Summary
PRCOM20180269
Building Permit - Commercial
Voided
SUMMIT WOODS SPE LLC
CHANGE OF TENANT
TENANT FINISH FOR ICE CREAM SHOP NO MECHANICAL, ELECTRICAL, OR PLUMBING WORK (ALL EXISTING) 1/28/2019: NO INSPECTIONS REQUESTED TO DATE. PER TELECON W/ FRANK ESCOBAR OF RED, PERMIT VOIDED THIS DATE. WHEN NEW TENANT IS FOUND NEW PERMIT MUST BE OBTAINED FOR CHANGE OF OCCUPANCY AND FOR RENOVATION (IF ANY) AND SPACE MUST BE MADE CODE-COMPLIANT FOR CERTIFICATE OF OCCUPANCY TO BE ISSUED.
02/06/2018
02/26/2018
08/14/2018
01/28/2019
Locations
Contacts
SUMMIT WOODS SPE LLC, Address:1 E WASHINGTON ST STE 300  
SDC ENGINEERING, Address:5907 RAYTOWN TFWY, Phone:(816) 356-1445  
ABC CONSTRUCTION, Address:9216 NALL AVE, Phone:(913) 375-7063  
ABLE ELECTRIC, Address:P O BOX 34505, Phone:(816) 506-0496  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 02/27/2018 02/26/2018
Joe Frogge
License Tax Application
Resolved
02/21/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Resolved
02/26/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 2/21/18 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
02/20/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 2/21/18 - acknowledged in letter
Misc
Resolved
02/21/2018

2012 IMC 507.2.2 Type II hoods. Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system. (see code section for more specific requirements) Action required: Provide hood over new oven or provide verification that oven is listed as ventless and the hvac system is designed to compensate for the heat and humidity created. 2/21/18 - oven eliminated from project
Bldg - Toilet room wall finish 1210.2.2
Resolved
02/21/2018

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant materials at toilets and mop sink.
Plumb - Indirect/Special Waste - Where required 802.1
Resolved
02/21/2018

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: 3 compartment sink is to discharge indirectly.
Fire Plan Review Approved with Conditions 02/27/2018 02/21/2018
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/20/2018

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(Acknowledged in letter verified at inspection) The existing fire sprinkler system shall be current with all required service and maintenance. A current service tag shall be posted on the systems riser.
Misc
Resolved
02/26/2018

Emergency lighting ACTION REQUIRED:Plans did not show emergency lighting Install emergency lighting throughout and at the exteriorof both exits if not existing.
Misc
Resolved
02/21/2018

Health inspection ACTION REQUIRED:(information purposes) Business will need to pass a health dept. inspection before opening.
Licensed Contractors Approved 02/20/2018 02/21/2018
Joe Frogge
Licensed Contractors Approved 02/16/2018 02/15/2018
Joe Frogge
LC - General Contractor
Resolved
02/09/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
02/09/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 02/16/2018 02/14/2018
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/14/2018

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(Verified at inspection) The existing fire sprinkler system shall be current with all required service and maintenance. A current service tag shall be posted on the systems riser.
Misc
Corrective Action Required
02/14/2018

Emergency lighting ACTION REQUIRED:Plans did not show emergency lighting Install emergency lighting throughout and at exits if not existing.
Misc
Corrective Action Required
02/14/2018

Health inspection ACTION REQUIRED:(information purposes) Business will need to pass a health dept. inspection before opening.
Building Plan Review Rejected 02/16/2018 02/08/2018
Joe Frogge
License Tax Application
Corrective Action Required
02/08/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
02/26/2018

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
02/08/2018

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
02/08/2018

2012 IMC 507.2.2 Type II hoods. Type II hoods shall be installed above dishwashers and appliances that produce heat or moisture and do not produce grease or smoke as a result of the cooking process, except where the heat and moisture loads from such appliances are incorporated into the HVAC system design or into the design of a separate removal system. (see code section for more specific requirements) Action required: Provide hood over new oven or provide verification that oven is listed as ventless and the hvac system is designed to compensate for the heat and humidity created.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
02/08/2018

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant materials at toilets and mop sink.
Plumb - Indirect/Special Waste - Where required 802.1
Corrective Action Required
02/08/2018

2012 IPC 802.1 Where required. Food-handling equipment and clear-water waste shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. All health-care related fixtures, devices and equipment shall discharge to the drainage system through an indirect waste pipe by means of an air gap in accordance with this chapter and section 713.3. Fixtures not required by this section to be indirectly connected shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: 3 compartment sink is to discharge indirectly.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $61.28 $61.28 Paid 02/26/2018
8331507-Sewer Connection Fee $120.00 $120.00 Paid 02/26/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
02/14/2018 Letter Fire Building Plan Review
02/15/2018 Letter Codes P/R Corrections Document
02/21/2018 Letter Fire Building Plan Review
02/26/2018 Letter Fire Building Plan Review
02/26/2018 RE New Food Establishment Plan Review - Approved FTG 0001471
02/26/2018 Letter Codes Plan Review Conditions
02/26/2018 Receipt Receipt for transaction: 2018-000674
02/26/2018 Letter Codes Building Permit
11/02/2018 Letter Codes 140 Day Letter
11/05/2018 Letter Codes 140 Day Letter
12/17/2018 Letter Codes 180 Day Letter
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home