Permit Application Status

PRCOM20173638


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20173638
Building Permit - Commercial
Final Completion
LEES SUMMIT CLINIC BLDG CO
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO ADD EXAM AND RESTROOMS
11/06/2017
11/30/2017
05/27/2018
01/02/2018
Locations
Contacts
TAILOR MADE EXTERIORS LLC, Address:Attn: Rick and Rachel Mullin, Phone:(816) 347-8328  
CLIMATE RESTORATION SERVICES LLC, Address:PO BOX 574, Phone:(816) 929-1312  
JJJ'S ELECTRICAL INC, Address:P O BOX 1811, Phone:(816) 853-6625  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
ROY BROWN ARCHITECT, Address:24 OAK HILL CLUSTER, Phone:(816) 228-1111  
LEES SUMMIT CLINIC BLDG CO, Address:615 SW 3RD ST  
BRUCE BEST, Phone:(816) 525-8918  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 12/05/2017 11/30/2017
Joe Dir
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/28/2017

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. ACTION REQUIRED:(verified at inspection) Fire extinguishers shall be mounted according to the above conditions. Close to an exit on normal paths of travel.
Misc
Resolved
11/30/2017

Exit Door swing ACTION REQUIRED: Revised plan sheet A-5 shows glass store fronts and doors to be replaced with the doors swinging in the wrong direction. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Misc
Resolved
11/30/2017

Emergency lighting ACTION REQUIRED:(verified at inspection) Add emergency lighting to the interior stairway leading to basement. Add emergency lighting to the west stairway/ramp leading to the basement. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604.
Building Plan Review Approved with Conditions 12/05/2017 11/28/2017
Joe Frogge
License Tax Application
Corrective Action Required
11/28/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 11/20/17 - acknowledged in letter
Project cost
Corrective Action Required
11/28/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 11/20/17 - acknowledged in letter
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
11/28/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify design to provide minimum 18" at latch side of door #7 out of northern restroom as well as door out of "optional" reception area restroom. 11/20/17 - Door #7 modified, but optional restroom door is still non-compliant 11/28/17 - restroom not to be constructed
Plan Submittal 2012 Codes
Resolved
11/28/2017

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise sheets TF-1, A-2, and A-4 to depict correct accessibility code which is 2009 ICC/ANSI A117.1. 11/20/17 - Sheet TF-1 updated, but A-2 and A-4 still reference 2003 code.
Bldg - Toilet room wall finish 1210.2.2
Resolved
11/28/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant restroom finish materials. (if paint is used it must be epoxy based) 11/20/17 - finish schedule updated to reference finishes at sinks. In this case it is the walls surrounding the water closets that need resolved.
Misc
Resolved
11/28/2017

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1.The grounding terminals of all receptacles. 2.Metal Boxes and enclosures containing receptacles. 3.All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2)Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 11/20/17 - acknowledged in letter but sheet ME-1 was not included in the resubmittal package.
Licensed Contractors Approved 11/28/2017 11/28/2017
Joe Frogge
Fire Plan Review Rejected 11/28/2017 11/21/2017
Joe Dir
Address numbers required
Resolved
11/21/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) numeric address of 615 shall be readable from the roadway (3rd street)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/17/2017

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. ACTION REQUIRED:(verified at inspection) Fire extinguishers shall be mounted according to the above conditions. Close to an exit on normal paths of travel.
Misc
Corrective Action Required
11/21/2017

Exit Door swing ACTION REQUIRED: Revised plan sheet A-5 shows glass store fronts and doors to be replaced with the doors swinging in the wrong direction. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Misc
Corrective Action Required
11/17/2017

Emergency lighting ACTION REQUIRED:(verified at inspection) Add emergency lighting to the interior stairway leading to basement. Add emergency lighting to the west stairway/ramp leading to the basement. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604.
Misc
Resolved
11/21/2017

applicable codes: ACTION REQUIRED: Applicable codes should include the 2012 IFC.
Building Plan Review Rejected 11/28/2017 11/20/2017
Joe Frogge
License Tax Application
Corrective Action Required
11/17/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 11/20/17 - acknowledged in letter
Project cost
Corrective Action Required
11/17/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes. 11/20/17 - acknowledged in letter
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
11/17/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify design to provide minimum 18" at latch side of door #7 out of northern restroom as well as door out of "optional" reception area restroom. 11/20/17 - Door #7 modified, but optional restroom door is still non-compliant
Plan Submittal 2012 Codes
Corrective Action Required
11/17/2017

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise sheets TF-1, A-2, and A-4 to depict correct accessibility code which is 2009 ICC/ANSI A117.1. 11/20/17 - Sheet TF-1 updated, but A-2 and A-4 still reference 2003 code.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
11/17/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant restroom finish materials. (if paint is used it must be epoxy based) 11/20/17 - finish schedule updated to reference finishes at sinks. In this case it is the walls surrounding the water closets that need resolved.
Bldg - Size of doors 1008.1.1
Resolved
11/20/2017

2012 IBC 1008.1.1 – Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in a Group i-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of door openings shall not be less than 80 inches. See Code for possible exceptions. Action required: Modify floor plan and door schedule to apply. (ref: door #5)
Misc
Corrective Action Required
11/17/2017

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1.The grounding terminals of all receptacles. 2.Metal Boxes and enclosures containing receptacles. 3.All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2)Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system. 11/20/17 - acknowledged in letter but sheet ME-1 was not included in the resubmittal package.
Licensed Contractors Approved 11/17/2017 11/20/2017
Joe Frogge
LC - General Contractor
Resolved
11/20/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
11/20/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 11/16/2017 11/08/2017
Joe Dir
Address numbers required
Corrective Action Required
11/08/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) numeric address of 615 shall be readable from the roadway (3rd street)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/08/2017

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. ACTION REQUIRED:(verified at inspection) Fire extinguishers shall be mounted according to the above conditions. Close to an exit on normal paths of travel.
Misc
Corrective Action Required
11/08/2017

Exit Door swing ACTION REQUIRED: Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Misc
Corrective Action Required
11/08/2017

Emergency lighting ACTION REQUIRED: Add emergency lighting to the interior stairway leading to basement. Add emergency lighting to the west stairway/ramp leading to the basement. [B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 604.
Misc
Corrective Action Required
11/08/2017

applicable codes: ACTION REQUIRED: Applicable codes should include the 2012 IFC.
Building Plan Review Rejected 11/16/2017 11/08/2017
Joe Frogge
License Tax Application
Corrective Action Required
11/08/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Project cost
Corrective Action Required
11/08/2017

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is for informational purposes.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
11/08/2017

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify design to provide minimum 18" at latch side of door #7 out of northern restroom as well as door out of "optional" reception area restroom.
Plan Submittal 2012 Codes
Corrective Action Required
11/08/2017

All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise sheets TF-1, A-2, and A-4 to depict correct accessibility code which is 2009 ICC/ANSI A117.1.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
11/08/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant restroom finish materials. (if paint is used it must be epoxy based)
Bldg - Size of doors 1008.1.1
Corrective Action Required
11/08/2017

2012 IBC 1008.1.1 – Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in a Group i-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of door openings shall not be less than 80 inches. See Code for possible exceptions. Action required: Modify floor plan and door schedule to apply. (ref: door #5)
Misc
Corrective Action Required
11/08/2017

2011 NEC 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Areas. Wiring in patient care areas shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care areas shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, or metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductor. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1.The grounding terminals of all receptacles. 2.Metal Boxes and enclosures containing receptacles. 3.All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (refer code for exceptions) (2)Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Licensed Contractors Rejected 11/06/2017 11/08/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
11/08/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
11/08/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $412.38 $412.38 Paid 11/15/2017
8331507-Sewer Connection Fee $210.00 $210.00 Paid 11/15/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 12/1/2017 at 1:45 PM 12/01/2017
Misc
Partial Correction
12/01/2017
OK TO COVER WALLS AT: CLERICAL STAFF AREA EXCEPT AT LOCATIONS WHERE HOLES IN TOP AND BOTTOM PLATES MUST BE FIRE-BLOCKED;
All Rough Inspection - Commercial Failed 1/2/2018 1/2/2018 at 10:25 AM 01/02/2018
Misc
Partial Correction
12/01/2017
OK TO COVER WALLS AT: CLERICAL STAFF AREA EXCEPT AT LOCATIONS WHERE HOLES IN TOP AND BOTTOM PLATES MUST BE FIRE-BLOCKED;
Misc
Corrective Action Required
01/02/2018
PHASE 2 AREA: FIRE-BLOCKING; BOCA PLATE;
All Rough Inspection - Commercial Partial 1/2/2018 at 1:25 PM 01/02/2018
Misc
Partial Correction
01/02/2018
OK TO COVER WALLS AT: CLERICAL STAFF AREA; [RECEPTION RESTROOM; DOCTOR OFFICE #1; HALLWAY EXAM RM #1; EXAM RM #2; EXAM RM #3; OFFICE;
Misc
Resolved
01/02/2018
PHASE 2 AREA: FIRE-BLOCKING; BOCA PLATE;
Final Inspection - Commercial Partial 1/3/2018 1/3/2018 at 7:05 AM 01/03/2018
Misc
Partial Correction
01/03/2018
STAFF AREA: PRE-FINAL
Occupancy Inspection - Fire Partial 1/3/2018 01/03/2018
Final Inspection - Commercial Partial 1/3/2018 at 3:00 PM 01/03/2018
Misc
Partial Correction
01/03/2018
SPACES OK FOR USE & OCCUPANCY PER CODES & FIRE DEPARTMENT: STAFF "BACK OFFICE"; RECEPTION NEW OFFICE;
Occupancy Inspection - Fire Passed 2/12/2018 02/12/2018
Final Inspection - Commercial Passed 2/12/2018 2/12/2018 at 3:20 PM 02/12/2018
Misc
Resolved
02/12/2018
SPACES OK FOR USE & OCCUPANCY PER CODES & FIRE DEPARTMENT: STAFF "BACK OFFICE"; RECEPTION NEW OFFICE;
Documents & Images
Date Uploaded File Type Document Name
11/08/2017 Letter Fire Building Plan Review
11/08/2017 Letter Codes P/R Corrections Document
11/15/2017 Receipt Receipt for transaction: 2017-007287
11/21/2017 Letter Fire Building Plan Review
11/22/2017 Letter Codes P/R Corrections Document
11/30/2017 Letter Fire Building Plan Review
11/30/2017 Letter Codes Plan Review Conditions
11/30/2017 Letter Codes Building Permit
12/01/2017 Letter Inspection Summary
01/02/2018 Letter Inspection Summary
01/03/2018 Letter Inspection Summary
02/12/2018 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.