Summary
PRCOM20171075
Building Permit - Commercial
Final Completion
MAZUMA CREDIT UNION
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO BANK **Police review required at final. Contact officers Scott Doumitt and Carmen Spaeth
04/10/2017
05/26/2017
10/09/2017
07/28/2017
Locations
Contacts
GRAYLING INC, Address:10258 W 87TH ST, Phone:(913) 341-5444  
METALCRAFT INC, Address:5138 MERRIAM DR., Phone:(913) 707-8824  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
KLOVER ARCHITECTS, Address:10955 LOWELL AVE, Phone:(913) 649-8181  
MAZUMA CREDIT UNION, Address:9300 TROOST AVE  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 04/17/2017 05/26/2017
Joe Frogge
LC - General Contractor
Resolved
05/26/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 4/20/17 - acknowledged in letter
LC - MEP Subs
Resolved
05/26/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 4/20/17 - acknowledged in letter
Building Plan Review Approved with Conditions 04/24/2017 04/21/2017
Joe Frogge
License Tax Application
Corrective Action Required
04/17/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 4/20/17 - acknowledged in letter
Misc
Resolved
04/20/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment (MCU-1) will be screened per referenced UDO section. 4/20/17 - per architect, the existing parapets fully screen the equipment
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Resolved
04/20/2017

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Modify Back Teller Station to provide minimum 36" of accessible space at maximum 36" high. 4/20/17 - per architect, the furniture noted is not for customers
Misc
Resolved
04/21/2017

Section 7.330. CPTED Review Requirement. All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”. Section 7.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space. 1. Bank/Financial Services 2. Bank Drive-Thru Facility 3. Check Cashing and Payday Loan Business 4. Convenience Store (C-Store) 5. Financial Services with Drive-up Window or Drive-Thru Facility 6. Pawn Shop 7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand 8. Unattended self-serve gas pumps 9. Unsecured Loan Business 10. Other similar uses shall meet the same standards as the above Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved. 4/21/17 - approved via letter from architect
Fire Plan Review Approved with Conditions 04/24/2017 04/20/2017
Joe Dir
Misc
Corrective Action Required
04/20/2017

All previous conditions have been acknowledged and addresses with resubmittal.
Building Plan Review Rejected 04/20/2017 04/12/2017
Joe Frogge
License Tax Application
Corrective Action Required
04/12/2017

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
04/12/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment (MCU-1) will be screened per referenced UDO section.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
04/12/2017

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Modify Back Teller Station to provide minimum 36" of accessible space at maximum 36" high.
Misc
Corrective Action Required
04/12/2017

Section 7.330. CPTED Review Requirement. All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”. Section 7.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space. 1. Bank/Financial Services 2. Bank Drive-Thru Facility 3. Check Cashing and Payday Loan Business 4. Convenience Store (C-Store) 5. Financial Services with Drive-up Window or Drive-Thru Facility 6. Pawn Shop 7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand 8. Unattended self-serve gas pumps 9. Unsecured Loan Business 10. Other similar uses shall meet the same standards as the above Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved.
Licensed Contractors Rejected 04/10/2017 04/12/2017
Joe Frogge
LC - General Contractor
Corrective Action Required
04/12/2017

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
04/12/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 04/20/2017 04/11/2017
Joe Dir
Address numbers required
Corrective Action Required
04/11/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Post the numeric address of 1155 on the building in a contrasting color to the background. Address shall be readable from the roadway (Douglas St.)
Portable fire extinguishers - general
Corrective Action Required
04/11/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide a minimum of two 2A-10BC fire extinguishers. (rating 5 pound)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
04/11/2017

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. ACTION REQUIRED: (verified at inspection) Mount the fire extinguishers on a normal path of travel close to an exit. The travel distance to an extinguisher shall be a maximum distance of 75 feet from anywhere within the business.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $494.85 $494.85 Paid 05/26/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 6/14/2017 6/14/2017 06/14/2017
Misc
Partial Correction
06/14/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WAR ROOM [109] COMPLETE PREIMETER BOTH FACES;
Underslab Electrical Inspection - Commercial Passed 6/26/2017 06/26/2017
In-wall Inspection Partial 7/13/2017 7/13/2017 07/13/2017
Misc
Partial Correction
06/14/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WAR ROOM [109] COMPLETE PREIMETER BOTH FACES; CURVED SHORT WALL AT COFFEE BAR; CROSSWALL AT DOOR OPENING #3;
Above Ceiling Inspection Partial 7/14/2017 7/14/2017 07/14/2017
Misc
Partial Correction
07/14/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS AT: 132 ABOVE TELLER STATIONS; CORRIDOR SOUTH TO VAULT;
Above Ceiling Inspection Partial 07/14/2017
Misc
Resolved
07/31/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS AT: 132 ABOVE TELLER STATIONS; CORRIDOR SOUTH TO VAULT; CUT BORDERS LESS THAN 2' AT WAR ROOM;
Above Ceiling Inspection Passed 7/21/2017 7/21/2017 07/21/2017
Misc
Resolved
07/21/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS AT: 132 ABOVE TELLER STATIONS; CORRIDOR SOUTH TO VAULT; CUT BORDERS LESS THAN 2' AT WAR ROOM;
Final Inspection - Commercial Passed 7/31/2017 7/31/2017 07/31/2017
In-wall Inspection Passed 7/13/2017 07/31/2017
Misc
Resolved
07/31/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: WAR ROOM [109] COMPLETE PREIMETER BOTH FACES; CURVED SHORT WALL AT COFFEE BAR; CROSSWALL AT DOOR OPENING #3;
Occupancy Inspection - Fire Passed 7/31/2017 07/31/2017
Documents & Images
Date Uploaded File Type Document Name
04/11/2017 Letter Fire Building Plan Review
04/12/2017 Letter Codes P/R Corrections Document
04/20/2017 Mazuma Security
04/20/2017 Letter Fire Building Plan Review
05/26/2017 Letter Codes Plan Review Conditions
05/26/2017 Receipt Receipt for transaction: 2017-003177
05/26/2017 Letter Codes Building Permit
06/14/2017 Letter Inspection Summary
06/26/2017 Letter Inspection Summary
07/13/2017 Letter Inspection Summary
07/14/2017 Letter Inspection Summary
07/21/2017 Letter Inspection Summary
07/31/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home