Summary
PRCOM20174120
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
CHANGE OF USE FROM CHURCH TO MUSIC STORE WITH RETAIL, PERFORMANCE VENUE, AND CLASSROOMS - NO CONSTRUCTION **drawing is in plan review file
12/28/2017
01/03/2018
01/29/2018
Locations
Contacts
SHINING LIGHT MUSIC LLC, Address:616 SW 3RD ST, Phone:(816) 347-0099  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 01/10/2018 01/02/2018
Joe Dir
Address numbers required
Corrective Action Required
01/02/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(Verified at inspection) Post the numeric address of 611 on the exterior of all doors leading into the business. Address shall be readable from the roadway.
Portable fire extinguishers - general
Corrective Action Required
01/02/2018

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(veriifed at inspection) If not existing Provide one 2A-10 BC fire extinguisher for every 3,000 sq ft of useable area of the business. Mount the fire extinguishers close to exits with a maximum travel distance of 75' to an extingusiher.
Building Plan Review Approved 01/10/2018 12/28/2017
Joe Frogge
Licensed Contractors Approved 01/10/2018 12/28/2017
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.00 $30.00 Paid 01/03/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Failed 1/26/2018 01/26/2018
Occupancy Inspection - Codes Commercial Failed 1/26/2018 1/26/2018 at 1:15 PM 01/26/2018
Misc
Corrective Action Required
01/26/2018
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
01/26/2018
BALCONY GUARD NOT COMPLIANT WITH COMMERCIAL CODE
Misc
Corrective Action Required
01/26/2018
CURRENT, LEGIBLE, ACCURATE PANEL SCHEDULES REQUIRED AT ELECTRICAL PANELS
Misc
Corrective Action Required
01/26/2018
ANTI-TIP DEVICE REQUIRED AT BREAK ROOM RANGE
Misc
Corrective Action Required
01/26/2018
ELECTRICAL RECEPTACLES: - GFCI PROTECTION REQUIRED NEAR BREAK ROOM SINK - APPARENT OPEN GROUND AT MW RECEPT - CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Occupancy Inspection - Codes Commercial Not Ready 1/29/2018 at 9:10 AM 01/29/2018
Misc
Corrective Action Required
01/26/2018
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
01/26/2018
BALCONY GUARD NOT COMPLIANT WITH COMMERCIAL CODE
Misc
Corrective Action Required
01/26/2018
CURRENT, LEGIBLE, ACCURATE PANEL SCHEDULES REQUIRED AT ELECTRICAL PANELS
Misc
Corrective Action Required
01/26/2018
ANTI-TIP DEVICE REQUIRED AT BREAK ROOM RANGE
Misc
Corrective Action Required
01/26/2018
ELECTRICAL RECEPTACLES: - GFCI PROTECTION REQUIRED NEAR BREAK ROOM SINK - APPARENT OPEN GROUND AT MW RECEPT - CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Occupancy Inspection - Codes Commercial Partial 1/29/2018 at 1:40 PM 01/29/2018
Misc
Corrective Action Required
01/29/2018
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
01/29/2018
BALCONY GUARD NOT COMPLIANT WITH COMMERCIAL CODE
Misc
Corrective Action Required
01/29/2018
CURRENT, LEGIBLE, ACCURATE PANEL SCHEDULES REQUIRED AT ELECTRICAL PANELS
Misc
Corrective Action Required
01/29/2018
ANTI-TIP DEVICE REQUIRED AT BREAK ROOM RANGE
Misc
Corrective Action Required
01/29/2018
ELECTRICAL RECEPTACLES: - GFCI PROTECTION REQUIRED NEAR BREAK ROOM SINK - APPARENT OPEN GROUND AT MW RECEPT - CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Occupancy Inspection - Fire Passed 1/29/2018 01/29/2018
Occupancy Inspection - Codes Commercial Full C of O 1/29/2018 at 3:55 PM 01/29/2018
Misc
Resolved
01/29/2018
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Resolved
01/29/2018
Misc
Resolved
01/29/2018
CURRENT, LEGIBLE, ACCURATE PANEL SCHEDULES REQUIRED AT ELECTRICAL PANELS BALCONY GUARD NOT COMPLIANT WITH COMMERCIAL CODE
Misc
Resolved
01/29/2018
ANTI-TIP DEVICE REQUIRED AT BREAK ROOM RANGE
Misc
Resolved
01/29/2018
ELECTRICAL RECEPTACLES: - GFCI PROTECTION REQUIRED NEAR BREAK ROOM SINK - APPARENT OPEN GROUND AT MW RECEPT - CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX -- NONE "SOFT" OR LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Documents & Images
Date Uploaded File Type Document Name
01/02/2018 Letter Fire Building Plan Review
01/03/2018 Letter Codes Plan Review Conditions
01/03/2018 Receipt Receipt for transaction: 2018-000027
01/03/2018 Letter Codes Building Permit
01/26/2018 Letter Inspection Summary
01/29/2018 Letter Field Certificate of Occupancy
01/30/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home