Summary
PRCOM20180098
Building Permit - Commercial
Certificate of Occupancy
ABUNDANT LIFE BAPTIST CHURCH OF LS MO
NEW COMMERCIAL
FOOD PANTRY BUILDING FOR ABUNDANT LIFE CHURCH
01/12/2018
03/21/2018
07/22/2018
11/27/2018
Locations
Contacts
ABUNDANT LIFE BAPTIST CHURCH OF LS MO, Address:414 SW PERSELS  
ELDECON INC, Address:120 SE 30TH ST, Phone:(660) 553-1121  
SHE DIGS IT LLC, Address:600 SE CENTRAL DR, Phone:(816) 295-1100  
METRO AIR CONDITIONING , Address:8151 MCCOY ST, Phone:(913) 888-3991  
PEARCE CONSTRUCTION MANAGEMENT LLC, Address:417 E 135TH ST , Phone:(816) 941-3000  
MANTEL TETER ARCHITECTS, INC, Address:929 WALNUT ST, SUITE 5104, Phone:(816) 931-5600  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/16/2018
Joe Dir
Installation acceptance testing
Corrective Action Required
08/16/2018

2012IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Building Plan Review Approved 02/08/2018 03/12/2018
Joe Frogge
Final Development Plan
Resolved
03/12/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 2/2/18 - acknowleded in letter
Bldg - Accessibility - Drinking fountains 1109.5.1
Resolved
02/02/2018

2012 IBC 1109.5.1 – Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. (See code section for possible exceptions.) Action required: Single bowl drinking fountains are allowed only if they satisfy requirements for ambulatory and non-ambulatory persons. To be field verified.
Misc
Resolved
02/02/2018

2012 IMC 501.2 Independent system required. Single or combined mechanical exhaust systems shall be independent of all other exhaust systems. (see code for specific requirements) Action required: Restroom exhaust fans share a common duct therefore must be protected by backdraft dampers.
Misc
Resolved
02/02/2018

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in unfinished areas are GFCI protected.
Final Development Plan Review Approved 06/28/2018 03/12/2018
Joe Frogge
Licensed Contractors Approved 02/01/2018 02/02/2018
Joe Frogge
LC - General Contractor
Resolved
02/02/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. (license for Pearce has expired)
Fire Plan Review Approved with Conditions 02/08/2018 02/02/2018
Joe Dir
Address numbers required
Corrective Action Required
02/01/2018

2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
02/01/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of two 2A-10BC fire extinguishers. Extinguishers to mounted close to an exit on a normal path of travel.
Misc
Resolved
02/02/2018

Codes ACTION REQUIRED: Provide a code summary for the project to include the 2012 Edition of the International Fire Code.
Misc
Corrective Action Required
02/01/2018

Door operation ACTION REQUIRED:(verified at inspection) No keyed locks on the egress side of an exit. 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Resolved
02/02/2018

Duct detection ACTION REQUIRED: Duct detection is required due to the CFM of the AHU. 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Building Plan Review Rejected 01/29/2018 01/23/2018
Joe Frogge
Final Development Plan
Corrective Action Required
01/23/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Bldg - Accessibility - Drinking fountains 1109.5.1
Corrective Action Required
01/23/2018

2012 IBC 1109.5.1 – Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. (See code section for possible exceptions.) Action required: Single bowl drinking fountains are allowed only if they satisfy requirements for ambulatory and non-ambulatory persons. To be field verified.
Misc
Corrective Action Required
01/23/2018

2012 IMC 501.2 Independent system required. Single or combined mechanical exhaust systems shall be independent of all other exhaust systems. (see code for specific requirements) Action required: Restroom exhaust fans share a common duct therefore must be protected by backdraft dampers.
Misc
Corrective Action Required
01/23/2018

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in unfinished areas are GFCI protected.
Licensed Contractors Rejected 01/12/2018 01/23/2018
Joe Frogge
LC - General Contractor
Corrective Action Required
01/23/2018

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. (license for Pearce has expired)
Fire Plan Review Rejected 01/29/2018 01/17/2018
Joe Dir
Address numbers required
Corrective Action Required
01/17/2018

2012IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
01/17/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Provide a minimum of two 2A-10BC fire extinguishers. Extinguishers to mounted close to an exit on a normal path of travel.
Misc
Resolved
02/02/2018

Codes ACTION REQUIRED: Provide a code summary for the project to include the 2012 Edition of the International Fire Code.
Misc
Corrective Action Required
01/17/2018

Door operation ACTION REQUIRED:(verified at inspection) No keyed locks on the egress side of an exit. 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Misc
Resolved
02/02/2018

Duct detection ACTION REQUIRED: Duct detection is required due to the CFM of the AHU. 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $2,256.25 $2,256.25 Paid 03/21/2018
Water Tap Fee $8,915.00 $8,915.00 Paid 03/21/2018
Water Meter Fee $657.68 $657.68 Paid 03/21/2018
8331507-Sewer Connection Fee $210.00 $210.00 Paid 03/21/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 5/8/2018 5/8/2018 05/08/2018
Misc
Corrective Action Required
05/08/2018
west side of footing- install ufer ground and call for inspection when ready.
Footing Inspection - Commercial Passed 5/9/2018 5/9/2018 at 12:00 PM 05/09/2018
Misc
Resolved
05/09/2018
west side of footing- install ufer ground and call for inspection when ready.
Underslab Plumbing Inspection - Commercial Partial 5/11/2018 05/11/2018
Misc
Corrective Action Required
05/11/2018
Partial approval- DWV inspected ok to cover pending waterlines and electrical when ready
Underslab Plumbing Inspection - Commercial Passed 5/23/2018 05/23/2018
Misc
Corrective Action Required
05/11/2018
Partial approval- DWV inspected ok to cover pending waterlines and electrical when ready
All Rough Inspection - Commercial Passed 9/4/2018 07/27/2018
Electrical Service Inspection Passed 8/8/2018 8/8/2018 at 10:00 AM 08/08/2018
Gas Piping Inspection - Commercial Passed 8/27/2018 8/28/2018 at 8:00 AM 08/28/2018
Gas Service Inspection - Commercial Passed 8/29/2018 8/29/2018 at 1:00 PM 08/29/2018
Above Ceiling Inspection Passed 9/4/2018 9/4/2018 at 11:20 AM 09/04/2018
Alarm Test Partial 9/14/2018 09/14/2018
Alarm Test Failed 9/20/2018 09/20/2018
Occupancy Inspection - Fire Failed 9/20/2018 09/20/2018
Occupancy Inspection - Codes Commercial Failed 9/20/2018 9/20/2018 09/20/2018
Misc
Corrective Action Required
09/20/2018
Post address - pending other departments for TCO Fire - alarm and address ENG inspectors- Planning- water-
Occupancy Inspection - Engineering Temporary C of O 9/20/2018 09/20/2018
Occupancy Inspection - Planning Temporary C of O 9/20/2018 09/20/2018
Corrective Action Required
09/20/2018
Per site superintended the location of the required landscaping is in conflict with the fire service line and needs to be changed. An updated landscaping plan will need to be submitted with the proposed new location of the vegetation to be installed.
Corrective Action Required
09/20/2018
Landscaping has yet to be installed.
Alarm Test Passed 9/26/2018 09/26/2018
Occupancy Inspection - Fire Passed 9/26/2018 09/26/2018
Occupancy Inspection - Codes Commercial Temporary C of O 9/26/2018 9/26/2018 09/26/2018
Misc
Corrective Action Required
09/20/2018
Ok for TCO
Occupancy Inspection - Codes Commercial Temporary C of O 11/02/2018
Misc
Corrective Action Required
09/26/2018
Ok for TCO request for 30 extension
Occupancy Inspection - Codes Commercial Failed 11/9/2018 11/09/2018
Misc
Corrective Action Required
11/02/2018
Ok for TCO request for 30 extension
Misc
Corrective Action Required
11/09/2018
no one present at final? no communication from other departments, please advise when ready.
Occupancy Inspection - Planning Passed 11/15/2018
Occupancy Inspection - Engineering Passed 11/21/2018
Occupancy Inspection - Codes Commercial Full C of O 11/27/2018 11/27/2018 at 9:45 AM 11/27/2018
Misc
Resolved
11/27/2018
Ok for TCO request for 30 extension
Misc
Resolved
11/27/2018
no one present at final? no communication from other departments, please advise when ready.
Documents & Images
Date Uploaded File Type Document Name
01/17/2018 address change
01/17/2018 Letter Fire Building Plan Review
01/23/2018 Letter Codes P/R Corrections Document
01/30/2018 New Food Establishment Plan Review - Approved FTG 0001166
02/02/2018 Letter Fire Building Plan Review
03/12/2018 Letter Codes Plan Review Conditions
03/13/2018 site contact
03/21/2018 Receipt Receipt for transaction: 2018-001039
03/21/2018 Letter Codes Building Permit
05/08/2018 Letter Inspection Summary
05/09/2018 Letter Inspection Summary
05/11/2018 Letter Inspection Summary
05/23/2018 Letter Inspection Summary
07/27/2018 Letter Inspection Summary
08/08/2018 Letter Inspection Summary
08/16/2018 Letter Fire (Alarm) Plan Review Notice
08/28/2018 Letter Inspection Summary
08/29/2018 Letter Inspection Summary
09/20/2018 Letter Inspection Summary
09/26/2018 Letter Codes Temporary Certificate of Occupancy
11/02/2018 Letter Codes Temporary Certificate of Occupancy
11/09/2018 Letter Inspection Summary
11/27/2018 Letter Field Certificate of Occupancy
12/06/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home