Permit Application Status

PRCOM20173935


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20173935
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
CHANGE OF TENANT
TENANT FINISH FOR NEW GYM
12/06/2017
01/16/2018
07/10/2018
04/11/2018
Locations
Contacts
LUKE DRAILY CONSTRUCTION INC, Address:75 NW BUSINESS PARK LANE, Phone:(816) 459-8531  
OVERLAND PARK MECHANICAL CO LLC, Address:16088 FOSTER, Phone:(913) 814-8200  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
PRODIGY PLUMBING & MECHANICAL INC, Address:8402 WESTRIDGE RD, Phone:(816) 984-9292  
D. ROSAS DESIGN GROUP, Address:5958 E CORRINE DRIVE STE 102, Phone:(480) 719-0790  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 02/13/2018
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/13/2018

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(veriifed at inspection) The existing systems riser shall be current with all required service and maintenance. A current service tag shall be posted on the systems riser.
Alarm Plan Review Released for Construction 02/13/2018
Joe Dir
Installation acceptance testing
Corrective Action Required
02/13/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing.(816)969-1300.
Fire Plan Review Approved with Conditions 01/22/2018 01/16/2018
Joe Dir
Posting of occupant load
Corrective Action Required
01/16/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) Post the occupant load of 47 near the main entrance.
Address numbers required
Corrective Action Required
01/16/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address (suite designation) shall be readable from the corridor and roadway
Installation acceptance testing
Corrective Action Required
01/16/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection. contact the fire department to schedule testing. 816-969-1300.
Misc
Corrective Action Required
01/16/2018

Door operations ACTION REQUIRED: (veriifed at inspection) No keyed locks on the egress side on an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Building Plan Review Approved 01/22/2018 01/12/2018
Joe Frogge
Misc
Resolved
01/12/2018

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Due to occupant load in Studio, provide an additional exit light at door into front Lobby. 1/5/17 - update electrical drawings that are sealed and signed by the electrical engineer to reflect changes.
Licensed Contractors Approved 01/12/2018 01/12/2018
Joe Frogge
Fire Plan Review Approved with Conditions 01/22/2018 01/12/2018
Joe Frogge
Posting of occupant load
Corrective Action Required
01/12/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) Post the occupant load of 47 near the main entrance.
Address numbers required
Corrective Action Required
01/12/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address (suite designation) shall be readable from the corridor and roadway
Installation acceptance testing
Corrective Action Required
01/12/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection. contact the fire department to schedule testing. 816-969-1300.
Misc
Corrective Action Required
01/12/2018

Door operations ACTION REQUIRED: (veriifed at inspection) No keyed locks on the egress side on an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Fire Plan Review Approved with Conditions 01/12/2018 01/11/2018
Joe Frogge
Posting of occupant load
Corrective Action Required
01/05/2018

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) Post the occupant load of 47 near the main entrance.
Construction documents for fire alarm systems
Resolved
01/08/2018

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system shop drawings submitted to the fire department for approval.
Address numbers required
Corrective Action Required
01/05/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address (suite designation) shall be readable from the corridor and roadway
Construction documents - Fire protection systems
Resolved
01/08/2018

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system shop drawings submitted to the fire department for apprioval.
Installation acceptance testing
Corrective Action Required
01/05/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection. contact the fire department to schedule testing. 816-969-1300.
Misc
Corrective Action Required
01/05/2018

Door operations ACTION REQUIRED: (veriifed at inspection) No keyed locks on the egress side on an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Building Plan Review Rejected 01/12/2018 01/05/2018
Joe Frogge
Code analysis required
Resolved
01/05/2018

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise code analysis to reflect corrected information as follows - Construction Type = IIB, Occupancy Group = A3, & Accessibility Code = 2009 ICC/ANSI A117.1
Misc
Resolved
01/05/2018

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer's report to verify that existing roof structure will support additional load at new roof top HVAC.
Bldg - Panic and fire exit hardware 1008.1.10
Resolved
01/05/2018

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Exit doors to comply. To be field verified.
Misc
Corrective Action Required
01/05/2018

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Due to occupant load in Studio, provide an additional exit light at door into front Lobby. 1/5/17 - update electrical drawings that are sealed and signed by the electrical engineer to reflect changes.
Licensed Contractors Approved 01/05/2018 01/05/2018
Joe Frogge
LC - MEP Subs
Resolved
01/05/2018

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Plumbing contractor.
Building Plan Review Rejected 12/18/2017 12/08/2017
Joe Frogge
Code analysis required
Corrective Action Required
12/08/2017

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Revise code analysis to reflect corrected information as follows - Construction Type = IIB, Occupancy Group = A3, & Accessibility Code = 2009 ICC/ANSI A117.1
Misc
Corrective Action Required
12/08/2017

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer's report to verify that existing roof structure will support additional load at new roof top HVAC.
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
12/08/2017

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Exit doors to comply. To be field verified.
Misc
Corrective Action Required
12/08/2017

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Due to occupant load in Studio, provide an additional exit light at door into front Lobby.
Licensed Contractors Rejected 12/06/2017 12/08/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
12/08/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Plumbing contractor.
Fire Plan Review Approved with Conditions 12/18/2017 12/07/2017
Joe Dir
Posting of occupant load
Corrective Action Required
12/07/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) Post the occupant load of 47 near the main entrance.
Construction documents for fire alarm systems
Corrective Action Required
12/07/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system shop drawings submitted to the fire department for approval.
Address numbers required
Corrective Action Required
12/07/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Address (suite designation) shall be readable from the corridor and roadway
Construction documents - Fire protection systems
Corrective Action Required
12/07/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system shop drawings submitted to the fire department for apprioval.
Installation acceptance testing
Corrective Action Required
12/07/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection. contact the fire department to schedule testing. 816-969-1300.
Misc
Corrective Action Required
12/07/2017

Door operations ACTION REQUIRED: (veriifed at inspection) No keyed locks on the egress side on an exit. [B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,593.15 $1,593.15 Paid 01/16/2018
8331507-Sewer Connection Fee $210.00 $210.00 Paid 01/16/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 2/5/2018 at 8:30 AM 02/05/2018
Misc
Corrective Action Required
02/05/2018
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Underslab Plumbing Inspection - Commercial Partial 2/6/2018 2/6/2018 at 8:25 AM 02/06/2018
Misc
Partial Correction
02/06/2018
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT CONNECTION TO BUILDING DRAIN LINE WHICH IS 3" VS 4" SHOWN ON DRAWINGS. HAVE A/E NOTIFY BUILDING INSPECTOR IF BUILDING DRAIN SIZE IS ADEQUATE FOR TENANT'S CALCULATED LOADS. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Miscellaneous Inspection Partial 2/8/2018 at 10:00 AM 02/08/2018
Misc
Partial Correction
02/08/2018
ELEMENTS OF LIGHTED SIGN FOUND TO BE UL-LABELED, BUT MANUFACTURER'S LABEL NOT FOUND. WILL ALLOW THIS ONLY TO BE FIELD-LABELED.
Underslab Plumbing Inspection - Commercial Passed 2/8/2018 2/8/2018 at 10:15 AM 02/08/2018
Misc
Resolved
02/08/2018
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING EXCEPT CONNECTION TO BUILDING DRAIN LINE WHICH IS 3" VS 4" SHOWN ON DRAWINGS. HAVE A/E NOTIFY BUILDING INSPECTOR IF BUILDING DRAIN SIZE IS ADEQUATE FOR TENANT'S CALCULATED LOADS. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Miscellaneous Inspection Partial 2/8/2018 at 1:15 PM 02/08/2018
Misc
Partial Correction
02/08/2018
ELEMENTS OF LIGHTED SIGN FOUND TO BE UL-LABELED, BUT MANUFACTURER'S LABEL NOT FOUND. WILL ALLOW THIS ONLY TO BE FIELD-LABELED.
Rough Electrical Inspection - Commercial Partial 2/16/2018 at 11:25 AM 02/16/2018
Misc
Partial Correction
02/16/2018
NO ISSUES FOUND ON RECONFIGURATION OF ELECTRICAL SERVICE
In-wall Inspection Partial 2/16/2018 at 10:15 AM 02/16/2018
Misc
Partial Correction
02/16/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS EXCEPT WHERE HAT CHANNEL HAS YET TO BE INSTALLED PRIOR TO APPLICATION OF GWB
In-wall Inspection Partial 2/20/2018 2/20/2018 at 9:35 AM 02/20/2018
Misc
Partial Correction
02/16/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS INCLUDING STUDIO SOUTH WALL WHERE HAT CHANNEL IS BEING INSTALLED PRIOR TO APPLICATION OF GWB
Above Ceiling Inspection Partial 2/20/2018 2/20/2018 at 9:50 AM 02/20/2018
Misc
Partial Correction
02/20/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: [MEN'S RR; WOMEN'S RR;
Above Ceiling Inspection Partial 2/26/2018 2/26/2018 at 11:10 AM 02/26/2018
Misc
Partial Correction
02/20/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: MEN'S RR; WOMEN'S RR; [LOBBY; OFFICE; SHOWER
Miscellaneous Inspection Partial 3/12/2018 at 9:45 AM 03/12/2018
Misc
Partial Correction
02/08/2018
ELEMENTS OF LIGHTED SIGN FOUND TO BE UL-LABELED, BUT MANUFACTURER'S LABEL NOT FOUND. WILL ALLOW THIS ONLY TO BE FIELD-LABELED.
Miscellaneous Inspection Partial 3/16/2018 at 10:25 AM 03/16/2018
Misc
Partial Correction
03/12/2018
ELEMENTS OF LIGHTED SIGN FOUND TO BE UL-LABELED, BUT MANUFACTURER'S LABEL NOT FOUND. WILL ALLOW THIS ONLY TO BE FIELD-LABELED.
In-wall Inspection Not Ready 3/21/2018 3/21/2018 at 7:30 AM 03/21/2018
Misc
Partial Correction
02/20/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS INCLUDING STUDIO SOUTH WALL WHERE HAT CHANNEL IS BEING INSTALLED PRIOR TO APPLICATION OF GWB
Above Ceiling Inspection Not Ready 3/21/2018 3/21/2018 03/21/2018
Misc
Partial Correction
02/26/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: MEN'S RR; WOMEN'S RR; [LOBBY; OFFICE; SHOWER
In-wall Inspection Partial 3/22/2018 at 7:50 AM 03/22/2018
Misc
Partial Correction
03/21/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS INCLUDING STUDIO SOUTH WALL WHERE HAT CHANNEL IS BEING INSTALLED PRIOR TO APPLICATION OF GWB; [LOBBY WALL SOUTH;
Above Ceiling Inspection Partial 3/22/2018 at 8:05 AM 03/22/2018
Misc
Partial Correction
03/21/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: MEN'S RR; WOMEN'S RR; LOBBY; OFFICE; SHOWER
Miscellaneous Correction
Partial Correction
03/22/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: FRONT 2/3, BUT BORDERS ONLY AT REAR 1/3 PENDING VERIFICATION ALL ABANDONED EXISTING HVAC AND PLUMBING VTR'S ARE SEALED;
Above Ceiling Inspection Passed 3/23/2018 3/23/2018 at 7:50 AM 03/23/2018
Misc
Resolved
03/23/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: MEN'S RR; WOMEN'S RR; LOBBY; OFFICE; SHOWER
Miscellaneous Correction
Resolved
03/23/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: FRONT 2/3, BUT BORDERS ONLY AT REAR 1/3 PENDING VERIFICATION ALL ABANDONED EXISTING HVAC AND PLUMBING VTR'S ARE SEALED;
Gas Piping Inspection - Commercial Failed 3/27/2018 at 1:10 PM 03/27/2018
Miscellaneous Correction
Corrective Action Required
03/27/2018
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING. SUPPORT SUPPORT WITHIN 18" OF ENDS, 90'S, TEES, AND JOINTS.
Miscellaneous Correction
Corrective Action Required
03/27/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. PAINT 100% OF STEEL PIPE INCLUDING AT SUPPORTS. SEE GAS PIPING AT METER AND ROOFTOP.
Miscellaneous Correction
Corrective Action Required
03/27/2018
PRESSURE TEST WILL BE WITNESSED AFTER PIPE INSTALLATION IS APPROVED.
Gas Piping Inspection - Commercial Failed 3/30/2018 at 8:40 AM 03/30/2018
Miscellaneous Correction
Resolved
03/30/2018
IFGC 407.2 & 415; IRC G2423 SUPPORT OF HORIZONTAL RUNS OF RIGID STEEL PIPING: SPACING OF BLOCKS/HANGERS -- : 1/2" PIPE -- 6' MAX SPACING; 3/4" OR 1" PIPE -- 8' MAX SPACING; 1-1/4" OR LARGER PIPE -- 10' MAX SPACING. SUPPORT SUPPORT WITHIN 18" OF ENDS, 90'S, TEES, AND JOINTS.
Miscellaneous Correction
Corrective Action Required
03/27/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. PAINT 100% OF STEEL PIPE INCLUDING AT SUPPORTS. SEE GAS PIPING AT METER AND ROOFTOP. STEEL PIPE NOT PAINTED 100%. SEE BOTTOM OF PIPE AND AT SUPPORT CLAMPS.
Miscellaneous Correction
Corrective Action Required
03/27/2018
PRESSURE TEST WILL BE WITNESSED AFTER PIPE INSTALLATION IS APPROVED.
Gas Service Inspection - Commercial Passed 4/2/2018 4/2/2018 at 7:40 AM 04/02/2018
Gas Piping Inspection - Commercial Passed 4/2/2018 4/2/2018 at 7:20 AM 04/02/2018
Miscellaneous Correction
Resolved
04/02/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. PAINT 100% OF STEEL PIPE INCLUDING AT SUPPORTS. SEE GAS PIPING AT METER AND ROOFTOP. STEEL PIPE NOT PAINTED 100%. SEE BOTTOM OF PIPE AND AT SUPPORT CLAMPS.
Miscellaneous Correction
Resolved
04/02/2018
PRESSURE TEST WILL BE WITNESSED AFTER PIPE INSTALLATION IS APPROVED.
In-wall Inspection Passed 3/22/2018 04/02/2018
Misc
Resolved
04/02/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS INCLUDING STUDIO SOUTH WALL WHERE HAT CHANNEL IS BEING INSTALLED PRIOR TO APPLICATION OF GWB; [LOBBY WALL SOUTH;
Miscellaneous Inspection Passed 4/2/2018 04/02/2018
Misc
Partial Correction
03/16/2018
ELEMENTS OF LIGHTED SIGN FOUND TO BE UL-LABELED, BUT MANUFACTURER'S LABEL NOT FOUND. WILL ALLOW THIS ONLY TO BE FIELD-LABELED.
Rough Electrical Inspection - Commercial Passed 2/16/2018 04/06/2018
Misc
Resolved
04/06/2018
NO ISSUES FOUND ON RECONFIGURATION OF ELECTRICAL SERVICE
Miscellaneous Inspection Passed 4/6/2018 at 10:05 AM 04/06/2018
Alarm Test Passed 4/10/2018 04/10/2018
Occupancy Inspection - Fire Passed 4/10/2018 04/10/2018
Occupancy Inspection - Codes Commercial Failed 4/11/2018 4/11/2018 at 8:35 AM 04/11/2018
Miscellaneous Correction
Resolved
04/06/2018
ADDRESS LABEL GAS SERVICE
Miscellaneous Correction
Resolved
04/06/2018
ELEMENTS OF LIGHTED SIGN FOUND TO BE UL-LABELED, BUT MANUFACTURER'S LABEL NOT FOUND. WILL ALLOW THIS ONLY TO BE FIELD-LABELED.
Miscellaneous Correction
Corrective Action Required
04/06/2018
ALL DEBRIS AND UNUSED MATERIAL TO BE REMOVED FROM ROOFTOP. ALL ROOFTOP MECHANICAL EQUIPMENT TO BE LABELED AND DESIGNATIONS REFLECTED AT ELECTRICAL PANEL.
Occupancy Inspection - Codes Commercial Full C of O 4/11/2018 at 2:20 PM 04/11/2018
Miscellaneous Correction
Resolved
04/11/2018
ALL DEBRIS AND UNUSED MATERIAL TO BE REMOVED FROM ROOFTOP. ALL ROOFTOP MECHANICAL EQUIPMENT TO BE LABELED AND DESIGNATIONS REFLECTED AT ELECTRICAL PANEL.
Documents & Images
Date Uploaded File Type Document Name
12/07/2017 Letter Fire Building Plan Review
12/08/2017 Letter Codes P/R Corrections Document
01/08/2018 Letter Fire Building Plan Review
01/11/2018 Letter Codes P/R Corrections Document
01/12/2018 Letter Codes Plan Review Conditions
01/16/2018 Receipt Receipt for transaction: 2018-000141
01/16/2018 Letter Codes Building Permit
01/16/2018 Letter Fire Building Plan Review
02/05/2018 Letter Inspection Summary
02/06/2018 Letter Inspection Summary
02/08/2018 Letter Inspection Summary
02/13/2018 Letter Fire (Alarm) Plan Review Notice
02/13/2018 Letter Fire (Sprinkler) Plan Review
02/16/2018 Letter Inspection Summary
02/20/2018 Letter Inspection Summary
02/26/2018 Letter Inspection Summary
03/22/2018 Letter Inspection Summary
03/23/2018 Letter Inspection Summary
03/27/2018 Letter Inspection Summary
03/30/2018 Letter Inspection Summary
04/02/2018 Letter Inspection Summary
04/06/2018 Letter Inspection Summary
04/11/2018 Letter Inspection Summary
04/11/2018 Letter Field Certificate of Occupancy
04/12/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home