Permit Application Status

PRCOM20161193


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161193
Building Permit - Commercial
Certificate of Occupancy
RAVID LEE SUMMIT LLC
NEW TENANT FINISH
TENANT FINISH FOR RESTAURANT **plans are in plan review file
05/23/2016
07/26/2016
11/20/2016
08/19/2016
Locations
Contacts
RAVID LEE SUMMIT LLC, Address:1901 HARRISON ST FL 2ND  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
COMFORT SYSTEMS HTG/CLG, Address:17232 BEL-RAY PL, Phone:(816) 322-1013  
TRITON PLUMBING, Address:P O BOX 380038, Phone:(816) 522-6865  
NOEL WALLCOVERINGS, Address:8620 E 83RD , Phone:(913) 208-2866  
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/31/2016
Joe Dir
Sprinkler Plan Review Released for Construction 12/31/2016
Joe Dir
Licensed Contractors Approved 07/19/2016 07/26/2016
Joe Frogge
LC - MEP Subs
Resolved
07/26/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - General Contractor
Resolved
07/26/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
Fire Plan Review Approved with Conditions 07/26/2016 07/25/2016
Joe Dir
07/25/2016

IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/19/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action required: All existing fire protection equipment shall have documentation of current inspections. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
07/19/2016

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minmum of one 2A:10B:C fire extinguisher. Verified at inspection.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
07/19/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
07/19/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for modifications to the sprinkler system.
Posting of occupant load
Corrective Action Required
07/19/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inpection.
Building Plan Review Approved with Conditions 07/26/2016 07/22/2016
Joe Frogge
Health Dept Review
Resolved
07/19/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
07/19/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
07/19/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
07/22/2016

Installation of grease duct serving pizza oven. Action required: Provide detailed instructions that describes entirety of installation of duct that is acting as a chimney. Information to include, but is not limited to, clearances, wrap, cleanouts, type of steel, termination location, etc. Chimeny system to comply with 2012 IMC Chapter 8, 2011 NFPA 96, and 2016 NFPA 211. 7/20/16 - newest drawing submittal specifies use of a UL 737 chimney flue which is intended for residential use. Stove specifications call for a UL 103, Type HT listed chimney.
Health Department Review Approved 06/03/2016 07/19/2016
Joe Frogge
Building Plan Review Rejected 06/03/2016 05/24/2016
Joe Frogge
License Tax Application
Corrective Action Required
05/24/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
05/24/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
05/24/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Misc
Resolved
06/10/2016

2012 IPC 1003.1 Where required. Interceptors and separators shall be provided to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the public sewer, the private sewage system or the sewage treatment plant or processes. Action required: Provide grease trap. (reuse existing?) 6/9/16 - per architect, existing grease trap will be reused.
Misc
Resolved
06/10/2016

2012 IMC 507.2 Where Required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliance under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed. Exception: Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. 2012 IMC 202 General Definitions: EXTRA-HEAVY-DUTY COOKING APPLIANCE. Extra-heavy-duty cooking appliances include appliances utilizing solid fuel such as wood, charcoal, briquettes, and mesquite to provide all or part of the heat source for cooking. Action required: Provide complete design for Type I hood system or provide documentation from equipment manufacturer that certifies this equipment as exempt.
Misc
Corrective Action Required
06/10/2016

Installation of grease duct serving pizza oven. Action required: Provide detailed instructions that describes entirety of installation of duct that is acting as a chimney. Information to include, but is not limited to, clearances, wrap, cleanouts, type of steel, termination location, etc. Chimeny system to comply with 2012 IMC Chapter 8, 2011 NFPA 96, and 2016 NFPA 211.
Licensed Contractors Rejected 06/03/2016 05/24/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
05/24/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/24/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 06/03/2016 05/24/2016
Jim Eden
Misc
Resolved
06/10/2016

M] 609.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code. [M] 609.2 Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action required: Provide a detail/specifications for the pizza oven. Provide suppression as needed/required.
Posting of occupant load
Corrective Action Required
05/24/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inpection.
Construction documents - Fire protection systems
Corrective Action Required
05/24/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for modifications to the sprinkler system.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
05/24/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
05/24/2016

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minmum of one 2A:10B:C fire extinguisher. Verified at inspection.
Misc
Corrective Action Required
05/24/2016

Solid Fuel Cooking Operations The use of wood burning appliances shall be in accordance with NFPA 96, Chapter 14, including the storage of fuel and handling of ash. Action required: Provide specifications for the wood fired oven. Provide all the needed appurtenances for the use of solid fuel.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
05/24/2016

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action required: All existing fire protection equipment shall have documentation of current inspections. Verified at inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $87.92 $87.92 Paid 07/26/2016
8331507-Sewer Connection Fee $60.00 $60.00 Paid 07/26/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 7/29/2016 07/29/2016
Misc
Corrective Action Required
07/29/2016
SHORT WALLS ARE NOT STABLE. SEE NOTE (3).
In-wall Inspection Passed 8/2/2016 8/2/2016 08/02/2016
Misc
Resolved
08/02/2016
SHORT WALLS ARE NOT STABLE. SEE NOTE (3).
Above Ceiling Inspection Partial 8/12/2016 8/12/2016 08/12/2016
Misc
Corrective Action Required
08/12/2016
OK TO COVER ACT CEILING SYSTEM EXCEPT AT: - EXHAUST HOSES AT BOTH RR VENT FANS NOT CONNECTED - R.A. GRILLE LYING ABOVE CEILING IN KITCHEN OK TO COVER ELSEWHERE
Above Ceiling Inspection Passed 8/19/2016 08/19/2016
Misc
Resolved
08/19/2016
OK TO COVER ACT CEILING SYSTEM EXCEPT AT: - EXHAUST HOSES AT BOTH RR VENT FANS NOT CONNECTED - R.A. GRILLE LYING ABOVE CEILING IN KITCHEN OK TO COVER ELSEWHERE
Occupancy Inspection - Codes Commercial Full C of O 8/19/2016 8/19/2016 08/19/2016
Occupancy Inspection - Fire Passed 08/19/2016
Documents & Images
Date Uploaded File Type Document Name
05/24/2016 Letter Codes P/R Corrections Document
06/10/2016 Letter Codes P/R Corrections Document
06/10/2016 Letter Codes P/R Corrections Document
07/25/2016 Letter Fire Building Plan Review
07/26/2016 Letter Codes Plan Review Conditions
07/26/2016 Receipt Receipt for transaction: 2016-004964
07/26/2016 Letter Codes Building Permit
07/29/2016 Letter Inspection Summary
08/02/2016 Letter Inspection Summary
08/12/2016 Letter Inspection Summary
08/19/2016 Letter Field Certificate of Occupancy
08/22/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home