Permit Application Status

PRCOM20182297


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20182297
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
CHANGE OF TENANT
TENANT FINISH FOR CARRY OUT BAKERY
07/19/2018
08/27/2018
05/06/2019
11/05/2018
Locations
Contacts
BRETON AVENIR CONSTRUCITON INC, Address:14724 PLEASANT VALLEY RD, Phone:(614) 344-4843  
CENTRAL SYSTEMS MECHANICAL INC, Address:104 W 9TH ST STE 303, Phone:(816) 228-2022  
SMART POWER SERVICES, Address:1151 SE CENTURY DR, Phone:(816) 366-0385  
KMZC PLUMBING INC, Address:301 W WEA ST  
LANDRY ARCHITECTS, Address:1202 RICHARDSON DRIVE STE 106, Phone:(214) 631-6941 Ext:106  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 09/17/2018
Joe Dir
Installation acceptance testing
Corrective Action Required
09/17/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the devices installed will be required prior to the tenants final occupancy inspection. Contact the fire department to schedule testing.(816)969-1300
Sprinkler Plan Review Released for Construction 09/06/2018
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
09/06/2018

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(verified at inspection) The existing systems riser shall be current with service and maintenance. A current service tag shall be posted on the systems riser.
Misc
Corrective Action Required
09/06/2018

VK302 155 degree head ACTION REQUIRED: Please consider placing a higher than a 155 degree head infront of the oven area.
Licensed Contractors Approved 07/31/2018 08/27/2018
Development Center
LC - General Contractor
Corrective Action Required
07/24/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
08/21/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 07/31/2018 07/25/2018
Joe Frogge
Suite address
Corrective Action Required
07/24/2018

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: The correct address for this suite is 910 NW Blue Pkwy, Unit:T. Please update your records.
Health Dept Review
Resolved
07/25/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
07/24/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Department Review Approved 07/25/2018
Joe Frogge
Fire Plan Review Approved with Conditions 07/31/2018 07/20/2018
Joe Dir
Construction documents - Fire protection systems
Corrective Action Required
07/20/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings for any modifications to be done to the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
07/20/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED(information purposes) Acceptance testing of the fire alarm system modification and duct detection will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Portable fire extinguishers - general
Corrective Action Required
07/20/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of one 2A-10BC fire extinguisher. The extinguisher is to be mounted in the kitchen area close to an exit
Health Dept Inspection
Corrective Action Required
07/20/2018

Duct detection ACTION REQUIRED:(information purposes) RTU-2 will require duct detection installed. 907.2.13.1.2 Duct smoke detection. Duct smoke detectors complying with Section 907.3.1 shall be located as follows: 1. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection.
Health Dept Inspection (aquatic)
Corrective Action Required
07/20/2018

Health Department ACTION REQUIRED:(information purposes) An inspection from the Mo. Heath Department will be required prior to the final occupancy inspection.
Construction documents for fire alarm systems
Corrective Action Required
07/20/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of any modifications to be done to the fire alarm system.
Address numbers required
Corrective Action Required
07/20/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address shall be readable from the roadway. Front and rear doors to be addressed.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,000.00 $1,000.00 Paid 08/27/2018
8331507-Sewer Connection Fee $210.00 $210.00 Paid 08/27/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 9/5/2018 at 10:30 AM 09/05/2018
Underslab Plumbing Inspection - Commercial Failed 9/7/2018 9/7/2018 at 7:35 AM 09/07/2018
Misc
Corrective Action Required
09/07/2018
UNDERSLAB DWV PIPING NOT PER APPROVED DRAWINGS.
Underslab Plumbing Inspection - Commercial Partial 9/10/2018 9/7/2018 at 12:35 PM 09/07/2018
Misc
Partial Correction
09/07/2018
UNDERSLAB DWV PIPING OK TO COVER EXCEPT PIPING FOR TWO F.D.s NEAR SOUTH WALL NOT SHOWN ON APPROVED DRAWINGS.
Underslab Plumbing Inspection - Commercial Passed 9/10/2018 9/10/2018 at 8:10 AM 09/10/2018
Misc
Resolved
09/10/2018
UNDERSLAB DWV PIPING OK TO COVER EXCEPT PIPING FOR TWO F.D.s NEAR SOUTH WALL NOT SHOWN ON APPROVED DRAWINGS.
In-wall Inspection Failed 9/17/2018 at 10:15 AM 09/17/2018
Misc
Corrective Action Required
09/17/2018
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. COLORADO JIMS DO NOT SECURE MC TO RESIST TUGGING. USE CLAMPS THAT FASTEN MC IN PLACE WITHIN 12" OF BOX ENTRY.
Misc
Corrective Action Required
09/17/2018
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
In-wall Inspection Failed 9/18/2018 9/18/2018 at 9:05 AM 09/18/2018
Misc
Resolved
09/18/2018
NEC 334-10 SECURING / SUPPORT OF MC ELECTRICAL CABLE: SECURE WITHIN 12" OF BOXES AND SUPPORT AT 6' MAX INTERVALS THEREAFTER. COLORADO JIMS DO NOT SECURE MC TO RESIST TUGGING. USE CLAMPS THAT FASTEN MC IN PLACE WITHIN 12" OF BOX ENTRY.
Misc
Resolved
09/18/2018
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES). CHECK ALL.
Misc
Corrective Action Required
09/18/2018
PLUMBING SPECIFICATION REQUIRES TYPE "L" COPPER TUBING FOR H & C WATER
Misc
Corrective Action Required
09/18/2018
OVEN IS OBSTRUCTING WALL COVERINGS
In-wall Inspection Passed 9/20/2018 9/20/2018 at 2:25 PM 09/20/2018
Misc
Resolved
09/20/2018
PLUMBING SPECIFICATION REQUIRES TYPE "L" COPPER TUBING FOR H & C WATER
Misc
Resolved
09/20/2018
OVEN IS OBSTRUCTING WALL COVERINGS
Above Ceiling Inspection Failed 9/26/2018 at 10:50 AM 09/26/2018
Misc
Corrective Action Required
09/26/2018
ATTEMPTED TO CONTACT PHONE NUMBER PROVIDED TO INQUIRE ABOUT INSPECTION REQUEST. VOICEMAIL.
Above Ceiling Inspection Partial 9/28/2018 9/28/2018 09/28/2018
Misc
Partial Correction
09/28/2018
STELL FOR RTU WELDS INSPECTED ONLY. NO VISIBLE ISSUES
Above Ceiling Inspection Partial 10/11/2018 10/11/2018 at 8:15 AM 10/11/2018
Misc
Partial Correction
09/28/2018
STELL FOR RTU WELDS INSPECTED ONLY. NO VISIBLE ISSUES
Misc
Partial Correction
10/11/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PERIMETER SOFFIT AT [100];
Electrical Service Inspection Passed 10/19/2018 10/19/2018 at 10:20 AM 10/19/2018
Gas Piping Inspection - Commercial Failed 10/29/2018 at 7:30 AM 10/29/2018
Misc
Corrective Action Required
10/29/2018
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF NIPPLE TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Corrective Action Required
10/29/2018
INSTALL PROPERLY SIZED CLAMPS AT ALL ROOFTOP PIPING SUPPORT BLOCKS
Gas Service Inspection - Commercial Failed 10/26/2018 10/29/2018 at 8:05 AM 10/29/2018
Misc
Corrective Action Required
10/29/2018
SEE GAS PIPING
Misc
Corrective Action Required
10/29/2018
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Gas Piping Inspection - Commercial Passed 10/30/2018 at 8:10 AM 10/30/2018
Misc
Resolved
10/30/2018
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF NIPPLE TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Resolved
10/30/2018
INSTALL PROPERLY SIZED CLAMPS AT ALL ROOFTOP PIPING SUPPORT BLOCKS
Gas Service Inspection - Commercial Passed 10/30/2018 at 8:25 AM 10/30/2018
Misc
Resolved
10/30/2018
SEE GAS PIPING
Misc
Resolved
10/30/2018
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRY: WHERE TWO OR MORE SERVICES ARE GROUPED LOOSE-HANG ADDRESS-STAMPED MEDALLION ON LOAD SIDE PIPE.
Alarm Test Passed 10/31/2018 10/31/2018
Above Ceiling Inspection Partial 11/1/2018 11/1/2018 at 10:55 AM 11/01/2018
Misc
Resolved
11/01/2018
STELL FOR RTU WELDS INSPECTED ONLY. NO VISIBLE ISSUES
Misc
Resolved
11/01/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: PERIMETER SOFFIT AT [100];
Misc
Partial Correction
11/01/2018
OK TO COVER WHEN READY ACT FRAMING + ABOVE-CEILING SYSTEMS EXCEPT CRAFT AREA AND AT RECIRCULATION PUMP AT 107 NE CHECK MC ELECTRICAL CABLE FOR SUPPORT AT 6' MAXIMUM INTERVALS. NO LINE VOLTAGE OR LOW VOLTAGE ELECTRICAL CABLE TO BE SUPPORTED ON CEILING SUPPORT WIRES. SUPPORT FROM IDENTIFIED SLACK WIRES. SECURE RECIRCULATION PUMP TO STRUCTURE.
Above Ceiling Inspection Passed 11/2/2018 11/02/2018
Misc
Resolved
11/02/2018
OK TO COVER WHEN READY ACT FRAMING + ABOVE-CEILING SYSTEMS EXCEPT CRAFT AREA AND AT RECIRCULATION PUMP AT 107 NE CHECK MC ELECTRICAL CABLE FOR SUPPORT AT 6' MAXIMUM INTERVALS. NO LINE VOLTAGE OR LOW VOLTAGE ELECTRICAL CABLE TO BE SUPPORTED ON CEILING SUPPORT WIRES. SUPPORT FROM IDENTIFIED SLACK WIRES. SECURE RECIRCULATION PUMP TO STRUCTURE.
Occupancy Inspection - Codes Commercial Temporary C of O 11/2/2018 11/2/2018 at 2:50 PM 11/02/2018
Misc
Corrective Action Required
11/02/2018
RESOLVE FIRE DEPARTMENT ISSUES
Occupancy Inspection - Fire Temporary C of O 11/2/2018 11/02/2018
Occupancy Inspection - Codes Commercial Full C of O 11/5/2018 at 11:20 AM 11/05/2018
Misc
Resolved
11/05/2018
RESOLVE FIRE DEPARTMENT ISSUES
Occupancy Inspection - Fire Passed 11/5/2018 11/05/2018
Documents & Images
Date Uploaded File Type Document Name
07/20/2018 Letter Fire Building Plan Review
07/24/2018 Letter Codes P/R Corrections Document
07/25/2018 New Food Establishment Plan Review - Approved FTG 0001368
08/21/2018 FW Nothing Bundt Cakes permit
08/27/2018 Receipt Receipt for transaction: 2018-006000
08/27/2018 Letter Codes Building Permit
08/27/2018 Letter Codes Plan Review Conditions
09/05/2018 Letter Inspection Summary
09/06/2018 Letter Fire (Sprinkler) Plan Review
09/07/2018 Letter Inspection Summary
09/07/2018 Letter Inspection Summary
09/10/2018 Letter Inspection Summary
09/17/2018 Letter Inspection Summary
09/17/2018 Letter Fire (Alarm) Plan Review Notice
09/18/2018 Letter Inspection Summary
09/19/2018 Lees Summit Submittal Approval Letter
09/20/2018 Letter Inspection Summary
09/26/2018 Letter Inspection Summary
10/11/2018 Letter Inspection Summary
10/19/2018 Letter Inspection Summary
10/29/2018 Letter Inspection Summary
10/30/2018 Letter Inspection Summary
11/01/2018 Letter Inspection Summary
11/02/2018 Letter Inspection Summary
11/02/2018 Letter Codes Temporary Certificate of Occupancy
11/05/2018 Letter Field Certificate of Occupancy
12/06/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home