Permit Application Status

PRCOM20192572


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192572
Building Permit - Commercial
Certificate of Occupancy
MIDWEST DIVISION LSH LLC
NEW TENANT FINISH
TENANT FINISH FOR MEDICAL OFFICES ASSIGNED SUITES: 1100 - Bariatric 1200 - Neuro 1300 - GI 3100 - Cardiology 3200 - Surgery Clinic 3300 - Imaging UNDERSLAB PLUMBING UNDER SEPARATE PERMIT - PRCOM20193600
09/10/2019
01/07/2020
06/07/2020
07/17/2020
Locations
Contacts
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
ACI BOLAND, Address:1421 EAST 104TH ST; SUITE 100, Phone:(816) 763-9600  
melson@aciboland.com  
STANGER INDUSTRIES, Address:4911 ELMWOOD AVE, Phone:(816) 861-2800  
BART'S ELECTRIC COMPANY INC, Address:7103 STEWART RD, Phone:(816) 421-0007  
STANGER INDUSTRIES, Address:4911 ELMWOOD AVE, Phone:(816) 861-2800  
TURNER CONSTRUCTION COMPANY, Address:1220 WASHINGTON STE 1000, Phone:(816) 283-0555  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 12/17/2019 12/16/2019
Joe Frogge
LC - MEP Subs
Resolved
12/16/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/8/19 - Acknowledged in letter
Fire Plan Review Approved with Conditions 12/17/2019 12/11/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
12/10/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the alarm system, provide three sets of PE stamped shop drawings.
Hazardous material identification
Corrective Action Required
12/10/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection) Label all rooms
Construction documents - Fire protection systems
Corrective Action Required
12/10/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
12/10/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Approved with Conditions 12/17/2019 12/10/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
12/10/2019

The permit for these suites is tied to an incomplete shell. Occupancy for the suites will not be granted until occupancy for shell has been granted. Action required: Comment is for informational purposes. 10/8/19 - Acknowledged in letter
Project cost
Resolved
12/16/2019

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 10/8/19 - Acknowledged in letter
Suite address
Corrective Action Required
12/10/2019

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Comment is for informational purposes. This building has been assigned the address of 1980 SE Blue Pkwy. Please update your records. The suites have been assigned the following numbers: 1100 - Bariatric 1200 - Neuro 1300 - GI 3100 - Cardiology 3200 - Surgery Clinic 3300 - Imaging 10/8/19 - Acknowledged in letter
Fire Plan Review Approved with Conditions 12/17/2019 10/08/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
10/03/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the alarm system, provide three sets of PE stamped shop drawings.
Hazardous material identification
Corrective Action Required
10/03/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection) Label all rooms
Construction documents - Fire protection systems
Corrective Action Required
10/03/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
10/03/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Approved with Conditions 12/17/2019 10/08/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/03/2019

The permit for these suites is tied to an incomplete shell. Occupancy for the suites will not be granted until occupancy for shell has been granted. Action required: Comment is for informational purposes. 10/8/19 - Acknowledged in letter
Project cost
Corrective Action Required
10/03/2019

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 10/8/19 - Acknowledged in letter
Suite address
Corrective Action Required
10/03/2019

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Comment is for informational purposes. This building has been assigned the address of 1980 SE Blue Pkwy. Please update your records. The suites have been assigned the following numbers: 1100 - Bariatric 1200 - Neuro 1300 - GI 3100 - Cardiology 3200 - Surgery Clinic 3300 - Imaging 10/8/19 - Acknowledged in letter
Plan Submittal 2012 Codes
Resolved
10/08/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit Action required: Update code analysis to show correct accessibility code which is ICC/ANSI A117.1-2017
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
10/08/2019

ICC A117.1-2017 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of doors out of Dressing Rooms 3-310 & 3-311.
Licensed Contractors Rejected 12/17/2019 10/08/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
10/03/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/8/19 - Acknowledged in letter
Building Plan Review Rejected 09/20/2019 09/17/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
09/17/2019

The permit for these suites is tied to an incomplete shell. Occupancy for the suites will not be granted until occupancy for shell has been granted. Action required: Comment is for informational purposes.
Project cost
Corrective Action Required
09/17/2019

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Suite address
Corrective Action Required
09/17/2019

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Comment is for informational purposes. This building has been assigned the address of 1980 SE Blue Pkwy. Please update your records. The suites have been assigned the following numbers: 1100 - Bariatric 1200 - Neuro 1300 - GI 3100 - Cardiology 3200 - Surgery Clinic 3300 - Imaging
Code analysis required
Resolved
10/01/2019

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis to show correct construction type which is 1B. 10/1/19 - umm.. i was totally mistaken
Plan Submittal 2012 Codes
Corrective Action Required
09/17/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit Action required: Update code analysis to show correct accessibility code which is ICC/ANSI A117.1-2017
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
09/17/2019

ICC A117.1-2017 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of doors out of Dressing Rooms 3-310 & 3-311.
Licensed Contractors Rejected 09/20/2019 09/17/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/17/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 09/20/2019 09/11/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
09/11/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the alarm system, provide three sets of PE stamped shop drawings.
Hazardous material identification
Corrective Action Required
09/11/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection) Label all rooms
Construction documents - Fire protection systems
Corrective Action Required
09/11/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the sprinkler system, provide three sets of PE stamped shop drawings.
Installation acceptance testing
Corrective Action Required
09/11/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $13,040.00 $13,040.00 Paid 01/07/2020
8331507-Sewer Connection Fee $1,440.00 $1,440.00 Paid 01/07/2020
7232302-Commercial Excise Tax Fee $45,075.00 $45,075.00 Paid 02/04/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Plumbing Inspection - Commercial Partial 2/5/2020 at 3:00 PM 02/05/2020
Misc
Corrective Action Required
02/05/2020
WASTE&VENT PLUMBING PRESSURE TEST: 3RD FL NORTH BRANCH OK
Rough Plumbing Inspection - Commercial Partial 2/6/2020 2/6/2020 02/06/2020
Misc
Corrective Action Required
02/05/2020
WASTE&VENT PLUMBING PRESSURE TEST: 3RD FL W&V OK
Rough Plumbing Inspection - Commercial Partial 2/12/2020 02/12/2020
Misc
Corrective Action Required
02/06/2020
WASTE&VENT PLUMBING PRESSURE TEST: 1ST AND 3RD FL W&V OK
In-wall Inspection Failed 2/12/2020 2/12/2020 02/12/2020
Misc
Corrective Action Required
02/12/2020
1ST FL: NW AREA BOUNDED BY CORRIDORS : -Protect plumbing at bottom wall track -Complete insulating and supporting all in-wall water lines -Install blocking for grab bars 3RD FL: -Rms not ready: 3-100/111/122/124/125/137 -Fb floor penetrations -Support and insulatre in-wall water lines
In-wall Inspection Partial 2/18/2020 2/18/2020 02/18/2020
Misc
Corrective Action Required
02/12/2020
1ST FL: NW AREA BOUNDED BY CORRIDORS : -Protect plumbing at bottom wall track -Install blocking for grab bars 3RD FL: -Rms not ready: 3-100/111/122/124/125/137
In-wall Inspection Partial 2/20/2020 2/20/2020 02/20/2020
Misc
Corrective Action Required
02/18/2020
1ST FL: NW AREA BOUNDED BY CORRIDORS : 3RD FL: -Rms not ready: 3-100/111/122/124/125/137
FIRST FLOOR
Corrective Action Required
02/20/2020
1ST FL: NW AREA BOUNDED BY CORRIDORS : ; GI area (NE corner)
SECOND FLOOR
Corrective Action Required
02/20/2020
THIRD FLOOR
Corrective Action Required
02/20/2020
3RD FL: -Rms ;
In-wall Inspection Partial 2/26/2020 2/26/2020 02/26/2020
Misc
Corrective Action Required
02/20/2020
1ST FL: NW AREA BOUNDED BY CORRIDORS : 3RD FL: -Rms not ready: 3-100/111/122/124/125/137
FIRST FLOOR
Corrective Action Required
02/20/2020
1ST FL: NW AREA BOUNDED BY CORRIDORS : ; GI area (NE corner) BI (SOUTH) ALL AREAS EXCEPT 3 WEST ROOMS COLUMNS.
SECOND FLOOR
Corrective Action Required
02/20/2020
THIRD FLOOR
Corrective Action Required
02/20/2020
3RD FL: -Rms ;
Rough Plumbing Inspection - Commercial Partial 2/26/2020 02/26/2020
Misc
Corrective Action Required
02/12/2020
WASTE&VENT PLUMBING PRESSURE TEST: 1ST AND 3RD FL W&V OK ROOF DRAINS- 3 -8" AND TESTED.
In-wall Inspection Passed 3/3/2020 3/3/2020 at 12:50 PM 03/03/2020
Misc
Resolved
03/03/2020
1ST FL AND 3RD FLOOR IN-WALL-OK
FIRST FLOOR
Resolved
03/03/2020
1ST FL: NW AREA BOUNDED BY CORRIDORS : ; GI area (NE corner) BI (SOUTH) ALL AREAS EXCEPT 3 WEST ROOMS COLUMNS.
Rough Plumbing Inspection - Commercial Partial 4/1/2020 4/3/2020 04/03/2020
Misc
Corrective Action Required
02/26/2020
-WASTE&VENT PLUMBING PRESSURE TEST: 1ST, 2ND, AND 3RD FL W&V OK -ROOF DRAINS- 3 -8" AND TESTED.
In-wall Inspection Passed 4/8/2020 4/8/2020 at 3:00 PM 04/08/2020
Above Ceiling Inspection Partial 4/3/2020 4/13/2020 at 10:50 AM 04/13/2020
Misc
Partial Correction
04/13/2020
ABOVE-CEILING OK TO COVER: -3RD FLOOR
Above Ceiling Inspection Partial 4/17/2020 4/17/2020 at 3:30 PM 04/17/2020
Misc
Partial Correction
04/13/2020
ABOVE-CEILING OK TO COVER: -3RD FL -1ST FL: Neurology Suite OK except 224/231/232
Above Ceiling Inspection Partial 4/21/2020 4/21/2020 at 3:10 PM 04/21/2020
Misc
Partial Correction
04/17/2020
ABOVE-CEILING OK TO COVER: -3RD FL -1ST FL: Neurology Suite, GI and Bariatric rooms
Above Ceiling Inspection Passed 05/21/2020
Misc
Resolved
05/21/2020
ABOVE-CEILING OK TO COVER: -3RD FL -1ST FL: Neurology Suite, GI and Bariatric rooms
Rough Plumbing Inspection - Commercial Passed 05/21/2020
Misc
Resolved
04/17/2020
-WASTE&VENT PLUMBING PRESSURE TEST: 1ST, 2ND, AND 3RD FL W&V OK -ROOF DRAINS- 3 -8" AND TESTED.
Occupancy Inspection - Codes Commercial Failed 5/21/2020 5/21/2020 at 2:10 PM 05/21/2020
Misc
Corrective Action Required
05/21/2020
INSPECTION OF 3RD FLOOR ONLY: -INSTALL RESTROOM SIGNAGES -RECEPTACLES LOCATED WITHIN SIX FT OF THE INSIDE WALL OF THE NURSE STATION SINKS SHALL BE GFCI-PROTECTED
Occupancy Inspection - Codes Commercial Temporary C of O 5/22/2020 at 1:35 PM 05/22/2020
Misc
Corrective Action Required
05/21/2020
-INSTALL RESTROOM SIGNAGES -RECEPTACLES LOCATED WITHIN SIX FT OF THE INSIDE WALL OF THE NURSE STATION SINKS SHALL BE GFCI-PROTECTED -INSTALL BOX EXTENSIONS FOR ALL BOXES RECESSED BEHIND COMBUSTIBLE WALL FINISH AT RECEPTION AREAS -PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES LOCATED WITHIN SIX FT OF SINKS IN RM 1-310, 317, AND 320 -COMPLETE P/T DISCHARGE AND PAN DRAINAGE FOR WATER HEATER IN RM 1-323 **EXAM LIGHTS ABOVE ROOMS 1-208, 1-321, AND 3-219 ARE CURRENTLY NOT INSTALLED BUT WILL BE INSTALLED BY OWNERS.
Occupancy Inspection - Fire Passed 5/21/2020 5/21/2020 05/27/2020
Occupancy Inspection - Codes Commercial Temporary C of O 5/27/2020 05/27/2020
Misc
Resolved
07/17/2020
-EXAM LIGHTS ABOVE ROOMS 1-208, 1-321, AND 3-219 ARE CURRENTLY NOT INSTALLED.
Occupancy Inspection - Codes Commercial Full C of O 07/17/2020
Misc
Partial Correction
05/27/2020
-EXAM LIGHTS ABOVE ROOMS 1-208, 1-321, AND 3-219 ARE CURRENTLY NOT INSTALLED.
Documents & Images
Date Uploaded File Type Document Name
09/10/2019 Letter License Tax Bill
09/11/2019 Letter Fire Building Plan Review
09/17/2019 Letter DS P/R Corrections Document
10/08/2019 Letter Fire Building Plan Review
12/10/2019 RE LSMC Medical Office Bldg Tenant Suites - permit PRCOM20192572
12/11/2019 Letter Fire Building Plan Review
12/13/2019 CMR - PRCOM20192572
12/19/2019 LT update info
12/19/2019 Letter License Tax Bill
01/07/2020 Receipt Receipt for transaction: 2020-000070
01/07/2020 Letter DS Building Permit
02/04/2020 Receipt Receipt for transaction: 2020-000448
02/05/2020 Letter INSPECTION SUMMARY
02/06/2020 Letter INSPECTION SUMMARY
02/12/2020 Letter INSPECTION SUMMARY
02/12/2020 Letter INSPECTION SUMMARY
02/18/2020 Letter INSPECTION SUMMARY
02/20/2020 Letter INSPECTION SUMMARY
02/26/2020 Letter INSPECTION SUMMARY
02/26/2020 Letter INSPECTION SUMMARY
03/03/2020 Letter INSPECTION SUMMARY
04/03/2020 Letter INSPECTION SUMMARY
04/08/2020 Letter INSPECTION SUMMARY
04/13/2020 Letter INSPECTION SUMMARY
04/17/2020 Letter INSPECTION SUMMARY
04/21/2020 Letter INSPECTION SUMMARY
05/21/2020 Letter INSPECTION SUMMARY
05/21/2020 Letter INSPECTION SUMMARY
05/21/2020 Letter INSPECTION SUMMARY
05/22/2020 Letter Codes Temporary Certificate of Occupancy
05/27/2020 Letter Codes Temporary Certificate of Occupancy
07/17/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home