Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
|
10/06/2016
|
|
Joe Dir
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED SERVICE / MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SYSTEM RISER.
(VERIFIED AT INSPECTION)
|
|
|
Fire Plan Review
|
Approved with Conditions
|
09/22/2016
|
09/19/2016
|
|
Joe Dir
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 1184 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATION TO BE DONE TO THE FIRE SPRINKLER SYSTEM. All fire sprinkler system work shall be conducted by a certified sprinkler company.
all rooms within the suite shall have fire sprinkler coverage. Storage closet off the kitchen area appears to need coverage.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH REQUIRED ANNUAL MAINTENANCE/ SERVICE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SPRINKLER RISER.
(VERIFIED AT INSPECTION)
|
|
Misc
Corrective Action Required
Other previous review conditions have been addressed in the resub letter and or resub plans.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
09/16/2016
|
|
Joe Dir
|
|
Misc
Corrective Action Required
IFC 2012 MANUAL FIRE ALARM BOXES
2. Manual fire alarm boxes are not required in Group E occupancies where all of the following apply:
2.1. Interior corridors are protected by smoke detectors.
2.2. Auditoriums, cafeterias, gymnasiums and similar areas are protected by heat detectors or other approved detection devices.
2.3. Shops and laboratories involving dusts or vapors are protected by heat detectors or other approved detection devices.
3. Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, the emergency voice/alarm communication system will activate on sprinkler water flow and manual activation is provided from a normally occupied location.
ADDTION OF A ANNUNCIATOR NOT REQUIRED DUE TO A ADDRESSABLE MONITORIED FIRE ALARM PANEL
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACCEPTANCE TESTING OF THE NOTIFICATION AND ACTIVATION DEVICES WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
|
|
|
Building Plan Review
|
Approved
|
09/22/2016
|
09/15/2016
|
|
Joe Frogge
|
|
Misc
2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist:
1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2).
2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1.
3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits.
(see code section for exceptions)
Action required: Provide two exits from tenant space. Doors to swing in direction of travel. Provide exit lighting and panic hardware where appropriate. (note: if door 107 swings in direction of egress travel it would then violate 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances.)
9/12/16 - Door 107 will likely have to be removed in that it now violates 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances. i.e. 18" is required at latch side of door.
Also, emergency lighting is required at exterior side of exit doors.
|
|
Bldg - Design occupant load 1004.1
2012 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section.
Action required: Update code analysis to depict educational type occupancy. Load calculates at 71.
9/12/16 - Occupancy Group shall be type E
|
|
|
Licensed Contractors
|
Approved
|
09/15/2016
|
09/15/2016
|
|
Joe Frogge
|
|
|
Licensed Contractors
|
Approved
|
09/12/2016
|
09/14/2016
|
|
Joe Frogge
|
|
LC - MEP Subs
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Electrical contractor.
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
|
|
|
Building Plan Review
|
Rejected
|
09/19/2016
|
09/14/2016
|
|
Joe Frogge
|
|
Gen - Submittal documents 7-137
Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri.
Action required: Provide detailed MEP designs or provide detailed scopes of work that include all methods and materials.
|
|
Misc
2012 IBC 2902.2 Separate Facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (see code for exceptions)
Action required: Restrooms to be labelled separately for each sex. Public shall have access to both restrooms.
|
|
Misc
Corrective Action Required
2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist:
1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2).
2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1.
3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits.
(see code section for exceptions)
Action required: Provide two exits from tenant space. Doors to swing in direction of travel. Provide exit lighting and panic hardware where appropriate. (note: if door 107 swings in direction of egress travel it would then violate 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances.)
9/12/16 - Door 107 will likely have to be removed in that it now violates 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances. i.e. 18" is required at latch side of door.
Also, emergency lighting is required at exterior side of exit doors.
|
|
Bldg - Design occupant load 1004.1
Corrective Action Required
2012 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section.
Action required: Update code analysis to depict educational type occupancy. Load calculates at 71.
9/12/16 - Occupancy Group shall be type E
|
|
|
Fire Plan Review
|
Approved with Conditions
|
09/19/2016
|
09/14/2016
|
|
Joe Dir
|
|
|
|
|
|
|
|
|
|
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 1184 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATION TO BE DONE TO THE FIRE SPRINKLER SYSTEM. All fire sprinkler system work shall be conducted by a certified sprinkler company.
all rooms within the suite shall have fire sprinkler coverage. Storage closet off the kitchen area appears to need coverage.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH REQUIRED ANNUAL MAINTENANCE/ SERVICE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SPRINKLER RISER.
(VERIFIED AT INSPECTION)
|
|
Misc
Corrective Action Required
Other previous review conditions have been addressed in the resub letter and or resub plans.
|
|
|
Zoning Review
|
Approved
|
08/31/2016
|
08/25/2016
|
|
Joe Frogge
|
|
approved per Hector Soto - email in file
|
Fire Plan Review
|
Rejected
|
08/31/2016
|
08/24/2016
|
|
Joe Dir
|
|
|
|
Misc
Corrective Action Required
UPDATE THE OCCUPANT LOAD FOR A EDUCATIONAL OCCUPANCY, whiCH WILL TAKE THE OCCUPANCY TO ABVE 50.
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 1184 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATION TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH REQUIRED ANNUAL MAINTENANCE/ SERVICE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SPRINKLER RISER.
(VERIFIED AT INSPECTION)
|
|
Misc
Corrective Action Required
B] 1008.1.2 Door swing.
Egress doors shall be of the pivoted or side-hinged swinging type.Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
PROVIDEA A MINUMUM OF ONE 2A-10BC FIRE EXTINGUISHER (RATED 5 POUND)
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
MOUNT THE FIRE EXTINGUISHER(S) ON A NORMAL PATH OF TRAVEL WITH A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANYWHERE WITHIN THE SUITE.
|
|
Misc
Corrective Action Required
PROVIDE MORE INFORMATION AS WHAT APPLIANCES WILL BE IN THE KITCHEN. IF A STOVE IS INSTALLED A LETTER STATING THAT IT WILL BE USED FOR WARMING OF FOOD ONLY. IF GREASE LADEN VAPORS WILL BE CREATED A TYPE 1 HOOD SYSTEM WILL BE REQUIRED.
|
|
|
Building Plan Review
|
Rejected
|
08/31/2016
|
08/24/2016
|
|
Joe Frogge
|
|
Bldg - Design occupant load 1004.1
Corrective Action Required
2012 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section.
Action required: Update code analysis to depict educational type occupancy. Load calculates at 71.
|
|
Misc
Corrective Action Required
2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist:
1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2).
2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1.
3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits.
(see code section for exceptions)
Action required: Provide two exits from tenant space. Doors to swing in direction of travel. Provide exit lighting and panic hardware where appropriate. (note: if door 107 swings in direction of egress travel it would then violate 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances.)
|
|
Misc
Corrective Action Required
2012 IBC 2902.2 Separate Facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (see code for exceptions)
Action required: Restrooms to be labelled separately for each sex. Public shall have access to both restrooms.
|
|
Gen - Submittal documents 7-137
Corrective Action Required
Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri.
Action required: Provide detailed MEP designs or provide detailed scopes of work that include all methods and materials.
|
|
|
Licensed Contractors
|
Rejected
|
08/31/2016
|
08/24/2016
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
|
|
LC - MEP Subs
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Electrical contractor.
|
|
|