Summary
PRCOM20191238
Building Permit - Commercial
Certificate of Occupancy
PINE TREE PLAZA LLC
CHANGE OF TENANT
TENANT FINISH FOR MASSAGE BUSINESS
05/14/2019
06/21/2019
11/26/2019
09/24/2019
Locations
Contacts
PINE TREE PLAZA LLC, Address:601 E SOUTH ST  
NEIGHBORS CONSTRUCTION COMPANY INC, Address:1708 E 123RD ST, Phone:(913) 422-5555  
ALDEN PLUMBING & MECHANICAL LLC, Address:5600 W 95TH ST STE307, Phone:(816) 666-8662  
ALLIED ELECTRICAL CONSTRUCTION INC, Address:13416 HORSESHOE DR W, Phone:(816) 532-4446  
BLUE RIVER PLUMBING INC, Address:9125 BARTON ST, Phone:(913) 701-6410  
  
JOWLER CREEK ARCHITECTURE, Address:15105 JOWLER CREEK RD, Phone:(816) 876-6794  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 06/14/2019 06/19/2019
Joe Frogge
LC - MEP Subs
Resolved
06/19/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 5/24/19 - acknowledged in letter
Building Plan Review Approved with Conditions 06/21/2019 06/14/2019
Joe Frogge
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
06/14/2019

2018 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Provide minimum 36" wide section of counter that is no taller than 36". 5/24/19 - Architect's letter states that the tenant has , per business plan, instructions to provide individual help to those in need.
Misc
Resolved
06/14/2019

City of Lee's Summit Code of Ordinances Section 28-63 thru 28-65. Actions required: - (28-63 C 3a) Provide verification that paints will be washable and mold resistant. - (28-65 F) Provide separate dressing room for each sex with individual lockers for each therapist and employee with inwardly opening doors. 5/30/19 - we are unable at this time to approve the Code Modification Request (CMR) that was submitted. The issue has been raised with our law department but we have yet to receive a response.
Fire Plan Review Approved with Conditions 06/21/2019 06/14/2019
Joe Frogge
Tenant identification
Corrective Action Required
06/14/2019

2018 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. ACTION REQUIRED: (verified at inspection) All rooms shall be identified with the type of room use. Room identifiaction shall be readable from the corridor. Storage, utility room, massage room etc.
Address numbers required
Corrective Action Required
06/14/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Front and rear door addressing shall be readable from the roadway. Interior business door off the the rear common area shall be addressed.
Duct smoke detectors
Corrective Action Required
06/14/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED: Duct detection required to be installed. Include remote test switches with audible alarms.
Door operations
Corrective Action Required
06/14/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ACTION REQUIRED:(verified at inspection) No keyed locks on the egress side (interior) of an exit.
Building Plan Review Rejected 05/30/2019 05/30/2019
Joe Frogge
License Tax Application
Resolved
05/24/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Bldg - Occupant load calculations - Increased 1004.2
Resolved
05/24/2019

2018 IBC 1004.5.1 - Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted.
Miscellaneous Correction
Resolved
05/24/2019

2018 IBC 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the minimum width or required capacity of a means of egress component except projections permitted by this chapter. The minimum width or required capacity of a means of egress system shall not be diminished along the path of egress travel. Action required: Drinking fountain shall not reduce the minimum required corridor width of 36". To be field verified.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
05/22/2019

2018 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Provide minimum 36" wide section of counter that is no taller than 36". 5/24/19 - Architect's letter states that the tenant has , per business plan, instructions to provide individual help to those in need.
Accessibility - Water closet clearance width 604.3.1
Resolved
05/24/2019

ICC A117.1-2017 604.3.1 – Clearance width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Minimum water closet clearance not met as drawn.
Misc
Corrective Action Required
05/22/2019

City of Lee's Summit Code of Ordinances Section 28-63 thru 28-65. Actions required: - (28-63 C 3a) Provide verification that paints will be washable and mold resistant. - (28-65 F) Provide separate dressing room for each sex with individual lockers for each therapist and employee with inwardly opening doors. 5/30/19 - we are unable at this time to approve the Code Modification Request (CMR) that was submitted. The issue has been raised with our law department but we have yet to receive a response.
Licensed Contractors Rejected 05/30/2019 05/24/2019
Joe Frogge
LC - General Contractor
Resolved
05/24/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/22/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 5/24/19 - acknowledged in letter
Fire Plan Review Approved with Conditions 05/30/2019 05/23/2019
Joe Dir
Misc
Resolved
05/23/2019

Door swing ACTION REQUIRED: Reverse the door swing of the egress door leading from massage area into the lounge/ reception area (100) to swing in the direction of egress.
Tenant identification
Corrective Action Required
05/22/2019

2018 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. ACTION REQUIRED: (verified at inspection) All rooms shall be identified with the type of room use. Room identifiaction shall be readable from the corridor. Storage, utility room, massage room etc.
Address numbers required
Corrective Action Required
05/22/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Front and rear door addressing shall be readable from the roadway. Interior business door off the the rear common area shall be addressed.
Duct smoke detectors
Corrective Action Required
05/22/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED: Duct detection required to be installed. Include remote test switches with audible alarms.
Door operations
Corrective Action Required
05/22/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ACTION REQUIRED:(verified at inspection) No keyed locks on the egress side (interior) of an exit.
Panic and fire exit hardware
Resolved
05/23/2019

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. ACTION REQUIRED: Add the occupant load of the storage area to the total occupant of the business. Panic hardware may be required for exits.
Building Plan Review Rejected 05/24/2019 05/20/2019
Joe Frogge
License Tax Application
Corrective Action Required
05/20/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Bldg - Occupant load calculations - Increased 1004.2
Corrective Action Required
05/20/2019

2018 IBC 1004.5.1 - Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted.
Miscellaneous Correction
Corrective Action Required
05/20/2019

2018 IBC 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the minimum width or required capacity of a means of egress component except projections permitted by this chapter. The minimum width or required capacity of a means of egress system shall not be diminished along the path of egress travel. Action required: Drinking fountain shall not reduce the minimum required corridor width of 36". To be field verified.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
05/20/2019

2018 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Provide minimum 36" wide section of counter that is no taller than 36".
Accessibility - Water closet clearance width 604.3.1
Corrective Action Required
05/20/2019

ICC A117.1-2017 604.3.1 – Clearance width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Minimum water closet clearance not met as drawn.
Misc
Corrective Action Required
05/20/2019

City of Lee's Summit Code of Ordinances Section 28-63 thru 28-65. Actions required: - (28-63 C 3a) Provide verification that paints will be washable and mold resistant. - (28-65 F) Provide separate dressing room for each sex with individual lockers for each therapist and employee with inwardly opening doors.
Licensed Contractors Rejected 05/20/2019
Joe Frogge
LC - General Contractor
Corrective Action Required
05/20/2019

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/20/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 05/24/2019 05/16/2019
Joe Dir
Misc
Corrective Action Required
05/16/2019

Door swing ACTION REQUIRED: Reverse the door swing of the egress door leading from massage area into the lounge/ reception area (100) to swing in the direction of egress.
Tenant identification
Corrective Action Required
05/16/2019

2018 IFC 408.11.2 - Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. ACTION REQUIRED: (verified at inspection) All rooms shall be identified with the type of room use. Room identifiaction shall be readable from the corridor. Storage, utility room, massage room etc.
Address numbers required
Corrective Action Required
05/16/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Front and rear door addressing shall be readable from the roadway. Interior business door off the the rear common area shall be addressed.
Duct smoke detectors
Corrective Action Required
05/16/2019

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. ACTION REQUIRED: Duct detection required to be installed. Include remote test switches with audible alarms.
Door operations
Corrective Action Required
05/16/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ACTION REQUIRED:(verified at inspection) No keyed locks on the egress side (interior) of an exit.
Panic and fire exit hardware
Corrective Action Required
05/16/2019

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. ACTION REQUIRED: Add the occupant load of the storage area to the total occupant of the business. Panic hardware may be required for exits.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $600.00 $600.00 Paid 06/21/2019
$8,250.00
7232302-Commercial License Tax Fee $8,250.00 $8,250.00 Paid 06/19/2019
$8,250.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sprinkler - Flow Test Partial 7/5/2019 at 7:20 AM 07/05/2019
Miscellaneous Inspection Partial 7/8/2019 at 2:50 PM 07/08/2019
Underslab Plumbing Inspection - Commercial Failed 7/17/2019 at 8:50 AM 07/17/2019
Underslab Plumbing Inspection - Commercial Partial 7/18/2019 7/18/2019 at 9:45 AM 07/18/2019
Misc
Partial Correction
07/18/2019
OK TO COVER EXCEPT AT FERNCO CONNECTION TO MAIN BUILDING DRAIN. REPLACE WITH STIFFBACK.
Underslab Plumbing Inspection - Commercial Passed 7/19/2019 at 8:45 AM 07/19/2019
Misc
Resolved
07/19/2019
OK TO COVER EXCEPT AT FERNCO CONNECTION TO MAIN BUILDING DRAIN. REPLACE WITH STIFFBACK.
All Rough Inspection - Commercial Failed 7/29/2019 7/30/2019 at 7:20 AM 07/29/2019
Misc
Corrective Action Required
07/29/2019
door locked
In-wall Inspection Failed 7/31/2019 at 7:10 AM 07/31/2019
Misc
Corrective Action Required
07/31/2019
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE BOCA PLATES). CHECK ALL.
Misc
Partial Correction
07/31/2019
OK TO INSULATE WALLS
In-wall Inspection Passed 8/2/2019 at 7:10 AM 08/02/2019
Misc
Resolved
08/02/2019
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE BOCA PLATES). CHECK ALL.
Misc
Resolved
08/02/2019
OK TO INSULATE WALLS
Occupancy Inspection - Water Utilities Passed 9/20/2019 08/21/2019
Above Ceiling Inspection Failed 9/11/2019 9/11/2019 at 7:10 AM 09/11/2019
Misc
Corrective Action Required
09/11/2019
AT RE-INSPECTION PROVIDE: - CITY-STAMPED PERMIT PRINT SET - LADDER 6' OR 8'
Misc
Corrective Action Required
09/11/2019
COMPLETE ABOVE-CEILING REMOVALS INCLUDING: - ABANDONED STUD MATERIAL - ABANDONED STRAP AND ALL-THREAD HANGERS
Misc
Corrective Action Required
09/11/2019
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT: SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL RE SUPPORT AT 5' MAX INTERVALS WITH 1-1/2" MIN WIDTH HANGERS. CLAMPS & LISTED TAPING OF INNER AND OUTER LAYER MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS.
Misc
Corrective Action Required
09/11/2019
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: SECURELY FASTEN WITHIN 12" OF ENTRY TO BOXES, INCLUDING FIXTURE WHIPS IN EXCESS OF 6` LONG
Misc
Corrective Action Required
09/11/2019
NEC 110-12: CHECK ALL ELECTRICAL JUNCTION BOXES FOR UNUSED OPENINGS - PLUG
Above Ceiling Inspection Passed 9/12/2019 9/12/2019 at 7:00 AM 09/12/2019
Misc
Resolved
09/12/2019
AT RE-INSPECTION PROVIDE: - CITY-STAMPED PERMIT PRINT SET - LADDER 6' OR 8'
Misc
Resolved
09/12/2019
COMPLETE ABOVE-CEILING REMOVALS INCLUDING: - ABANDONED STUD MATERIAL - ABANDONED STRAP AND ALL-THREAD HANGERS
Misc
Resolved
09/12/2019
SMACNA / AIR DIFUSSION COUNCIL / MANUFACTURER'S INSTRUCTIONS > INSTALLATION OF HVAC FLEXIBLE DUCT: SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL RE SUPPORT AT 5' MAX INTERVALS WITH 1-1/2" MIN WIDTH HANGERS. CLAMPS & LISTED TAPING OF INNER AND OUTER LAYER MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS.
Misc
Resolved
09/12/2019
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: SECURELY FASTEN WITHIN 12" OF ENTRY TO BOXES, INCLUDING FIXTURE WHIPS IN EXCESS OF 6` LONG
Misc
Resolved
09/12/2019
NEC 110-12: CHECK ALL ELECTRICAL JUNCTION BOXES FOR UNUSED OPENINGS - PLUG
Miscellaneous Inspection Passed 9/18/2019 at 2:15 PM 09/18/2019
All Rough Inspection - Commercial Passed 8/2/2019 09/18/2019
Misc
Resolved
09/18/2019
door locked
Occupancy Inspection - Fire Passed 9/20/2019 9/20/2019 09/20/2019
Occupancy Inspection - Codes Commercial Partial 9/20/2019 9/20/2019 09/20/2019
Misc
Informational
09/20/2019
Label doors Label panels Verify tenant separation
Occupancy Inspection - Codes Commercial Failed 9/23/2019 at 9:40 AM 09/23/2019
Misc
Corrective Action Required
09/20/2019
SEAL FLOOR SINK TO FLOOR
Misc
Corrective Action Required
09/23/2019
CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Occupancy Inspection - Codes Commercial Full C of O 9/24/2019 9/24/2019 at 1:30 PM 09/24/2019
Misc
Resolved
09/24/2019
SEAL FLOOR SINK TO FLOOR
Misc
Resolved
09/24/2019
CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Documents & Images
Date Uploaded File Type Document Name
05/16/2019 Letter Fire Building Plan Review
05/20/2019 Letter DS P/R Corrections Document
05/23/2019 Letter Fire Building Plan Review
05/30/2019 Letter DS P/R Corrections Document
06/14/2019 Letter License Tax Bill
06/21/2019 Receipt Receipt for transaction: 2019-003968
06/21/2019 Letter Codes Building Permit
06/21/2019 Letter Codes Plan Review Conditions
07/17/2019 Letter INSPECTION SUMMARY
07/18/2019 Letter INSPECTION SUMMARY
07/19/2019 Letter INSPECTION SUMMARY
07/29/2019 Letter INSPECTION SUMMARY
07/31/2019 Letter INSPECTION SUMMARY
08/02/2019 Letter INSPECTION SUMMARY
09/11/2019 Letter INSPECTION SUMMARY
09/12/2019 Letter INSPECTION SUMMARY
09/20/2019 Letter INSPECTION SUMMARY
09/23/2019 Letter INSPECTION SUMMARY
09/24/2019 Letter Field Certificate of Occupancy
09/25/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home