Permit Application Status

PRCOM20162097


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20162097
Building Permit - Commercial
Certificate of Occupancy
RAVID LEE SUMMIT LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR LEARNING CENTER
08/19/2016
09/20/2016
03/13/2017
12/05/2016
Locations
Contacts
MID-WEST INTERIORS INC, Address:711 NE PILGRIM WAY, Phone:(816) 353-3100  
CHIEF HEATING & COOLING INC, Address:920 NW TECHNOLOGY DR, Phone:(816) 246-4646  
THREE DIAMOND ELECTRIC LLC, Address:27606 E PINK HILL RD, Phone:(816) 228-5470  
SCHOELLER PLUMBING INC, Address:PO BOX 1268, Phone:(816) 628-3848  
RAVID LEE SUMMIT LLC, Address:1901 HARRISON ST FL 2ND  
BNB DESIGNS ARCHITECTURE AND INTERIORS, Address:108 N NETTLETON AVE, Phone:(913) 422-5762  
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/06/2016
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/06/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXISTING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH ALL REQUIRED SERVICE / MAINTENANCE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SYSTEM RISER. (VERIFIED AT INSPECTION)
Fire Plan Review Approved with Conditions 09/22/2016 09/19/2016
Joe Dir
Construction documents for fire alarm systems
Corrective Action Required
09/15/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Address numbers required
Corrective Action Required
09/15/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1184 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
09/15/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATION TO BE DONE TO THE FIRE SPRINKLER SYSTEM. All fire sprinkler system work shall be conducted by a certified sprinkler company. all rooms within the suite shall have fire sprinkler coverage. Storage closet off the kitchen area appears to need coverage.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
09/15/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH REQUIRED ANNUAL MAINTENANCE/ SERVICE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SPRINKLER RISER. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
09/15/2016

Other previous review conditions have been addressed in the resub letter and or resub plans.
Alarm Plan Review Released for Construction 09/16/2016
Joe Dir
Misc
Corrective Action Required
09/16/2016

IFC 2012 MANUAL FIRE ALARM BOXES 2. Manual fire alarm boxes are not required in Group E occupancies where all of the following apply: 2.1. Interior corridors are protected by smoke detectors. 2.2. Auditoriums, cafeterias, gymnasiums and similar areas are protected by heat detectors or other approved detection devices. 2.3. Shops and laboratories involving dusts or vapors are protected by heat detectors or other approved detection devices. 3. Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, the emergency voice/alarm communication system will activate on sprinkler water flow and manual activation is provided from a normally occupied location. ADDTION OF A ANNUNCIATOR NOT REQUIRED DUE TO A ADDRESSABLE MONITORIED FIRE ALARM PANEL
Installation acceptance testing
Corrective Action Required
09/16/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACCEPTANCE TESTING OF THE NOTIFICATION AND ACTIVATION DEVICES WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Building Plan Review Approved 09/22/2016 09/15/2016
Joe Frogge
Misc
Resolved
09/15/2016

2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist: 1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2). 2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1. 3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits. (see code section for exceptions) Action required: Provide two exits from tenant space. Doors to swing in direction of travel. Provide exit lighting and panic hardware where appropriate. (note: if door 107 swings in direction of egress travel it would then violate 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances.) 9/12/16 - Door 107 will likely have to be removed in that it now violates 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances. i.e. 18" is required at latch side of door. Also, emergency lighting is required at exterior side of exit doors.
Bldg - Design occupant load 1004.1
Resolved
09/15/2016

2012 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section. Action required: Update code analysis to depict educational type occupancy. Load calculates at 71. 9/12/16 - Occupancy Group shall be type E
Licensed Contractors Approved 09/15/2016 09/15/2016
Joe Frogge
Licensed Contractors Approved 09/12/2016 09/14/2016
Joe Frogge
LC - MEP Subs
Resolved
09/14/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Electrical contractor.
LC - General Contractor
Resolved
09/14/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Building Plan Review Rejected 09/19/2016 09/14/2016
Joe Frogge
Gen - Submittal documents 7-137
Resolved
09/12/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Provide detailed MEP designs or provide detailed scopes of work that include all methods and materials.
Misc
Resolved
09/12/2016

2012 IBC 2902.2 Separate Facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (see code for exceptions) Action required: Restrooms to be labelled separately for each sex. Public shall have access to both restrooms.
Misc
Corrective Action Required
09/12/2016

2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist: 1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2). 2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1. 3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits. (see code section for exceptions) Action required: Provide two exits from tenant space. Doors to swing in direction of travel. Provide exit lighting and panic hardware where appropriate. (note: if door 107 swings in direction of egress travel it would then violate 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances.) 9/12/16 - Door 107 will likely have to be removed in that it now violates 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances. i.e. 18" is required at latch side of door. Also, emergency lighting is required at exterior side of exit doors.
Bldg - Design occupant load 1004.1
Corrective Action Required
09/12/2016

2012 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section. Action required: Update code analysis to depict educational type occupancy. Load calculates at 71. 9/12/16 - Occupancy Group shall be type E
Fire Plan Review Approved with Conditions 09/19/2016 09/14/2016
Joe Dir
09/14/2016

09/14/2016

09/14/2016

09/14/2016

09/14/2016

Construction documents for fire alarm systems
Corrective Action Required
09/12/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Address numbers required
Corrective Action Required
09/12/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1184 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
09/12/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATION TO BE DONE TO THE FIRE SPRINKLER SYSTEM. All fire sprinkler system work shall be conducted by a certified sprinkler company. all rooms within the suite shall have fire sprinkler coverage. Storage closet off the kitchen area appears to need coverage.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
09/12/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH REQUIRED ANNUAL MAINTENANCE/ SERVICE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SPRINKLER RISER. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
09/14/2016

Other previous review conditions have been addressed in the resub letter and or resub plans.
Zoning Review Approved 08/31/2016 08/25/2016
Joe Frogge
approved per Hector Soto - email in file
Fire Plan Review Rejected 08/31/2016 08/24/2016
Joe Dir
08/24/2016

Misc
Corrective Action Required
08/24/2016

UPDATE THE OCCUPANT LOAD FOR A EDUCATIONAL OCCUPANCY, whiCH WILL TAKE THE OCCUPANCY TO ABVE 50.
Construction documents for fire alarm systems
Corrective Action Required
08/24/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATIONS TO BE DONE TO THE FIRE ALARM SYSTEM.
Address numbers required
Corrective Action Required
08/24/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF 1184 ON THE EXTERIOR OF THE FRONT AND REAR DOORS IN A CONTRASTING COLOR READABLE FROM THE ROADWAY. (VERIFIED AT INSPECTION)
Construction documents - Fire protection systems
Corrective Action Required
08/24/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE CONTRACTOR PROVIDE SHOP DRAWINGS FOR ANY ALTERATION TO BE DONE TO THE FIRE SPRINKLER SYSTEM.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/24/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. THE EXSITING FIRE SPRINKLER SYSTEM SHALL BE CURRENT WITH REQUIRED ANNUAL MAINTENANCE/ SERVICE. A CURRENT SERVICE TAG SHALL BE POSTED ON THE SPRINKLER RISER. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
08/24/2016

B] 1008.1.2 Door swing. Egress doors shall be of the pivoted or side-hinged swinging type.Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Portable fire extinguishers - general
Corrective Action Required
08/24/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDEA A MINUMUM OF ONE 2A-10BC FIRE EXTINGUISHER (RATED 5 POUND)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/24/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHER(S) ON A NORMAL PATH OF TRAVEL WITH A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANYWHERE WITHIN THE SUITE.
Misc
Corrective Action Required
08/24/2016

PROVIDE MORE INFORMATION AS WHAT APPLIANCES WILL BE IN THE KITCHEN. IF A STOVE IS INSTALLED A LETTER STATING THAT IT WILL BE USED FOR WARMING OF FOOD ONLY. IF GREASE LADEN VAPORS WILL BE CREATED A TYPE 1 HOOD SYSTEM WILL BE REQUIRED.
Building Plan Review Rejected 08/31/2016 08/24/2016
Joe Frogge
Bldg - Design occupant load 1004.1
Corrective Action Required
08/24/2016

2012 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section. Action required: Update code analysis to depict educational type occupancy. Load calculates at 71.
Misc
Corrective Action Required
08/24/2016

2012 IBC 1021.2 Exits from stories. Two exits, or exit access stairways or ramps providing access to exist, from any story or occupied roof shall be provided where one of the following conditions exist: 1. The occupant load or number of dwelling units exceeds one of the values in Table 1021.2(1) or 1021.2(2). 2. The exit access travel distance exceeds that specified in Table 1021.2(1) or 1021.2(2) as determined in accordance with the provisions of Section 1016.1. 3. Helistop landing areas located on buildings or structures shall be provided with two exits, or exit access stairways or ramps providing access to exits. (see code section for exceptions) Action required: Provide two exits from tenant space. Doors to swing in direction of travel. Provide exit lighting and panic hardware where appropriate. (note: if door 107 swings in direction of egress travel it would then violate 2009 ICC/ANSI A117.1 Section 404.2.3 Maneuvering Clearances.)
Misc
Corrective Action Required
08/24/2016

2012 IBC 2902.2 Separate Facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (see code for exceptions) Action required: Restrooms to be labelled separately for each sex. Public shall have access to both restrooms.
Gen - Submittal documents 7-137
Corrective Action Required
08/24/2016

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Provide detailed MEP designs or provide detailed scopes of work that include all methods and materials.
Licensed Contractors Rejected 08/31/2016 08/24/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
08/24/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/24/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Electrical contractor.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $173.08 $173.08 Paid 09/20/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 9/27/2016 9/27/2016 09/27/2016
In-wall Inspection Passed 10/4/2016 10/4/2016 10/04/2016
Above Ceiling Inspection Failed 10/26/2016 10/26/2016 10/26/2016
Misc
Corrective Action Required
10/26/2016
COMPLETE REMOVAL OF ABANDONED HANGERS / BRACES
Misc
Corrective Action Required
10/26/2016
ELIMINATE UNUSED OPENINGS AND CONNECTORS AT ELECTRICAL J.B.'s
Misc
Corrective Action Required
10/26/2016
SECURE MC CABLE WITHIN 12" OF ENTRY TO J.B.'s EXCEPT FIXTURE WHIPS NO MORE THAN 6' LONG. SUPPORT MC CABLE AT MAX 6' INTERVALS.
Above Ceiling Inspection Passed 10/27/2016 10/27/2016 10/27/2016
Misc
Resolved
10/27/2016
COMPLETE REMOVAL OF ABANDONED HANGERS / BRACES
Misc
Resolved
10/27/2016
ELIMINATE UNUSED OPENINGS AND CONNECTORS AT ELECTRICAL J.B.'s
Misc
Resolved
10/27/2016
SECURE MC CABLE WITHIN 12" OF ENTRY TO J.B.'s EXCEPT FIXTURE WHIPS NO MORE THAN 6' LONG. SUPPORT MC CABLE AT MAX 6' INTERVALS.
Miscellaneous Inspection Passed 11/14/2016 11/14/2016
Occupancy Inspection - Codes Commercial Temporary C of O 11/15/2016 11/15/2016 11/15/2016
Misc
Corrective Action Required
11/15/2016
RESOLVE FIRE DEPT ISSUES
Occupancy Inspection - Fire Temporary C of O 11/15/2016 11/15/2016
Occupancy Inspection - Fire Passed 11/29/2016 11/29/2016
Occupancy Inspection - Codes Commercial Full C of O 12/5/2016 12/05/2016
Misc
Resolved
12/05/2016
RESOLVE FIRE DEPT ISSUES
Documents & Images
Date Uploaded File Type Document Name
08/24/2016 Letter Fire Building Plan Review
08/25/2016 Letter Codes P/R Corrections Document
09/14/2016 Letter Fire Building Plan Review
09/14/2016 Letter Codes P/R Corrections Document
09/16/2016 Letter Fire (Alarm) Plan Review Notice
09/19/2016 Letter Fire Building Plan Review
09/19/2016 Letter Codes Plan Review Conditions
09/20/2016 Receipt Receipt for transaction: 2016-006033
09/20/2016 Letter Codes Building Permit
09/27/2016 Letter Inspection Summary
10/04/2016 Letter Inspection Summary
10/06/2016 Letter Fire (Sprinkler) Plan Review
10/26/2016 Letter Inspection Summary
10/27/2016 Letter Inspection Summary
11/15/2016 Letter Codes Temporary Certificate of Occupancy
12/05/2016 Letter Field Certificate of Occupancy
12/06/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home