Denver_EOTF C_Permit Set
04/28/2020 Letter License Tax Not Applicable
04/29/2020 Letter Fire Building Plan Review
04/30/2020 Letter DS P/R Corrections Document
05/01/2020 Email Food Establishment Remodel Plan Review - Approved FTG 0001306
07/08/2020 Plans Approved - Permit Set
07/29/2020 Receipt Receipt for transaction: 2020-004799
07/29/2020 Letter DS Building Permit
08/04/2020 Letter INSPECTION SUMMARY
08/05/2020 Letter Codes Plan Review Conditions
08/05/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/17/2020 Letter INSPECTION SUMMARY
08/25/2020 Letter INSPECTION SUMMARY
08/25/2020 Letter INSPECTION SUMMARY
08/25/2020 Letter Codes Temporary Certificate of Occupancy
12/09/2020 Letter Codes Final Certificate of Occupancy
12/09/2020 Letter Field Certificate of Occupancy
12/09/2020 Letter INSPECTION SUMMARY
12/09/2020 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home