Permit Application Status

PRCOM20191408


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191408
Building Permit - Commercial
Certificate of Occupancy
MCBOB LLC
ADDITION COMMERCIAL
ADDITION TO CAR DEALERSHIP
05/31/2019
07/19/2019
12/09/2019
12/31/2019
Locations
Contacts
MCBOB LLC, Address:3200 NW OUTER RD S  
ROTHWELL CONSTRUCTION INC, Address:1500 NORTH 7 HWY STE 100, Phone:(816) 228-8808  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
BCI MECHANICAL INC, Address:P O BOX 441, Phone:(913) 856-6747  
KASA ELECTRIC LLC, Address:1206 NW VALLEY RIDGE DR, Phone:(816) 228-4886  
TAYLOR MECHANICAL INC, Address:23700 E 189th st, Phone:(816) 743-9900  
JEFF@ROTHWELL-CONSTRUCTION.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/17/2019
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
10/17/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hydrostatic Test. Current annual inspection tag to be on the riser.
Alarm Plan Review Released for Construction 09/25/2019
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
09/25/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
09/25/2019

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. (Informational Purposes) Alarm system to be operational in the existing space during construction.
Final Development Plan Review Approved 07/19/2019
Joe Frogge
Building Plan Review Approved with Conditions 06/24/2019 06/18/2019
Joe Frogge
Final Development Plan
Resolved
07/19/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 6/18/19 - acknowledged in letter
License Tax Application
Corrective Action Required
06/17/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/18/19 - acknowledged in letter
Code analysis required
Resolved
06/18/2019

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Provide occupant load calculations. Include restroom fixture calculations to verify that existing fixtures are adequate.
Miscellaneous Correction
Resolved
06/18/2019

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Action required: Provide ladders at parapets between old and new construction.
Licensed Contractors Approved 06/17/2019 06/18/2019
Joe Frogge
Fire Plan Review Approved with Conditions 06/24/2019 06/17/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
06/17/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide shop drawings for any modifications performed on the alarm system
Hazardous material identification
Corrective Action Required
06/17/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Action Required) Provide placards for rooms containing hazardous materials
Address numbers required
Corrective Action Required
06/17/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Address building 2101 readable from roadway
Construction documents - Fire protection systems
Corrective Action Required
06/17/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide shop drawings for any modifications performed on the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
06/17/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/17/2019

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. (Action Required) Existing sprinkler system to remain fully functional during construction. New FDC to be functional as soon as possible
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/17/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide 3 2A10BC extinguishers near the exits.
Duct smoke detectors
Corrective Action Required
06/17/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes)
Illumination required
Corrective Action Required
06/17/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required)(Verified At Inspection) Add emergency lighting to mezzanine and stairwell.
Fire Plan Review Approved with Conditions 06/14/2019 06/11/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
06/11/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide shop drawings for any modifications performed on the alarm system
Hazardous material identification
Corrective Action Required
06/11/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Action Required) Provide placards for rooms containing hazardous materials
Address numbers required
Corrective Action Required
06/11/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Action Required) Address building 2101 readable from roadway
Construction documents - Fire protection systems
Corrective Action Required
06/11/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide shop drawings for any modifications performed on the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
06/11/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/11/2019

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. (Action Required) Existing sprinkler system to remain fully functional during construction. New FDC to be functional as soon as possible
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/11/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide 3 2A10BC extinguishers near the exits.
Duct smoke detectors
Corrective Action Required
06/11/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Informational Purposes)
Illumination required
Corrective Action Required
06/11/2019

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Add emergency lighting to mezzanine and stairwell.
Building Plan Review Rejected 06/14/2019 06/05/2019
Joe Frogge
Final Development Plan
Corrective Action Required
06/05/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
06/05/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Code analysis required
Corrective Action Required
06/05/2019

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Provide occupant load calculations. Include restroom fixture calculations to verify that existing fixtures are adequate.
Miscellaneous Correction
Corrective Action Required
06/05/2019

2018 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Action required: Provide ladders at parapets between old and new construction.
Licensed Contractors Approved 06/14/2019 05/31/2019
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Addition to Commercial $4,787.84 $4,787.84 Paid Not payable online 07/19/2019
8331507-Sewer Connection Fee $30.00 $30.00 Paid Not payable online 07/19/2019
Outstanding Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $21,862.50 $0.00 $21,862.50 Not Paid


$21,862.50    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Failed 8/6/2019 (1:00) 8/6/2019 at 1:10 PM 08/06/2019
Misc
Corrective Action Required
08/06/2019
not ready
Footing Inspection - Commercial Partial 8/6/2019 at 2:40 PM 08/06/2019
Misc
Partial Correction
08/06/2019
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: FROM K/7 CCW TO K.8/4;
Footing Inspection - Commercial Partial 8/9/2019 (8:00) 8/9/2019 at 8:15 AM 08/09/2019
Misc
Partial Correction
08/06/2019
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: FROM K/7 CCW TO K.8/4; THE REST OF INT&EXT GB
Footing Inspection - Commercial Partial 8/13/2019 8/13/2019 at 9:45 AM 08/13/2019
Misc
Partial Correction
08/09/2019
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: AREA A & B
Underslab Plumbing Inspection - Commercial Partial 8/23/2019 8/23/2019 at 1:45 PM 08/23/2019
Misc
Corrective Action Required
08/23/2019
UNDERSLAB UNDER SERVICE BAYS 153&154&155: SUBMIT AS-BUILT FOR CHANGE IN LOCATION OF THE TRENCH DRAIN AND DELETE OF EXISTING 4" DRAIN CONNECTION TO THE WASTE PUMP
In-wall Inspection Partial 9/24/2019 9/24/2019 at 11:10 AM 09/24/2019
Misc
Partial Correction
09/24/2019
IN-WALL OK: -ALTERATION TO EXISTING MANAGER OFFICE RM 112
Underslab Electrical Inspection - Commercial Partial 9/30/2019 09/30/2019
Misc
Partial Correction
09/30/2019
SERVICE BAY UE OK
In-wall Inspection Partial 9/30/2019 9/30/2019 at 10:45 AM 09/30/2019
Misc
Partial Correction
09/24/2019
IN-WALL OK: -ALTERATION TO EXISTING MANAGER OFFICE RM 112; RM 102-OK TO COVER EXTERIOR SIDE OF EXTERIOR WALL
In-wall Inspection Partial 10/9/2019 10/9/2019 at 12:55 PM 10/09/2019
Misc
Partial Correction
09/30/2019
IN-WALL OK: -ALTERATION TO EXISTING MANAGER OFFICE RM 112; RM 102-107
In-wall Inspection Partial 10/21/2019 10/21/2019 at 1:10 PM 10/21/2019
Misc
Partial Correction
10/09/2019
IN-WALL OK: -ALTERATION TO EXISTING MANAGER OFFICE RM 112; RM 102-107; RM 122-125, 129
Gas Piping Inspection - Commercial Passed 10/22/2019 at 10:30 AM 10/22/2019
In-wall Inspection Partial 10/24/2019 10/24/2019 at 1:55 PM 10/24/2019
Misc
Partial Correction
10/21/2019
IN-WALL OK: -ALTERATION TO EXISTING MANAGER OFFICE RM 112; RM 102-107; RM 122-125, 129; COUNTER WALL IN RM 131, 156
In-wall Inspection Partial 11/6/2019 11/6/2019 at 10:25 AM 11/06/2019
Misc
Partial Correction
10/24/2019
IN-WALL OK: -ALTERATION TO EXISTING MANAGER OFFICE RM 112; RM 102-107; RM 122-125, 129; COUNTER WALL IN RM 131, 156; RM 135-136
Above Ceiling Inspection Partial 11/6/2019 11/6/2019 at 2:20 PM 11/06/2019
Misc
Partial Correction
11/06/2019
ABOVE-CEILING OK: -TWO OFFICES-OK TO MOVE ITEMS IN WHILE WORK CONTINUE IN SHOW ROOM
Above Ceiling Inspection Failed 11/15/2019 11/15/2019 at 9:55 AM 11/15/2019
Misc
Partial Correction
11/06/2019
ABOVE-CEILING OK: -TWO OFFICES-OK TO MOVE ITEMS IN WHILE WORK CONTINUE IN SHOW ROOM -RM 103-106 INSPECTED. REMOVE NON-PLENUM RATED CABLE FROM ABOVE-CEILING PLENUM SPACE; WRAP EXPOSED ROOF DRAIN PVC PIPES LOCATED IN PLENUM SPACE WITH APPROVED LISTED MATERIAL
Sprinkler - Hydrostatic Test Passed 11/15/2019 11/15/2019
In-wall Inspection Passed 11/19/2019 11/19/2019 11/19/2019
Misc
Resolved
11/19/2019
IN-WALL OK: -ALTERATION TO EXISTING MANAGER OFFICE RM 112; RM 102-107; RM 122-125, 129; COUNTER WALL IN RM 131, 156; RM 135-136
Above Ceiling Inspection Partial 11/19/2019 11/19/2019 11/19/2019
Misc
Partial Correction
11/15/2019
-WRAP EXPOSED PVC IN PLENUM SPACE ABOVE SHOW RM OFFICE WITH APPROVED LISTED MATERIAL
Above Ceiling Inspection Passed 11/21/2019 11/21/2019 11/21/2019
Misc
Resolved
11/21/2019
-WRAP EXPOSED PVC IN PLENUM SPACE ABOVE SHOW RM OFFICE WITH APPROVED LISTED MATERIAL
Above Ceiling Inspection Passed 11/26/2019 11/26/2019 at 10:10 AM 11/26/2019
Underslab Electrical Inspection - Commercial Passed 11/26/2019
Misc
Resolved
11/26/2019
SERVICE BAY UE OK
Underslab Plumbing Inspection - Commercial Passed 11/26/2019
Misc
Resolved
11/26/2019
UNDERSLAB UNDER SERVICE BAYS 153&154&155: SUBMIT AS-BUILT FOR CHANGE IN LOCATION OF THE TRENCH DRAIN AND DELETE OF EXISTING 4" DRAIN CONNECTION TO THE WASTE PUMP
Footing Inspection - Commercial Passed 11/26/2019
Misc
Resolved
11/26/2019
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: AREA A & B
Sewer Service Inspection Passed 8/2/2019 8/2/2019 12/03/2019
Occupancy Inspection - Fire Temporary C of O 12/3/2019 12/3/2019 12/03/2019
Alarm Test Passed 12/3/2019 12/03/2019
Occupancy Inspection - Codes Commercial Temporary C of O 12/3/2019 12/16/2019 at 2:40 PM 12/03/2019
Misc
Corrective Action Required
12/03/2019
-APPROVAL FROM THE FOLLOWING DEPT REQUIRED: FIRE, PLANNING, FIELD SERVICE -COMPLETE PL LIGHT INSTALLATION -LABEL ALL BREAKERS -HANDRAIL FOR MEZZANINE STAIR SHALL COMPLY WITH IBC 1014.6. GUADRAIL HEIGHT SHALL BE MIN 42" PER IBC 1015.3
Occupancy Inspection - Engineering Temporary C of O 12/4/2019 12/04/2019
Occupancy Inspection - Planning Temporary C of O 12/3/2019 12/3/2019 12/04/2019
Corrective Action Required
12/03/2019
Replace dead/stressed shrub on the east side of the new trash enclosure. Also, install additional shrubs on the east side of the new trash enclosure per the approved landscape plan.
Corrective Action Required
12/04/2019
Complete re-installation of the parking lot light pole on the west side of the building.
Sprinkler - Hydrostatic Test Passed 12/17/2019 12/17/2019
Occupancy Inspection - Fire Passed 12/17/2019 12/17/2019
Occupancy Inspection - Codes Commercial Temporary C of O 12/18/2019 12/18/2019 at 2:20 PM 12/18/2019
Misc
Corrective Action Required
12/03/2019
-APPROVAL FROM THE FOLLOWING DEPT REQUIRED: PLANNING, FIELD SERVICE -HANDRAIL FOR MEZZANINE STAIR SHALL COMPLY WITH IBC 1014.6.GUADRAIL HEIGHT SHALL BE MIN 42" PER IBC 1015.3
Occupancy Inspection - Codes Commercial Full C of O 12/31/2019 12/31/2019 at 3:00 PM 12/31/2019
Misc
Resolved
12/31/2019
-APPROVAL FROM THE FOLLOWING DEPT REQUIRED: PLANNING, FIELD SERVICE
Documents & Images
Date Uploaded File Type Document Name
06/03/2019 Letter License Tax Bill
06/11/2019 Letter Fire Building Plan Review
06/12/2019 Letter DS P/R Corrections Document
06/17/2019 Letter Fire Building Plan Review
07/19/2019 Letter Codes Plan Review Conditions
07/19/2019 Receipt Receipt for transaction: 2019-004914
07/19/2019 Letter DS Building Permit
08/06/2019 Letter INSPECTION SUMMARY
08/09/2019 Letter INSPECTION SUMMARY
08/13/2019 Letter INSPECTION SUMMARY
08/23/2019 Letter INSPECTION SUMMARY
09/24/2019 Letter INSPECTION SUMMARY
09/25/2019 Letter Fire (Alarm) Plan Review Notice
09/25/2019 Letter Fire (Alarm) Plan Review Notice
09/30/2019 Letter INSPECTION SUMMARY
09/30/2019 Letter INSPECTION SUMMARY
10/09/2019 Letter INSPECTION SUMMARY
10/17/2019 Letter Fire (Sprinkler) Plan Review
10/21/2019 Letter INSPECTION SUMMARY
10/22/2019 Letter INSPECTION SUMMARY
10/24/2019 Letter INSPECTION SUMMARY
11/06/2019 Letter INSPECTION SUMMARY
11/15/2019 Letter INSPECTION SUMMARY
11/19/2019 Letter INSPECTION SUMMARY
11/21/2019 Letter INSPECTION SUMMARY
11/21/2019 Letter INSPECTION SUMMARY
11/21/2019 Letter INSPECTION SUMMARY
11/21/2019 Letter INSPECTION SUMMARY
11/21/2019 Letter INSPECTION SUMMARY
11/21/2019 Letter DS Building Permit
11/21/2019 Letter Fire Building Plan Review
11/26/2019 Letter INSPECTION SUMMARY
11/26/2019 Letter INSPECTION SUMMARY
11/26/2019 Letter INSPECTION SUMMARY
11/26/2019 Letter INSPECTION SUMMARY
12/03/2019 Letter INSPECTION SUMMARY
12/03/2019 Letter Codes Temporary Certificate of Occupancy
12/18/2019 Letter Codes Temporary Certificate of Occupancy
12/31/2019 Letter Codes Final Certificate of Occupancy
12/31/2019 Letter Field Certificate of Occupancy
01/13/2020 Engineer Report/Study Scanned from a Xerox Multifunction Printer
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home