| Review Type |
Outcome |
Est. Completion Date |
Completed |
|
Alarm Plan Review
|
Released for Construction
|
|
08/16/2018
|
|
|
Joe Dir
|
|
|
Installation acceptance testing
Corrective Action Required
2012IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACTION REQUIRED: (information purposes)
Acceptance testing of the system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
|
|
|
|
|
Building Plan Review
|
Approved
|
02/08/2018
|
03/12/2018
|
|
|
Joe Frogge
|
|
|
Final Development Plan
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
2/2/18 - acknowleded in letter
|
|
|
Bldg - Accessibility - Drinking fountains 1109.5.1
2012 IBC 1109.5.1 – Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. (See code section for possible exceptions.)
Action required: Single bowl drinking fountains are allowed only if they satisfy requirements for ambulatory and non-ambulatory persons. To be field verified.
|
|
|
Misc
2012 IMC 501.2 Independent system required. Single or combined mechanical exhaust systems shall be independent of all other exhaust systems. (see code for specific requirements)
Action required: Restroom exhaust fans share a common duct therefore must be protected by backdraft dampers.
|
|
|
Misc
2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
(2) Kitchens
(3) Rooftops
(4) Outdoors
(5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink.
(6) Indoor wet locations
(7) Locker rooms with associated showering facilities
(8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used.
(refer to code for exceptions)
Action required: Modify drawings to show that all receptacles in unfinished areas are GFCI protected.
|
|
|
|
|
Final Development Plan Review
|
Approved
|
06/28/2018
|
03/12/2018
|
|
|
Joe Frogge
|
|
|
|
|
Licensed Contractors
|
Approved
|
02/01/2018
|
02/02/2018
|
|
|
Joe Frogge
|
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. (license for Pearce has expired)
|
|
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/08/2018
|
02/02/2018
|
|
|
Joe Dir
|
|
|
Address numbers required
Corrective Action Required
2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED:(verified at inspection)
Address shall be readable from the roadway.
|
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
ACTION REQUIRED:(verified at inspection)
Provide a minimum of two 2A-10BC fire extinguishers. Extinguishers to mounted close to an exit on a normal path of travel.
|
|
|
Misc
Codes
ACTION REQUIRED:
Provide a code summary for the project to include the 2012 Edition of the International Fire Code.
|
|
|
Misc
Corrective Action Required
Door operation
ACTION REQUIRED:(verified at inspection)
No keyed locks on the egress side of an exit.
1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
|
|
|
Misc
Duct detection
ACTION REQUIRED:
Duct detection is required due to the CFM of the AHU.
907.3.1 Duct smoke detectors. Smoke detectors installed
in ducts shall be listed for the air velocity, temperature and
humidity present in the duct. Duct smoke detectors shall
be connected to the building’s fire alarm control unit when
a fire alarm system is required by Section 907.2. Activation
of a duct smoke detector shall initiate a visible and
audible supervisory signal at a constantly attended location
and shall perform the intended fire safety function in
accordance with this code and the International Mechanical
Code. Duct smoke detectors shall not be used as a substitute
for required open area detection.
Exceptions:
1. The supervisory signal at a constantly attended
location is not required where duct smoke detectors
activate the building’s alarm notification
appliances.
2. In occupancies not required to be equipped with a
fire alarm system, actuation of a smoke detector
shall activate a visible and an audible signal in an
approved location. Smoke detector trouble conditions
shall activate a visible or audible signal in
an approved location and shall be identified as air
duct detector trouble.
|
|
|
|
|
Building Plan Review
|
Rejected
|
01/29/2018
|
01/23/2018
|
|
|
Joe Frogge
|
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
|
|
|
Bldg - Accessibility - Drinking fountains 1109.5.1
Corrective Action Required
2012 IBC 1109.5.1 – Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. (See code section for possible exceptions.)
Action required: Single bowl drinking fountains are allowed only if they satisfy requirements for ambulatory and non-ambulatory persons. To be field verified.
|
|
|
Misc
Corrective Action Required
2012 IMC 501.2 Independent system required. Single or combined mechanical exhaust systems shall be independent of all other exhaust systems. (see code for specific requirements)
Action required: Restroom exhaust fans share a common duct therefore must be protected by backdraft dampers.
|
|
|
Misc
Corrective Action Required
2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
(2) Kitchens
(3) Rooftops
(4) Outdoors
(5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink.
(6) Indoor wet locations
(7) Locker rooms with associated showering facilities
(8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used.
(refer to code for exceptions)
Action required: Modify drawings to show that all receptacles in unfinished areas are GFCI protected.
|
|
|
|
|
Licensed Contractors
|
Rejected
|
01/12/2018
|
01/23/2018
|
|
|
Joe Frogge
|
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. (license for Pearce has expired)
|
|
|
|
|
Fire Plan Review
|
Rejected
|
01/29/2018
|
01/17/2018
|
|
|
Joe Dir
|
|
|
Address numbers required
Corrective Action Required
2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED:(verified at inspection)
Address shall be readable from the roadway.
|
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
ACTION REQUIRED:(verified at inspection)
Provide a minimum of two 2A-10BC fire extinguishers. Extinguishers to mounted close to an exit on a normal path of travel.
|
|
|
Misc
Codes
ACTION REQUIRED:
Provide a code summary for the project to include the 2012 Edition of the International Fire Code.
|
|
|
Misc
Corrective Action Required
Door operation
ACTION REQUIRED:(verified at inspection)
No keyed locks on the egress side of an exit.
1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
|
|
|
Misc
Duct detection
ACTION REQUIRED:
Duct detection is required due to the CFM of the AHU.
907.3.1 Duct smoke detectors. Smoke detectors installed
in ducts shall be listed for the air velocity, temperature and
humidity present in the duct. Duct smoke detectors shall
be connected to the building’s fire alarm control unit when
a fire alarm system is required by Section 907.2. Activation
of a duct smoke detector shall initiate a visible and
audible supervisory signal at a constantly attended location
and shall perform the intended fire safety function in
accordance with this code and the International Mechanical
Code. Duct smoke detectors shall not be used as a substitute
for required open area detection.
Exceptions:
1. The supervisory signal at a constantly attended
location is not required where duct smoke detectors
activate the building’s alarm notification
appliances.
2. In occupancies not required to be equipped with a
fire alarm system, actuation of a smoke detector
shall activate a visible and an audible signal in an
approved location. Smoke detector trouble conditions
shall activate a visible or audible signal in
an approved location and shall be identified as air
duct detector trouble.
|
|
|
|