Permit Application Status

PRCOM20162474


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20162474
Building Permit - Commercial
Final Completion
LAW OFFICE OF CAMRON HOORFAR PC
ALTERATION COMMERCIAL
STRUCTURAL REPAIRS AND ELECTRICAL FULL PERMIT: PRCOM20162403
09/28/2016
09/28/2016
11/29/2017
Locations
Contacts
LAW OFFICE OF CAMRON HOORFAR PC, Address:415 SW JEFFERSON ST  
ASAP ANY AND ALL CO, Address:617 W GROVER ST, Phone:(816) 612-7579  
AMERICAN LEGACY CONSTRUCTION GROUP, Address:1121 SE BROADWAY DR , Phone:(816) 554-3800  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 10/10/2016 09/28/2016
Development Center
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $32.99 $32.99 Paid 09/28/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 10/5/2016 10/05/2016
Misc
Partial Correction
10/05/2016
THREE FOOTINGS AT 30"x30" + ONE AT 16"x16" PREPARED FOR POUR. ONE ADDITIONAL AT 16"x16" TO BE SHOWN ON REVISED DRAWING NOT READY FOR INSPECTION.
Footing Inspection - Commercial Failed 11/16/2016 (9:30) 11/16/2016 11/16/2016
Misc
Partial Correction
10/05/2016
THREE FOOTINGS AT 30"x30" + ONE AT 16"x16" PREPARED FOR POUR. ONE ADDITIONAL AT 16"x16" TO BE SHOWN ON REVISED DRAWING NOT READY FOR INSPECTION.
Misc
Corrective Action Required
11/16/2016
FOUR PIERS AT WEST END OF BUILDING FOUND TO HAVE 0"(NW PIER DOES NOT EXTEND BELOW GRADE) TO 18" DEPTH BELOW GRADE. NOT APPROVED TO SUPPORT ANTICIPATED DEAD AND LIVE LOADS. LICENSED A/E REPORT REQUIRED. PHONE CALL TO "ENGINEER" CONTACT NUMBER PROVIDED PRODUCED UNINTELLIGIBLE RESPONSE.
All Rough Inspection - Commercial Partial 11/21/2016 11/21/2016 11/21/2016
Misc
Partial Correction
11/21/2016
NO ISSUES FOUND ON INSTALLATION OF TRIPLE 2x10 CENTER BEAM AND 6x6 POSTS AT BASEMENT
All Rough Inspection - Commercial Partial 11/22/2016 11/22/2016 11/22/2016
Misc
Partial Correction
11/21/2016
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL;
Footing Inspection - Commercial Partial 12/9/2016 12/09/2016
Misc
Partial Correction
11/16/2016
BASEMENT: THREE FOOTINGS AT 30"x30" + ONE AT 16"x16" PREPARED FOR POUR. ONE ADDITIONAL AT 16"x16"; ADDITIONAL 16"x16" FOOTING AT BASE OF SOUTH STAIR STRINGER;
Misc
Corrective Action Required
11/16/2016
FOUR PIERS AT WEST END OF BUILDING FOUND TO HAVE 0"(NW PIER DOES NOT EXTEND BELOW GRADE) TO 18" DEPTH BELOW GRADE. NOT APPROVED TO SUPPORT ANTICIPATED DEAD AND LIVE LOADS. LICENSED A/E REPORT REQUIRED. PHONE CALL TO "ENGINEER" CONTACT NUMBER PROVIDED PRODUCED UNINTELLIGIBLE RESPONSE.
All Rough Inspection - Commercial Partial 12/9/2016 12/09/2016
Misc
Partial Correction
11/22/2016
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC;
Footing Inspection - Commercial Not Ready 12/22/2016 (10:00) 12/22/2016 12/22/2016
Misc
Partial Correction
12/09/2016
BASEMENT: THREE FOOTINGS AT 30"x30" + ONE AT 16"x16" PREPARED FOR POUR. ONE ADDITIONAL AT 16"x16"; ADDITIONAL 16"x16" FOOTING AT BASE OF SOUTH STAIR STRINGER;
Misc
Corrective Action Required
12/09/2016
FOUR PIERS AT WEST END OF BUILDING FOUND TO HAVE 0"(NW PIER DOES NOT EXTEND BELOW GRADE) TO 18" DEPTH BELOW GRADE. NOT APPROVED TO SUPPORT ANTICIPATED DEAD AND LIVE LOADS. LICENSED A/E REPORT REQUIRED. PHONE CALL TO "ENGINEER" CONTACT NUMBER PROVIDED PRODUCED UNINTELLIGIBLE RESPONSE.
Footing Inspection - Commercial Partial 12/27/2016 12/27/2016 12/27/2016
Misc
Partial Correction
12/22/2016
BASEMENT: THREE FOOTINGS AT 30"x30" + ONE AT 16"x16" PREPARED FOR POUR. ONE ADDITIONAL AT 16"x16"; ADDITIONAL 16"x16" FOOTING AT BASE OF SOUTH STAIR STRINGER; ADDITIONAL 16"x16" FOOTING AT CENTER OF NEW LVL BEAM AT BASEMENT;
Misc
Partial Correction
12/27/2016
FOUR PIERS AT WEST END OF BUILDING FOUND TO HAVE 0"(NW PIER DOES NOT EXTEND BELOW GRADE) TO 18" DEPTH BELOW GRADE. NOT APPROVED TO SUPPORT ANTICIPATED DEAD AND LIVE LOADS. LICENSED A/E REPORT REQUIRED. PHONE CALL TO "ENGINEER" CONTACT NUMBER PROVIDED PRODUCED UNINTELLIGIBLE RESPONSE.
Footing Inspection - Commercial Partial 12/27/2016 12/27/2016
Misc
Partial Correction
12/27/2016
BASEMENT: THREE FOOTINGS AT 30"x30" + ONE AT 16"x16" PREPARED FOR POUR. ONE ADDITIONAL AT 16"x16"; ADDITIONAL 16"x16" FOOTING AT BASE OF SOUTH STAIR STRINGER; ADDITIONAL 20"x20" FOOTING AT CENTER OF NEW LVL BEAM AT BASEMENT SOUTH OF STAIR;
Misc
Partial Correction
12/27/2016
FOUR PIERS AT WEST END OF BUILDING FOUND TO HAVE 0"(NW PIER DOES NOT EXTEND BELOW GRADE) TO 18" DEPTH BELOW GRADE. NOT APPROVED TO SUPPORT ANTICIPATED DEAD AND LIVE LOADS. LICENSED A/E REPORT REQUIRED. PHONE CALL TO "ENGINEER" CONTACT NUMBER PROVIDED PRODUCED UNINTELLIGIBLE RESPONSE.
All Rough Inspection - Commercial Partial 1/10/2017 1/10/2017 01/10/2017
Misc
Partial Correction
12/09/2016
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC; W4x13 HEADER OVER WEST ENTRANCE DOOR; NOTED SIX 6x6 WOOD COLUMNS AT BASEMENT SUBJECT TO APPROVAL WHEN APPROVED DRAWINGS ARE ON SITE.
Electrical Service Inspection Partial 1/10/2017 1/10/2017 01/10/2017
Misc
Corrective Action Required
01/10/2017
SUPPLEMENTAL GROUND ROD CONNECTION NOT FOUND EXPOSED FOR INSPECTION
All Rough Inspection - Commercial Partial 1/12/2017 1/12/2017 01/12/2017
Misc
Partial Correction
01/10/2017
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC; W4x13 HEADER OVER WEST ENTRANCE DOOR; SIX 6x6 WOOD COLUMNS AT BASEMENT;
Electrical Service Inspection Passed 1/12/2017 01/12/2017
Misc
Resolved
01/12/2017
SUPPLEMENTAL GROUND ROD CONNECTION NOT FOUND EXPOSED FOR INSPECTION
Piers/Caissons Inspection - Commercial Partial 1/19/2017 01/19/2017
Misc
Partial Correction
01/19/2017
OK TO POUR WHEN READY PIERS AT WEST END OF BUILDING AT LOCATIONS AS NUMBERED ON APPROVED DRAWING: #2; #3;
Footing Inspection - Commercial Passed 1/19/2017 (9:30) 1/19/2017 01/19/2017
Misc
Resolved
01/19/2017
BASEMENT: THREE FOOTINGS AT 30"x30" + ONE AT 16"x16" PREPARED FOR POUR. ONE ADDITIONAL AT 16"x16"; ADDITIONAL 16"x16" FOOTING AT BASE OF SOUTH STAIR STRINGER; ADDITIONAL 20"x20" FOOTING AT CENTER OF NEW LVL BEAM AT BASEMENT SOUTH OF STAIR;
Misc
Resolved
01/19/2017
FOUR PIERS AT WEST END OF BUILDING FOUND TO HAVE 0"(NW PIER DOES NOT EXTEND BELOW GRADE) TO 18" DEPTH BELOW GRADE. NOT APPROVED TO SUPPORT ANTICIPATED DEAD AND LIVE LOADS. LICENSED A/E REPORT REQUIRED. PHONE CALL TO "ENGINEER" CONTACT NUMBER PROVIDED PRODUCED UNINTELLIGIBLE RESPONSE.
Piers/Caissons Inspection - Commercial Partial 1/25/2017 (11:30) 1/25/2017 01/25/2017
Misc
Partial Correction
01/19/2017
OK TO POUR WHEN READY PIERS AT WEST END OF BUILDING AT LOCATIONS AS NUMBERED ON APPROVED DRAWING: #2; #3; #1;
Piers/Caissons Inspection - Commercial Partial 1/26/2017 (8:00) 1/26/2017 01/26/2017
Misc
Partial Correction
01/25/2017
OK TO POUR WHEN READY PIERS AT WEST END OF BUILDING AT LOCATIONS AS NUMBERED ON APPROVED DRAWING: #2; #3; #1; #6;
Piers/Caissons Inspection - Commercial Passed 1/31/2017 (1:00) 1/31/2017 01/31/2017
Misc
Resolved
01/31/2017
OK TO POUR WHEN READY PIERS AT WEST END OF BUILDING AT LOCATIONS AS NUMBERED ON APPROVED DRAWING: #2; #3; #1; #6; #4; #5
All Rough Inspection - Commercial Partial 2/9/2017 2/9/2017 02/09/2017
Misc
Partial Correction
01/12/2017
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC; W4x13 HEADER OVER WEST ENTRANCE DOOR; SIX 6x6 WOOD COLUMNS AT BASEMENT;
All Rough Inspection - Commercial Partial 2/17/2017 2/17/2017 02/17/2017
Misc
Partial Correction
01/12/2017
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC; W4x13 HEADER OVER WEST ENTRANCE DOOR; SIX 6x6 WOOD COLUMNS AT BASEMENT; 1ST FLOOR INTERIOR WALL STRAP BRACING COMPLETE PER DRAWING;
All Rough Inspection - Commercial Partial 2/22/2017 2/22/2017 02/22/2017
Misc
Partial Correction
02/17/2017
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC; W4x13 HEADER OVER WEST ENTRANCE DOOR; SIX 6x6 WOOD COLUMNS AT BASEMENT; 1ST FLOOR INTERIOR WALL STRAP BRACING COMPLETE PER DRAWING; SUBFLOOR PATCHES AT HVAC OVER-CUTS;
All Rough Inspection - Commercial Partial 3/1/2017 3/1/2017 03/01/2017
Misc
Partial Correction
02/22/2017
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC; W4x13 HEADER OVER WEST ENTRANCE DOOR; SIX 6x6 WOOD COLUMNS AT BASEMENT; 1ST FLOOR INTERIOR WALL STRAP BRACING COMPLETE PER DRAWING; SUBFLOOR PATCHES AT HVAC OVER-CUTS; TWO 2x8 HEADERS INSTALLED TO SUPPORT LOADS ABOVE AT EAST END OF 1ST FLOOR
All Rough Inspection - Commercial Passed 3/1/2017 08/28/2017
Misc
Resolved
08/28/2017
NO ISSUES FOUND ON: INSTALLATION OF TRIPLE 2x10 CENTER BEAM, JOISTS AND 6x6 POSTS AT BASEMENT; RESTROOM WALL, WINDOW AND DOOR FRAMING AT UPPER LEVEL; 2x4 STUDS ADDED TO SOUTH KNEE WALL FRAMING AT ATTIC; W4x13 HEADER OVER WEST ENTRANCE DOOR; SIX 6x6 WOOD COLUMNS AT BASEMENT; 1ST FLOOR INTERIOR WALL STRAP BRACING COMPLETE PER DRAWING; SUBFLOOR PATCHES AT HVAC OVER-CUTS; TWO DOUBLE 2x8 HEADERS INSTALLED AT EAST END OF 1ST FLOOR TO SUPPORT LOADS ABOVE;
Corrective Action Required
08/28/2017
Miscellaneous Inspection Passed 8/29/2017 at 9:05 AM 08/29/2017
Final Inspection - Commercial Passed 11/29/2017 at 1:00 PM 11/29/2017
Investigation Inspection Complete 11/30/2017 11/29/2017
Documents & Images
Date Uploaded File Type Document Name
09/28/2016 Receipt Receipt for transaction: 2016-006148
09/28/2016 Letter Codes Building Permit
10/05/2016 Letter Inspection Summary
11/16/2016 Harfoor struct repair
11/16/2016 Letter Inspection Summary
11/21/2016 Letter Inspection Summary
11/22/2016 Letter Inspection Summary
12/09/2016 Letter Inspection Summary
12/21/2016 more struct repairs
12/22/2016 Letter Inspection Summary
12/27/2016 Letter Inspection Summary
12/27/2016 Letter Inspection Summary
01/10/2017 Letter Inspection Summary
01/12/2017 Letter Inspection Summary
01/19/2017 Letter Inspection Summary
01/26/2017 Letter Inspection Summary
01/26/2017 Letter Inspection Summary
01/26/2017 Letter Inspection Summary
01/31/2017 Letter Inspection Summary
02/17/2017 Letter Inspection Summary
02/22/2017 Letter Inspection Summary
03/01/2017 Letter Inspection Summary
08/29/2017 Letter Inspection Summary
11/29/2017 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home