Permit Application Status

PRCOM20191222


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20191222
Building Permit - Commercial
Final Completion
RHOADES REAL ESTATE LLC
ALTERATION COMMERCIAL
CONSTRUCTION OF WALL TO SEPARATE 1 SPACE INTO 2 WHITE BOXES *drawing is in plan review file
05/13/2019
05/17/2019
05/22/2019
Locations
Contacts
HIRST & ASSOCIATES PC, Address:3810 NE BEECHWOOD DR, Phone:(816) 225-2550  
ASHLAR HOMES LLC, Address:2800 NW HUNTER DR, Phone:(816) 228-1188  
RHOADES REAL ESTATE LLC, Address:410 SE 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 05/23/2019 05/14/2019
Joe Dir
Address numbers required
Corrective Action Required
05/14/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Addressing of the white boxes shall be readable from the roadway.
Building Plan Review Approved 05/23/2019 05/13/2019
Joe Frogge
Licensed Contractors Rejected 05/23/2019 05/13/2019
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 05/17/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 5/22/2019 5/22/2019 at 9:20 AM 05/22/2019
Misc
Partial Correction
05/22/2019
AT SOUTH WING-WALL AT UNIT 107 STAPLE NMB CABLE WITHIN 8" OF ENTRY TO BOX. THEN OK TO COVER WALL CAVITIES.
Misc
Corrective Action Required
05/22/2019
TWO-GANG SWITCH BOX AT NORTH WING-WALL AT UNIT 107 IS SET MORE THAN 1/4" FROM FACE OF GWB. REQUIRES BOX EXTENSIONS TO CORRECT. ALSO, (SAME LOCATION) EQUIPMENT GROUND CONDUCTORS MUST BE CONNECTED WITH CRIMP CONNECTORS OR WIRE NUTS -- NOT JUST TWISTED TOGETHER.
In-wall Inspection Passed 5/22/2019 at 2:30 PM 05/22/2019
Misc
Resolved
05/22/2019
AT SOUTH WING-WALL AT UNIT 107 STAPLE NMB CABLE WITHIN 8" OF ENTRY TO BOX. THEN OK TO COVER WALL CAVITIES. TWO-GANG SWITCH BOX AT NORTH WING-WALL AT UNIT 107 IS SET MORE THAN 1/4" FROM FACE OF GWB. REQUIRES BOX EXTENSIONS TO CORRECT. ALSO, (SAME LOCATION) EQUIPMENT GROUND CONDUCTORS MUST BE CONNECTED WITH CRIMP CONNECTORS OR WIRE NUTS -- NOT JUST TWISTED TOGETHER.
Misc
Resolved
05/22/2019
TWO-GANG SWITCH BOX AT NORTH WING-WALL AT UNIT 107 IS SET MORE THAN 1/4" FROM FACE OF GWB. REQUIRES BOX EXTENSIONS TO CORRECT. ALSO, (SAME LOCATION) EQUIPMENT GROUND CONDUCTORS MUST BE CONNECTED WITH CRIMP CONNECTORS OR WIRE NUTS -- NOT JUST TWISTED TOGETHER.
Final Inspection - Commercial Passed 5/22/2019 05/22/2019
Documents & Images
Date Uploaded File Type Document Name
05/13/2019 Letter License Tax Not Applicable
05/14/2019 Letter Fire Building Plan Review
05/16/2019 Letter Codes Plan Review Conditions
05/17/2019 Receipt Receipt for transaction: 2019-002411
05/17/2019 Letter Codes Building Permit
05/22/2019 Letter INSPECTION SUMMARY
05/22/2019 Letter INSPECTION SUMMARY
05/22/2019 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home