Permit Application Status

PRCOM20192047


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192047
Building Permit - Commercial
Certificate of Occupancy
PINE TREE PLAZA LLC
CHANGE OF TENANT
TENANT FINISH FOR SALES OF CONSTRUCTION TILE AND ASSOCIATED PRODUCTS
07/30/2019
09/09/2019
03/28/2020
11/19/2019
Locations
Contacts
PINE TREE PLAZA LLC, Address:601 E SOUTH ST  
DAN KUYKENDALL ENTERPRISES INC, Address:3856 IRON ORE DRIVE, Phone:(903) 821-1375  
RODINA COMPANY INC, Address:1204 N 59TH ST, Phone:(913) 334-5336  
M & G ELECTRICAL AND CONTRACTING SERVICES , Address:1035 GROOMS RD, Phone:(336) 394-4198  
RODINA COMPANY INC, Address:1204 N 59TH ST, Phone:(913) 334-5336  
STUDIO M ARCHITECTS INC, Address:530 NORTH 3RD STREET STE 230, Phone:(612) 841-1243  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/24/2019
Michael Weissenbach
Building Plan Review Approved with Conditions 10/07/2019 10/03/2019
Joe Frogge
License Tax Application
Corrective Action Required
09/30/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 8/29/19 - acknowledged in letter
Screening - Rooftop equipment
Corrective Action Required
09/30/2019

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section or provide verification that existing screening is adequate. 8/29/19 - Per architect, the units were installed at white box permit. Field verify
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
09/30/2019

1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish material at mop sink. 8/29/19 - deferred to construction - field verify
Fire Plan Review Approved with Conditions 10/07/2019 10/01/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
09/30/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for fire alarm system on any modifications to be done.
Address numbers required
Corrective Action Required
09/30/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
09/30/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for the fire sprinkler system on any modifications to be done.
Installation acceptance testing
Corrective Action Required
09/30/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing. All testing to be complete before an occupancy inspection.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/30/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Duct smoke detectors
Corrective Action Required
09/30/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes) CFM over 2000 will require duct detection.
Licensed Contractors Approved 10/07/2019 09/30/2019
Joe Frogge
Licensed Contractors Approved 09/06/2019 09/09/2019
Development Center
LC - General Contractor
Corrective Action Required
08/29/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 8/29/19 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
08/29/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 8/29/19 - acknowledged in letter
Building Plan Review Approved with Conditions 09/06/2019 08/29/2019
Joe Frogge
License Tax Application
Corrective Action Required
08/29/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 8/29/19 - acknowledged in letter
Screening - Rooftop equipment
Corrective Action Required
08/29/2019

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section or provide verification that existing screening is adequate. 8/29/19 - Per architect, the units were installed at white box permit. Field verify
Miscellaneous Correction
Resolved
08/29/2019

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Address the following: - Coordinate architectural and electrical drawings - provide exit sign at south side of corridor near restrooms - do not direct exiting through storage room
Bldg - Egress through intervening spaces 1014.2
Resolved
08/29/2019

2018 IBC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. Item 5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions) Action required: Exiting through storage room not allowed unless you can demonstrate compliance with listed exceptions.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
08/29/2019

1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish material at mop sink. 8/29/19 - deferred to construction - field verify
Bldg - Urinal partitions 1210.3.2
Resolved
08/29/2019

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Provide urinal partitions in male restroom or provide lockable door.
Plan Submittal 2012 Codes
Resolved
08/29/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update incorrect code references in General Notes on sheet M0.
Fire Plan Review Approved with Conditions 09/06/2019 08/29/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
08/29/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for fire alarm system on any modifications to be done.
Address numbers required
Corrective Action Required
08/29/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
08/29/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for the fire sprinkler system on any modifications to be done.
Installation acceptance testing
Corrective Action Required
08/29/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing. All testing to be complete before an occupancy inspection.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/29/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Egress through intervening spaces.
Resolved
08/29/2019

2018 IFC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. (Action Required) 1. Remove exit sign leading into the warehouse. 2. Provide sheet for exit/emergency lighting.
Duct smoke detectors
Corrective Action Required
08/29/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes) CFM over 2000 will require duct detection.
Fire Plan Review Rejected 08/09/2019 08/10/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
08/10/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of stamped shop drawings for fire alarm system on any modifications to be done.
Address numbers required
Corrective Action Required
08/10/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Construction documents - Fire protection systems
Corrective Action Required
08/10/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of stamped shop drawings for the fire sprinkler system on any modifications to be done.
Installation acceptance testing
Corrective Action Required
08/10/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing. All testing to be complete before an occupancy inspection.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/10/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Egress through intervening spaces.
Corrective Action Required
08/10/2019

2018 IFC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. (Action Required) 1. Remove exit sign leading into the warehouse. 2. Provide sheet for exit/emergency lighting.
Duct smoke detectors
Corrective Action Required
08/10/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes)
Building Plan Review Rejected 08/09/2019 08/09/2019
Joe Frogge
License Tax Application
Corrective Action Required
08/09/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
08/19/2019

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineered design for new roof penetrations and loads or provide engineer’s report to verify that existing roof structure will support additional load. 8/19/19 - verified that structural mods were designed under shell permit PRCOM20191560
Screening - Rooftop equipment
Corrective Action Required
08/09/2019

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section or provide verification that existing screening is adequate.
Miscellaneous Correction
Corrective Action Required
08/09/2019

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Address the following: - Coordinate architectural and electrical drawings - provide exit sign at south side of corridor near restrooms - do not direct exiting through storage room
Bldg - Egress through intervening spaces 1014.2
Corrective Action Required
08/09/2019

2018 IBC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. Item 5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions) Action required: Exiting through storage room not allowed unless you can demonstrate compliance with listed exceptions.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
08/09/2019

1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish material at mop sink.
Bldg - Urinal partitions 1210.3.2
Corrective Action Required
08/09/2019

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Provide urinal partitions in male restroom or provide lockable door.
Plan Submittal 2012 Codes
Corrective Action Required
08/09/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update incorrect code references in General Notes on sheet M0.
Licensed Contractors Rejected 08/09/2019 08/09/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
08/09/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/09/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $800.00 $800.00 Paid 09/09/2019
$44,092.50
8331507-Sewer Connection Fee $240.00 $240.00 Paid 09/09/2019
7232302-Commercial License Tax Fee $44,092.50 $44,092.50 Paid 09/09/2019
$44,092.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 9/13/2019 at 10:35 AM 09/13/2019
Misc
Partial Correction
09/13/2019
OK TO COVER WHEN READY WALLS WITH WIRING AT DISPLAY STRUCTURES EXCEPT ONE AT NW CORNER YET TO BE CONSTRUCTED.
Misc
Corrective Action Required
09/13/2019
WALLS AT RESTROOMS 103 & 104 NOT APPROVED TO COVER: - DRINKING FOUNTAIN PLUMBING AND WIRING NOT AT LOCATION PER DRAWING - NO BLOCKING FOUND FOR 18" VERTICAL GRAB BARS WORK AT AND ABOVE CEILINGS NOT COMPLETED - NOT READY FOR INSPECTION. LIGHTING NOT IN PLACE. BOXES ABOVE NOT CLOSED. ACCESS PANELS REQUIRED FOR ACCESS TO J.B.s ABOVE CEILING.
Misc
Corrective Action Required
09/13/2019
DEMISING WALL AND PASSAGEWAY WALL TO REAR DOOR NOT READY FOR INSPECTION.
In-wall Inspection Partial 9/19/2019 09/19/2019
Misc
Partial Correction
09/13/2019
OK TO COVER WHEN READY WALLS WITH WIRING AT DISPLAY STRUCTURES EXCEPT ONE AT NW CORNER YET TO BE CONSTRUCTED.
Misc
Corrective Action Required
09/13/2019
WALLS AT RESTROOMS 103 & 104 NOT APPROVED TO COVER: - DRINKING FOUNTAIN PLUMBING AND WIRING NOT AT LOCATION PER DRAWING - NO BLOCKING FOUND FOR 18" VERTICAL GRAB BARS WORK AT AND ABOVE CEILINGS NOT COMPLETED - NOT READY FOR INSPECTION. LIGHTING NOT IN PLACE. BOXES ABOVE NOT CLOSED. ACCESS PANELS REQUIRED FOR ACCESS TO J.B.s ABOVE CEILING.
Misc
Corrective Action Required
09/13/2019
DEMISING WALL AND PASSAGEWAY WALL TO REAR DOOR NOT READY FOR INSPECTION.
Miscellaneous Correction
Corrective Action Required
09/19/2019
Okay to cover Display walls on north wall Okay to cover north west display walls Okay to cover warehouse side of break room and corridor
In-wall Inspection Partial 10/11/2019 at 9:30 AM 10/11/2019
Misc
Partial Correction
09/19/2019
OK TO COVER WHEN READY WALLS WITH WIRING AT DISPLAY STRUCTURES EXCEPT ONE AT NW CORNER YET TO BE CONSTRUCTED.
Misc
Resolved
10/11/2019
WALLS AT RESTROOMS 103 & 104 NOT APPROVED TO COVER: - DRINKING FOUNTAIN PLUMBING AND WIRING NOT AT LOCATION PER DRAWING - NO BLOCKING FOUND FOR 18" VERTICAL GRAB BARS WORK AT AND ABOVE CEILINGS NOT COMPLETED - NOT READY FOR INSPECTION. LIGHTING NOT IN PLACE. BOXES ABOVE NOT CLOSED. ACCESS PANELS REQUIRED FOR ACCESS TO J.B.s ABOVE CEILING.
Misc
Resolved
10/11/2019
DEMISING WALL AND PASSAGEWAY WALL TO REAR DOOR NOT READY FOR INSPECTION.
Miscellaneous Correction
Partial Correction
10/11/2019
Okay to cover Display walls on north wall Okay to cover north west display walls Okay to cover warehouse side of break room and corridor
Misc
Partial Correction
10/11/2019
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: 103-105 RESTROOMS AND BREAKROOM;
Underslab Plumbing Inspection - Commercial Passed 10/11/2019 at 9:55 AM 10/11/2019
Gas Service Inspection - Commercial Passed 10/16/2019 10/16/2019 at 1:05 PM 10/16/2019
Gas Piping Inspection - Commercial Failed 10/16/2019 at 1:20 PM 10/16/2019
Misc
Corrective Action Required
10/16/2019
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING. SUPPORT SUPPORT WITHIN 18" OF ENDS, 90'S, TEES, AND JOINTS.
Misc
Corrective Action Required
10/16/2019
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF NIPPLE TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Corrective Action Required
10/16/2019
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. PAINT 100% OF STEEL PIPE INCLUDING AT SUPPORTS. SEE GAS PIPING AT METER AND ROOFTOP.
Above Ceiling Inspection Partial 10/17/2019 10/17/2019 10/17/2019
Miscellaneous Correction
Informational
10/17/2019
Okay to cover ceilings in restrooms and break room. *** Hallway is not completed ***
In-wall Inspection Passed 10/21/2019 10/21/2019 at 9:55 AM 10/21/2019
Misc
Resolved
10/21/2019
OK TO COVER WHEN READY WALLS WITH WIRING AT DISPLAY STRUCTURES EXCEPT ONE AT NW CORNER YET TO BE CONSTRUCTED.
Miscellaneous Correction
Resolved
10/21/2019
Okay to cover Display walls on north wall Okay to cover north west display walls Okay to cover warehouse side of break room and corridor
Misc
Resolved
10/21/2019
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: 103-105 RESTROOMS AND BREAKROOM;
Above Ceiling Inspection Passed 10/21/2019 at 10:15 AM 10/21/2019
Miscellaneous Correction
Resolved
10/21/2019
Okay to cover ceilings in restrooms and break room. *** Hallway is not completed ***
Underslab Electrical Inspection - Commercial Passed 10/22/2019 10/22/2019 at 10:40 AM 10/22/2019
Rough Electrical Inspection - Commercial Passed 10/25/2019 10/25/2019 at 1:40 PM 10/25/2019
Alarm Test Passed 11/7/2019 11/07/2019
Miscellaneous Inspection Partial 11/11/2019 at 2:05 PM 11/11/2019
Miscellaneous Inspection Partial 11/12/2019 at 7:55 AM 11/12/2019
Miscellaneous Inspection Passed 11/12/2019 at 3:00 PM 11/12/2019
Gas Piping Inspection - Commercial Passed 11/13/2019 at 11:15 AM 11/13/2019
Misc
Resolved
11/13/2019
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING. SUPPORT SUPPORT WITHIN 18" OF ENDS, 90'S, TEES, AND JOINTS.
Misc
Resolved
11/13/2019
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF NIPPLE TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Resolved
11/13/2019
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. PAINT 100% OF STEEL PIPE INCLUDING AT SUPPORTS. SEE GAS PIPING AT METER AND ROOFTOP.
Occupancy Inspection - Codes Commercial Failed 11/13/2019 11/13/2019 at 1:40 PM 11/13/2019
Misc
Corrective Action Required
11/13/2019
ROOFTOP GAS PIPING: SOME SUPPORT BLOCKS DO NOT HAVE STRAPS SOME SUPPORT BLOCK STRAPS DO NOT HAVE BOLTS ONE OR MORE DIRT LEGS DO NOT HAVE CLEARANCE
Misc
Corrective Action Required
11/13/2019
ROOFTOP CLEANUP: REMOVE ALL EXCESS MATERIAL AND DEBRIS ON TENANT FOOTPRINT
Misc
Corrective Action Required
11/13/2019
STOREFRONT GLAZING MUST BE TEMPERED. NOT CLEANED TO DETERMINE.
Misc
Corrective Action Required
11/13/2019
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Corrective Action Required
11/13/2019
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Corrective Action Required
11/13/2019
ICC A117.1 609.4: VERTICAL GRAB BARS NOT INSTALLED AT ACCESSIBLE RESTROOMS
Misc
Corrective Action Required
11/13/2019
ELECT RECEPTS LOOSE AT: - SHOWROOM N WALL - MICROWAVE AT BREAK ROOM
Misc
Corrective Action Required
11/13/2019
JANITOR SINK NOT INSTALLED AT STOCK ROOM
Misc
Corrective Action Required
11/13/2019
OBTAIN APPROVAL FROM LSFD
Occupancy Inspection - Fire Failed 11/13/2019 11/13/2019 11/13/2019
Occupancy Inspection - Codes Commercial Temporary C of O 11/15/2019 11/15/2019 at 2:45 PM 11/15/2019
Misc
Corrective Action Required
11/13/2019
ROOFTOP GAS PIPING: TWO REQUIRED SUPPORT BLOCKS LACK STRAPS TWO DIRT LEGS ARE NOT PAINTED
Misc
Resolved
11/15/2019
ROOFTOP CLEANUP: REMOVE ALL EXCESS MATERIAL AND DEBRIS ON TENANT FOOTPRINT
Misc
Resolved
11/15/2019
STOREFRONT GLAZING MUST BE TEMPERED. NOT CLEANED TO DETERMINE.
Misc
Resolved
11/15/2019
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Resolved
11/15/2019
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF
Misc
Resolved
11/15/2019
ICC A117.1 609.4: VERTICAL GRAB BARS NOT INSTALLED AT ACCESSIBLE RESTROOMS
Misc
Resolved
11/15/2019
ELECT RECEPTS LOOSE AT: - SHOWROOM N WALL - MICROWAVE AT BREAK ROOM
Misc
Corrective Action Required
11/15/2019
JANITOR FLOOR SINK BEING CONSTRUCTED AT STOCK ROOM
Misc
Resolved
11/15/2019
OBTAIN APPROVAL FROM LSFD
Misc
Resolved
11/15/2019
M/E/P HUNG FROM ROOF DECK REQUIRES A/E LETTER.
Misc
Resolved
11/15/2019
F.D. AT STOCK ROOM NEEDS NEW GRATE
Occupancy Inspection - Codes Commercial Full C of O 11/19/2019 at 2:35 PM 11/19/2019
Misc
Resolved
11/19/2019
ROOFTOP GAS PIPING: TWO REQUIRED SUPPORT BLOCKS LACK STRAPS TWO DIRT LEGS ARE NOT PAINTED
Misc
Resolved
11/19/2019
JANITOR FLOOR SINK BEING CONSTRUCTED AT STOCK ROOM
Documents & Images
Date Uploaded File Type Document Name
08/10/2019 Letter Fire Building Plan Review
08/11/2019 Letter DS P/R Corrections Document
08/19/2019 design coordination
08/29/2019 Letter Fire Building Plan Review
09/09/2019 Receipt Receipt for transaction: 2019-006098
09/09/2019 Letter DS Building Permit
09/09/2019 Letter License Tax Bill
09/13/2019 Letter INSPECTION SUMMARY
09/19/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter Fire Building Plan Review
10/11/2019 Letter INSPECTION SUMMARY
10/11/2019 Letter INSPECTION SUMMARY
10/16/2019 Letter INSPECTION SUMMARY
10/16/2019 Letter INSPECTION SUMMARY
10/17/2019 Letter INSPECTION SUMMARY
10/21/2019 Letter INSPECTION SUMMARY
10/21/2019 Letter INSPECTION SUMMARY
10/24/2019 Letter Fire (Alarm) Plan Review Notice
10/25/2019 Letter INSPECTION SUMMARY
11/13/2019 Letter INSPECTION SUMMARY
11/15/2019 Letter Codes Temporary Certificate of Occupancy
11/19/2019 Letter Field Certificate of Occupancy
11/25/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home