Permit Application Status

PRCOM20172529


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20172529
Building Permit - Commercial
Certificate of Occupancy
PARROT PROPERTIES INC
NEW MULTI-FAMILY
NEW 2 STORY APARTMENT BUILDING WITH PARKING GARAGE BENEATH FOUNDATION PERMIT - PRCOM20181909
07/24/2017
12/06/2019
08/26/2020
Locations
Contacts
CITYSCAPE CONSTRUCTION VIEW HIGH LLC, Address:10 W CARMEL DR STE 200, Phone:(317) 574-1600 Ext:100  
STANDARD HEATING & COOLING TOO LLC, Address:2006 E PRAIRIE CIRCLE , Phone:(913) 782-5409  
STANDARD ELECTRIC COMPANY INC, Address:2006 E PRAIRIE CIRCLE, Phone:(913) 782-5409  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
SGN+A ARCHITECTS, Address:315 W PONCE DE LEON AVE #755, Phone:(404) 373-7370  
LATIMER SOMMERS & ASSOCIATES PA, Address:3639 SW SUMMERFIELD DR STE A, Phone:(785) 233-3232  
PARROT PROPERTIES INC, Address:11303 VIEW HIGH DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 08/07/2018 02/16/2018
Joe Frogge
Building Plan Review Approved 08/07/2018 02/16/2018
Joe Frogge
Licensed Contractors Approved 07/25/2018 02/16/2018
Joe Frogge
Special Inspections Review Approved 08/24/2017
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Multi-Family $10,486.73 $10,486.73 Paid 12/06/2019
8331507-Sewer Connection Fee $3,000.00 $3,000.00 Paid 12/06/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 3/4/2020 3/4/2020 03/04/2020
FIRST FLOOR
Corrective Action Required
03/04/2020
incomplete inspection Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . Incomplete inspection on 1st, 2nd floors
SECOND FLOOR
Corrective Action Required
03/04/2020
incomplete inspections 2nd floor - 201- draft stop between units. Secure service entrance cables 4.5ft. Seal between floors and in floor truss space. Plumb plates laundry water line at top plates. 202-Plumbing plates shower wall south end. Strap top plates at columns in kitchen. Corridor walls support truss at cut in top plates. And over dryer boxes. 204- 203- 205- 206- studs laundry wall bored for plumbing . Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . Incomplete inspection on 1st, 2nd floors
THIRD FLOOR
Corrective Action Required
03/04/2020
3rd floor- Dryer boxes 5 sided throughout building, all fire blocking at dbl wall construction and floor ceiling penetrations, basement level at foundation wall vertical to horizontal, Draft stops at no more than 2 units or 3000 sq ft. Submit Special inspection report for structural items. 311 dryer boxes Hurricane ties west truss over entrance. 312-Truss blocking ties front bedroom ,NW bed. Pre-rock dead space chase Fire block at 10ft between party walls. - Puddy pads kitchen wall. 310-h ties over back door and porch for truss. 309-h ties over porch blocking ties between trusses. 307- plus protection top plate right of sink. Fire stop dbl wall north end. 308-truss blocking , hole floor of bathroom at prerock. Plumb plates kit. Corridor joist hanger Ceiling joist in hallway 305- block dead space , dbl wall fire top . 306- elect nail plate top plate bedroom. 304-frig box. Plates at kit plmb 303- frig box Plates at kit plmb, Support plumbing in attic. Corridor truss clips. Truss blocking clips. 301- back to back boxes. 2nd floor - 201- draft stop between units. Secure service entrance cables 4.5ft. Seal between floors and in floor truss space. Plumb plates laundry water line at top plates. 202-Plumbing plates shower wall south end. Strap top plates at columns in kitchen. Corridor walls support truss at cut in top plates. And over dryer boxes. 204- 203- 205- 206- studs laundry wall bored for plumbing . Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . Incomplete inspection on 1st, 2nd floors
Sprinkler - Hydrostatic Test Passed 3/6/2020 03/06/2020
All Rough Inspection - Commercial Partial 3/12/2020 3/12/2020 03/12/2020
FIRST FLOOR
Corrective Action Required
03/04/2020
incomplete inspection Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . Incomplete inspection on 1st, 2nd floors
SECOND FLOOR
Corrective Action Required
03/04/2020
incomplete inspections 2nd floor - 201- draft stop between units. Secure service entrance cables 4.5ft. Seal between floors and in floor truss space. Plumb plates laundry water line at top plates. 202-Plumbing plates shower wall south end. Strap top plates at columns in kitchen. Corridor walls support truss at cut in top plates. And over dryer boxes. 204- 203- 205- 206- studs laundry wall bored for plumbing . Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . Incomplete inspection on 1st, 2nd floors
THIRD FLOOR
Corrective Action Required
03/04/2020
3rd floor- Dryer boxes 5 sided throughout building, all fire blocking at dbl wall construction and floor ceiling penetrations, basement level at foundation wall vertical to horizontal, Draft stops at no more than 2 units or 3000 sq ft. Submit Special inspection report for stru ctural items. 311 dryer boxes. 2nd floor - Corridor walls support truss at cut in top plates. And over dryer boxes. 204- 203- 205- 206- studs laundry wall bored for plumbing . Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . 207 fire caulk tension rod laundry 208 boca plate plumbing pantry 209 fire caulk tension rod bedroom 210 anchor bolts exterior walls 211 nail bottom plate shower bath 212 provide anchor bolts exterior walls Incomplete inspection on 1st
All Rough Inspection - Commercial Failed 3/18/2020 3/18/2020 03/18/2020
FIRST FLOOR
Corrective Action Required
03/12/2020
Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist G 7 / G 8 Fire block at double wall
SECOND FLOOR
Corrective Action Required
03/12/2020
2nd floor - 206- studs laundry wall bored for plumbing Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . Incomplete inspection on 1st
THIRD FLOOR
Corrective Action Required
03/12/2020
3rd floor- Dryer boxes 5 sided throughout building, all fire blocking at dbl wall construction and floor ceiling penetrations, basement level at foundation wall vertical to horizontal, Draft stops at no more than 2 units or 3000 sq ft. Submit Special inspection report for structural items. 311 dryer boxes. Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist
All Rough Inspection - Commercial Partial 3/23/2020 3/23/2020 03/23/2020
FIRST FLOOR
Corrective Action Required
03/18/2020
Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist G 7 / G 8 Fire block at double wall
SECOND FLOOR
Corrective Action Required
03/18/2020
2nd floor - 206- studs laundry wall bored for plumbing Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist . Incomplete inspection on 1st
THIRD FLOOR
Corrective Action Required
03/18/2020
3rd floor- Dryer boxes 5 sided throughout building, all fire blocking at dbl wall construction and floor ceiling penetrations, basement level at foundation wall vertical to horizontal, Draft stops at no more than 2 units or 3000 sq ft. Submit Special inspection report for structural items. 311 dryer boxes. Note: ground level need fire BLocking at foundation wall every10ft and at bottom of joist
Rated Assembly Inspection Partial 3/25/2020 03/25/2020
Misc
Informational
03/25/2020
RC channel ceiling & corridor walls all 3 floors Complete
All Rough Inspection - Commercial Partial 3/25/2020 03/25/2020
FIRST FLOOR
Resolved
03/25/2020
SECOND FLOOR
Resolved
03/25/2020
THIRD FLOOR
Corrective Action Required
03/23/2020
< Submit Special inspection report for structural items. >
Electrical Service Inspection Passed 4/9/2020 4/9/2020 04/09/2020
Rated Assembly Inspection Partial 4/10/2020 4/10/2020 04/10/2020
THIRD FLOOR
Informational
04/10/2020
- screw pattern 3rd floor unit & corridor walls & ceilings OK -
STAIR TOWER 1
Corrective Action Required
04/10/2020
- 3rd floor screw pattern walls & ceiling OK -
STAIR TOWER 2
Corrective Action Required
04/10/2020
- 3rd floor screw pattern walls & ceiling OK -
STAIR TOWER 3
Corrective Action Required
04/10/2020
- 3rd floor screw patttern walls & ceiling OK -
STAIR TOWER 4
Corrective Action Required
04/10/2020
- 3rd floor screw pattern walls & ceiling OK -
Rated Assembly Inspection Partial 4/15/2020 4/15/2020 04/15/2020
THIRD FLOOR
Informational
04/10/2020
- screw pattern 3rd floor unit & corridor walls & ceilings OK -
STAIR TOWER 1
Informational
04/15/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING OK -
STAIR TOWER 2
Informational
04/15/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING -
SECOND FLOOR
Resolved
04/15/2020
UNIT 202 REPLACE TYPE X ON CEILING WITH TYPE C
Rated Assembly Inspection Failed 4/24/2020 4/24/2020 04/24/2020
STAIR TOWER 2
Informational
04/15/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING -
STAIR TOWER 1
Informational
04/15/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING OK -
THIRD FLOOR
Informational
04/15/2020
- screw pattern 3rd floor unit & corridor walls & ceilings OK -
FIRST FLOOR
Corrective Action Required
04/24/2020
-FOLLOWING AREAS REPLACE TYPE X WITH TYPE C UNIT 109 ENTRY CLOSET G5 CORRIDOR UNIT 109 TO G5 ELECTRICAL ROOM 10" SCREW PATTERNS SHALL BE 8"
Rated Assembly Inspection Partial 4/27/2020 4/27/2020 04/27/2020
STAIR TOWER 2
Informational
04/24/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING -
STAIR TOWER 1
Informational
04/24/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING OK -
THIRD FLOOR
Informational
04/24/2020
- screw pattern 3rd floor unit & corridor walls & ceilings OK - - SCREW PATTERN 2ND FLLOR OK TO TAPE
FIRST FLOOR
Resolved
04/27/2020
1ST FLOOR SCREW PATTERN OK TO TAPE
Sprinkler - Flow Test Passed 8/13/2020 08/13/2020
Alarm Test Passed 8/13/2020 08/13/2020
Occupancy Inspection - Fire Failed 8/18/2020 8/18/2020 08/18/2020
Occupancy Inspection - Codes Commercial Failed 8/18/2020 8/18/2020 08/18/2020
Misc
Corrective Action Required
08/18/2020
- 109 ANTI TIP DEVICE RANGE, SPRINKLER HEAD PATIO - - G 10 SELF CLOSING DOOR - - FIRE CAULK LOW VOLT ALL GARAGES - - ELECTRICAL ROOM NEXT TO G3 FIRE CAULK CEILING - - LABEL A/C DISCONNECTS - - LABEL MAIN DISCONNECTS - - 2ND STORY STAIRS FIRE CAULK RISER PIPE - - SIDEWALK REAR ENTRANCE - - BUBBLE COVERS - - SEAL EXTERIOR LIGHT FIXTURES - - INSTALL A/C CONDENSORS - - GUARDRAIL RETAINING WALL -
Occupancy Inspection - Fire Passed 8/24/2020 8/24/2020 08/24/2020
Occupancy Inspection - Codes Commercial Failed 8/24/2020 8/24/2020 08/24/2020
Misc
Resolved
08/26/2020
Codes OK for TCO pending other depts
Water Service Inspection Passed 8/24/2020 08/24/2020
Occupancy Inspection - Engineering Passed 8/24/2020 08/24/2020
Rated Assembly Inspection Passed 8/26/2020 08/26/2020
STAIR TOWER 2
Informational
04/27/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING -
STAIR TOWER 1
Informational
04/27/2020
- 3rd floor screw pattern walls & ceiling OK - - 2ND FLOOR SCREW PATTERN WALLS & CEILING OK -
THIRD FLOOR
Informational
04/27/2020
- screw pattern 3rd floor unit & corridor walls & ceilings OK - - SCREW PATTERN 2ND FLLOR OK TO TAPE
All Rough Inspection - Commercial Passed 8/26/2020 08/26/2020
THIRD FLOOR
Corrective Action Required
03/25/2020
< Submit Special inspection report for structural items. >
Rough Electrical Inspection - Commercial Passed 8/26/2020 08/26/2020
Rough Mechanical Inspection - Commercial Passed 8/26/2020 08/26/2020
Rough Plumbing Inspection - Commercial Passed 8/26/2020 08/26/2020
Final Mechanical Inspection Passed 8/26/2020 08/26/2020
Final Electrical Inspection - Commercial Passed 8/26/2020 08/26/2020
Final Plumbing Inspection - Commercial Passed 8/26/2020 08/26/2020
Occupancy Inspection - Water Utilities Passed 8/26/2020 08/26/2020
Occupancy Inspection - Planning Passed 8/26/2020 11/05/2020
Occupancy Inspection - Codes Commercial Full C of O 8/26/2020 11/06/2020
Misc
Resolved
08/26/2020
Codes OK for TCO pending other depts
Documents & Images
Date Uploaded File Type Document Name
10/16/2017 Meridian Site Map
12/06/2019 Letter DS Building Permit
03/04/2020 Letter INSPECTION SUMMARY
03/18/2020 Letter INSPECTION SUMMARY
03/25/2020 Letter INSPECTION SUMMARY
03/25/2020 Letter INSPECTION SUMMARY
04/09/2020 Letter INSPECTION SUMMARY
04/10/2020 Letter INSPECTION SUMMARY
04/15/2020 Letter INSPECTION SUMMARY
04/24/2020 Letter INSPECTION SUMMARY
08/18/2020 Letter INSPECTION SUMMARY
08/24/2020 Letter INSPECTION SUMMARY
08/26/2020 Letter Codes Temporary Certificate of Occupancy
11/06/2020 Letter Codes Temporary Certificate of Occupancy
11/06/2020 Letter Field Certificate of Occupancy
11/06/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home