Permit Application Status

PRCOM20161177


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161177
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
NEW MULTI-FAMILY
BUILDING C -NEW 3 STORY INDEPENDENT LIVING UNIT
05/23/2016
11/21/2016
12/04/2016
12/15/2017
Locations
Contacts
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
GREEN FIELD ENERGY GROUP INC, Address:5 SW 4TH ST, Phone:(816) 524-5616  
TORGESON ELECTRIC CO INC, Address:3545 SW 6TH AVE, Phone:(785) 233-2213 Ext:101  
LMG CONSTRUCTION, Address:3011 ROANOKE RD, Phone:(816) 474-0333  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
SFCS ARCHITECTS, Address:1927 SOUTH TRYON ST, SUITE 207, Phone:(704) 372-7327  
KRUGER TECHNOLOGIES INC, Address:8271 MELROSE DR, Phone:(913) 498-1114  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 02/28/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
02/28/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Alarm Plan Review Released for Construction 12/31/2016
Joe Dir
Licensed Contractors Approved 06/23/2016 11/21/2016
Mike Weisenborn
LC - MEP Subs
Corrective Action Required
06/23/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Final Development Plan Review Approved 11/21/2016
Mike Weisenborn
Special Inspections Review Approved 10/14/2016
Joe Frogge
Fire Plan Review Approved with Conditions 08/26/2016
Joe Dir
Misc
Corrective Action Required
08/26/2016

DO NOT INSTALL STROBES (ALARM NOTIFICATION) IN THE STAIRWAYS
Construction documents for fire alarm systems
Corrective Action Required
08/26/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Knox box required
Corrective Action Required
08/26/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX FOR EACH BUILDING AND EACH ELEVATOR BANK. BOXES CAN BE OBTAINED ONLINE knox box.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
08/26/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
08/26/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING OF THE SPRINKLER, ALARM AND HOOD SUPRESSION SYSTEMS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
08/26/2016

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. THE MINIMUM SIZE FIRE EXTINGUISHER WILL BE (5POUND) 2A-10BC.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/26/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER WILL BE 75"
Misc
Corrective Action Required
08/26/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR LEVEL DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
08/26/2016

DOORS /HARDWARE [B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Misc
Corrective Action Required
08/26/2016

LABEL ALL DOORS TO SPRINKLER ROOMS, ELECTRICAL ROOMS, MECHANICAL ROOMS AND ELEVATOR ROOMS WITH THE ROOM DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
08/26/2016

ALL EXTERIOR HORN STROBE DEVICES SHALL BE LOCATED AT OR ABOVE THE FDCS (VERIFIED AT INSPECTION)
Fire Plan Review Rejected 06/27/2016 08/26/2016
Joe Dir
06/23/2016

06/23/2016

Misc
Corrective Action Required
06/23/2016

DO NOT INSTALL STROBES (ALARM NOTIFICATION) IN THE STAIRWAYS
Construction documents for fire alarm systems
Corrective Action Required
06/23/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Knox box required
Corrective Action Required
06/23/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX FOR EACH BUILDING AND EACH ELEVATOR BANK. BOXES CAN BE OBTAINED ONLINE knox box.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/23/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/23/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING OF THE SPRINKLER, ALARM AND HOOD SUPRESSION SYSTEMS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
06/23/2016

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. THE MINIMUM SIZE FIRE EXTINGUISHER WILL BE (5POUND) 2A-10BC.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/23/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER WILL BE 75"
Misc
Corrective Action Required
06/23/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR LEVEL DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/23/2016

DOORS /HARDWARE [B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Misc
Corrective Action Required
06/23/2016

LABEL ALL DOORS TO SPRINKLER ROOMS, ELECTRICAL ROOMS, MECHANICAL ROOMS AND ELEVATOR ROOMS WITH THE ROOM DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/23/2016

ALL EXTERIOR HORN STROBE DEVICES SHALL BE LOCATED AT OR ABOVE THE FDCS (VERIFIED AT INSPECTION)
Building Plan Review Rejected 06/30/2016 06/23/2016
Joe Frogge
License Tax Application
Corrective Action Required
06/23/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Final Development Plan
Corrective Action Required
06/23/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Resolved
10/14/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 6/23/16 - Not included in submittal
Elevator Certificate of Inspection
Corrective Action Required
06/23/2016

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Permit
Corrective Action Required
06/23/2016

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Inspection
Corrective Action Required
06/23/2016

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Resolved
06/23/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Resolved
06/23/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide blocking for future accessible features as noted in all Type B units.
Misc
Resolved
06/23/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Maintain minimum water closet clearance width at Type A units.
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.3.1.2.2.1 Clearance Width. Clearance around the water closet shall be 48 inches minimum in width, measured perpendicular from the side of the clearance that is 16 inches minimum and 18 inches maximum from the water closet centerline. Action required: Maintain minimum water closet clearance width at unit Type C.
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing facility, the shower compartment shall have dimensions of 36 inches minimum in width and 36 inches minimum in depth. A clearance of 48 inches minimum in length, measured perpendicular from the shower head wall, and 30 inches minimum in depth, measured from the face of the shower compartment, shall be provided. Reinforcing for a shower seat is not required in shower compartments larger than 36 inches in width and 36 inches in depth. Action required: Provide minimum shower compartment floor dimensions. Not compliant as scaled.
Misc
Resolved
06/23/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Miscellaneous Correction
Corrective Action Required
06/23/2016

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes. May be field verified. 6/23/16 - acknowledged in letter (field verify)
Engineered truss package
Resolved
06/23/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction. 6/23/16 - deferred
Screening - Ground mounted equipment
Resolved
06/23/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Miscellaneous Correction
Resolved
06/23/2016

2012 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: Modify drawings to show compliance. 6/23/16 - it has been decided to allow based upon complexity/quantity of loop vents, quantity of penetrations in fire rated horizontal assembly, and presence of maintenance staff.
Misc 12
Resolved
06/23/2016

20012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack. Action required: Modify drawings and/or diagrams to demonstrate compliance.
Misc 13
Resolved
06/23/2016

2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure. Action required: At rooms with large electrical equipment as defined above provide outswinging doors with panic hardware and emergency exit light.
Fire Plan Review Rejected 06/01/2016
Joe Dir
08/26/2016

Misc
Corrective Action Required
06/01/2016

NO STROBES (ALARM NOTIFICATION) IN THE STAIRWAYS
Construction documents for fire alarm systems
Corrective Action Required
06/01/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Access roads required for building and facilities
Corrective Action Required
06/01/2016

2012 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. PROVIDE DETAILS OF THE ACCESS ROADWAY AS PER PDP
Knox box required
Corrective Action Required
06/01/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX FOR EACH BUILDING AND EACH ELEVATOR BANK. BOXES CAN BE OBTAINED ONLINE knox box.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/01/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/01/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING OF THE SPRINKLER, ALARM AND HOOD SUPRESSION SYSTEMS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
06/01/2016

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. THE MINIMUM SIZE FIRE EXTINGUISHER WILL BE (5POUND) 2A-10BC.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/01/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER WILL BE 75" (VERIIFED AT INSPECTION
Misc
Corrective Action Required
06/01/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR LEVEL DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/01/2016

DOORS /HARDWARE [B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT.
Misc
Corrective Action Required
06/01/2016

LABEL ALL DOORS TO SPRINKLER ROOMS, ELECTRICAL ROOMS, MECHANICAL ROOMS AND ELEVATOR ROOMS WITH THE ROOM DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/01/2016

ALL EXTERIOR HORN STROBE DEVICES SHALL BE LOCATED TO OR ABOVE THE FDCS (VERIFIED AT INSPECTION)
Building Plan Review Rejected 05/27/2016
Joe Frogge
License Tax Application
Corrective Action Required
05/27/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
05/27/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/27/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Elevator Certificate of Inspection
Corrective Action Required
05/27/2016

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes.
Elevator Equipment Permit
Corrective Action Required
05/27/2016

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes.
Elevator Equipment Inspection
Corrective Action Required
05/27/2016

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes. Act
Misc
Corrective Action Required
05/27/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Corrective Action Required
05/27/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide blocking for future accessible features as noted in all Type B units.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Maintain minimum water closet clearance width at Type A units.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.3.1.2.2.1 Clearance Width. Clearance around the water closet shall be 48 inches minimum in width, measured perpendicular from the side of the clearance that is 16 inches minimum and 18 inches maximum from the water closet centerline. Action required: Maintain minimum water closet clearance width at unit Type C.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing facility, the shower compartment shall have dimensions of 36 inches minimum in width and 36 inches minimum in depth. A clearance of 48 inches minimum in length, measured perpendicular from the shower head wall, and 30 inches minimum in depth, measured from the face of the shower compartment, shall be provided. Reinforcing for a shower seat is not required in shower compartments larger than 36 inches in width and 36 inches in depth. Action required: Provide minimum shower compartment floor dimensions. Not compliant as scaled.
Misc
Corrective Action Required
05/27/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes. May be field verified.
Engineered truss package
Corrective Action Required
05/27/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction.
Screening - Ground mounted equipment
Corrective Action Required
05/27/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2012 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: Modify drawings to show compliance.
Misc 12
Corrective Action Required
05/27/2016

20012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack. Action required: Modify drawings and/or diagrams to demonstrate compliance.
Misc 13
Corrective Action Required
05/27/2016

2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure. Action required: At rooms with large electrical equipment as defined above provide outswinging doors with panic hardware and emergency exit light.
Licensed Contractors Rejected 05/23/2016 05/27/2016
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/27/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Multi-Family $23,085.70 $23,085.70 Paid 11/21/2016
8331507-Sewer Connection Fee $3,000.00 $3,000.00 Paid 11/21/2016
8331401-Water Tap Fee $21,427.00 $21,427.00 Paid 11/22/2016
8350015-Water Meter Fee $2,816.73 $2,816.73 Paid 11/22/2016
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 11/21/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 12/7/2016 (1:00) 12/7/2016 12/07/2016
Misc
Partial Correction
12/07/2016
OK TO POUR WHEN READY: ELEVATOR SUMP PIT SLAB
Footing Inspection - Commercial Partial 12/9/2016 12/09/2016
Misc
Partial Correction
12/09/2016
OK TO POUR WHEN READY: ELEVATOR SUMP PIT SLAB; ELEVATOR PIT SLAB;
Footing Inspection - Commercial Partial 12/13/2016 (8:00) 12/13/2016 12/13/2016
Misc
Partial Correction
12/09/2016
OK TO POUR WHEN READY: ELEVATOR SUMP PIT SLAB; ELEVATOR PIT SLAB;
Misc
Partial Correction
12/13/2016
DEEP FOOTINGS AT SOUTH ELEVATION
Concrete Walls and Columns Inspection Partial 12/16/2016 12/16/2016
Partial Correction
12/16/2016
OK TO POUR WHEN READY RETAINING WALL PER SECTION 7/S3.2
Footing Inspection - Commercial Not Ready 1/18/2017 (1:00) 1/18/2017 01/18/2017
Misc
Partial Correction
12/13/2016
OK TO POUR WHEN READY: ELEVATOR SUMP PIT SLAB; ELEVATOR PIT SLAB;
Misc
Partial Correction
12/13/2016
DEEP FOOTINGS AT SOUTH ELEVATION
Footing Inspection - Commercial Partial 1/19/2017 1/19/2017 01/19/2017
Misc
Resolved
01/19/2017
OK TO POUR WHEN READY: ELEVATOR SUMP PIT SLAB; ELEVATOR PIT SLAB;
Misc
Resolved
01/19/2017
DEEP FOOTINGS AT SOUTH ELEVATION
Misc
Corrective Action Required
01/19/2017
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS HAND-NUMBERED ON PERMIT PRINTS: FROM (1) C/W TO (2);
Footing Inspection - Commercial Partial 1/20/2017 (1:00) 1/20/2017 01/20/2017
Misc
Partial Correction
01/20/2017
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS HAND-NUMBERED ON PERMIT PRINTS: FROM (1) C/W TO (2); FROM (1) CC/W TO (5);
Footing Inspection - Commercial Partial 1/23/2017 (1:00) 1/23/2017 01/23/2017
Misc
Partial Correction
01/20/2017
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS HAND-NUMBERED ON PERMIT PRINTS: FROM (1) C/W TO (2); FROM (1) CC/W TO (3) TO (4), WITH UFER GROUND JUMPER IN PLACE AT NW WALL; TWO INTERIOR GRADE BEAMS INTERSECTING WALL ON LINE (1) TO (4)
Misc
Partial Correction
01/23/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS THROUGHOUT
Underslab Electrical Inspection - Commercial Partial 2/1/2017 02/01/2017
Misc
Partial Correction
02/01/2017
OK TO COVER WHEN READY PVC UNDER-SLAB ELECTRICAL CONDUIT: ONE 3" + ONE 1" FROM ELEVATOR EQUIPMENT ROOM TO MDP LOCATION; LOWER LIFT CONDUIT COMPLETE AT MDP LOCATION;
Concrete Walls and Columns Inspection Partial 2/1/2017 02/01/2017
Misc
Partial Correction
02/01/2017
OK TO POUR WHEN READY RETAINING WALL AT NORTH PER SECTION 6/S3.4;
Underslab Plumbing Inspection - Commercial Not Ready 2/2/2017 2/2/2017 02/02/2017
Misc
Corrective Action Required
02/02/2017
PIPING IN PROGRESS. NOT READY FOR INSPECTION.
Underslab Plumbing Inspection - Commercial Partial 2/3/2017 2/3/2017 02/03/2017
Misc
Partial Correction
02/03/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT NORTH WING. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Passed 2/6/2017 02/06/2017
Misc
Resolved
02/06/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT NORTH WING. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Electrical Inspection - Commercial Passed 2/9/2017 2/9/2017 02/09/2017
Misc
Resolved
02/09/2017
OK TO COVER WHEN READY: PVC UNDER-SLAB ELECTRICAL CONDUIT: ONE 3" + ONE 1" FROM ELEVATOR EQUIPMENT ROOM TO MDP LOCATION; LOWER LIFT CONDUIT COMPLETE AT MDP LOCATION; DEEP PIPE AT ELECTRICAL ROOM;
Footing Inspection - Commercial Partial 2/13/2017 (8:00) 2/13/2017 02/13/2017
Misc
Partial Correction
01/23/2017
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM BETWEEN POINTS HAND-NUMBERED ON PERMIT PRINTS: FROM (1) C/W TO (2); FROM (1) CC/W TO (3) TO (4), WITH UFER GROUND JUMPER IN PLACE AT NW WALL; TWO INTERIOR GRADE BEAMS INTERSECTING WALL ON LINE (1) TO (4); GRADE BEAMS CONNECTING COMMONS TO BLDG "C" (DESIGN MODIFIED TO CONSTUCT ALL GRADE BEAMS IN PLACE OF SOME FOOTINGS AND THICKENED SLABS)
Misc
Partial Correction
01/23/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS THROUGHOUT
Underslab Electrical Inspection - Commercial Passed 2/15/2017 02/15/2017
Electrical Service Inspection Partial 3/1/2017 3/1/2017 03/01/2017
Misc
Partial Correction
03/01/2017
RELEASE TEMPORARY ELECTRICAL SERVICE
Rough Framing Inspection - Commercial Partial 4/10/2017 4/10/2017 04/10/2017
B2304.6 Wall sheathing
Partial Correction
04/10/2017
OK TO COVER WHEN READY EXTERIOR WALL SHEATHING EXTERIOR FACE AT: 1ST LEVEL;
Rough Framing Inspection - Commercial Failed 5/15/2017 05/15/2017
B2304.6 Wall sheathing
Partial Correction
04/10/2017
OK TO COVER WHEN READY EXTERIOR WALL SHEATHING EXTERIOR FACE AT: 1ST LEVEL; NAILING AT 2ND LEVEL NOT APPROVED
Rough Framing Inspection - Commercial Partial 5/19/2017 05/19/2017
B2304.6 Wall sheathing
Partial Correction
05/15/2017
OK TO COVER WHEN READY EXTERIOR WALL SHEATHING EXTERIOR FACE AT: 1ST LEVEL; 2ND LEVEL;
All Rough Inspection - Commercial Partial 6/1/2017 6/1/2017 06/01/2017
Misc
Partial Correction
06/01/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SPACES: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 310; 312; 314; 317; 322; 403; 424;
Misc
Partial Correction
06/01/2017
OK TO COVER WHEN READY FRAMING OK WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205;
All Rough Inspection - Commercial Partial 6/6/2017 6/5/2017 06/05/2017
Misc
Partial Correction
06/01/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 310; 312; 314; 317; 322; 403; 424; [304; 305; 311; 315; 323; 324; [404; 405; 411; 415; 422; 423;
Misc
Partial Correction
06/01/2017
OK TO COVER WHEN READY FRAMING OK WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205;
All Rough Inspection - Commercial Partial 6/9/2017 6/6/2017 06/06/2017
Misc
Partial Correction
06/05/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 310; 312; 314; 317; 322; 403; 424; [304; 305; 311; 315; 323; 324; [404; 405; 411; 415; 422; 423;
Misc
Partial Correction
06/05/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211 AFTER TOP OF DEAD SPACE IS FIRE-BLOCKED; 212 EXCEPT FOR EAST WALL TO BE FIRE-BLOCKED;
Rough Framing Inspection - Commercial Failed 6/5/2017 6/7/2017 06/07/2017
B2304.6 Wall sheathing
Partial Correction
05/19/2017
OK TO COVER WHEN READY EXTERIOR WALL SHEATHING EXTERIOR FACE AT: 1ST LEVEL; 2ND LEVEL;
All Rough Inspection - Commercial Partial 6/8/2017 06/08/2017
Misc
Partial Correction
06/06/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/06/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212 EXCEPT FOR EAST WALL TO BE FIRE-BLOCKED;
Misc
Partial Correction
06/08/2017
OK TO INSTALL GWB CEILING AT CORRIDOR SPACES: 201; 216; 219; 221; 225;
All Rough Inspection - Commercial Partial 6/12/2017 6/12/2017 06/12/2017
Misc
Partial Correction
06/08/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/08/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; [215; 217; 222; 223; 224;
Misc
Partial Correction
06/08/2017
OK TO INSTALL GWB CEILING AT CORRIDOR SPACES: 201; 216; 219; 221; 225;
Rough Framing Inspection - Commercial Partial 6/13/2017 06/13/2017
B2304.6 Wall sheathing
Partial Correction
06/07/2017
OK TO COVER WHEN READY EXTERIOR WALL SHEATHING EXTERIOR FACE AT: 1ST LEVEL; 2ND LEVEL; RE-SCREWING OF 3RD LEVEL IN PROGRESS -- TO BE RE-INSPECTED
All Rough Inspection - Commercial Partial 6/13/2017 6/13/2017 06/13/2017
Misc
Partial Correction
06/12/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/12/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; 215; 217; 222; 223; 224; 214;
Misc
Partial Correction
06/12/2017
OK TO INSTALL GWB CEILING AT CORRIDOR SPACES: 201; 216; 219; 221; 225;
Rated Assembly Inspection Partial 6/1/2017 6/13/2017 06/13/2017
Misc
Partial Correction
06/13/2017
OK TO COVER WHEN READY PRE-ROCK GWB AT SHOWERS AT: 204; 205; 211; 212; 214; 215; 217; 222; 223; 224; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 404; 405; 411; 412; 414; 415; 417; 422; 423; 424;
Rough Framing Inspection - Commercial Partial 6/15/2017 06/15/2017
B2304.6 Wall sheathing
Partial Correction
06/13/2017
OK TO APPLY BUILDING WRAP WHEN READY TO EXTERIOR WALL SHEATHING AT: COMPLETE PERIMETER FULL HEIGHT
Rated Assembly Inspection Partial 6/16/2017 6/16/2017 06/16/2017
Misc
Partial Correction
06/13/2017
OK TO COVER WHEN READY PRE-ROCK GWB AT SHOWERS AT: 204; 205; 211; 212; 214; 215; 217; 222; 223; 224; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 404; 405; 411; 412; 414; 415; 417; 422; 423; 424;
Misc
Partial Correction
06/16/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AT: 201; 216; 219; 221;
Misc
Partial Correction
06/16/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214;
Misc
Partial Correction
06/16/2017
OK TO COVER WHEN READY FRAMING + SHAFT LINER BOARD AT STAIRWELLS -- WELL SIDE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314;
All Rough Inspection - Commercial Partial 6/16/2017 6/16/2017 06/16/2017
Misc
Partial Correction
06/13/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/13/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; 215; 217; 222; 223; 224; 214; [310; 312 EXCEPT MECH CLOSET(FIRE-BLOCKING); 311 NOT READY: CHECK & COMPLETE HOLD-DOWNS + FIRE-BLOCK AT MECH CLOSET
Misc
Partial Correction
06/13/2017
OK TO INSTALL GWB CEILING AT CORRIDOR SPACES: 201; 216; 219; 221; 225;
All Rough Inspection - Commercial Partial 6/19/2017 6/19/2017 06/19/2017
Misc
Partial Correction
06/16/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/16/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; 215; 217; 222; 223; 224; 214; 310; 311; 312;
Misc
Partial Correction
06/16/2017
OK TO INSTALL GWB CEILING AT CORRIDOR SPACES: 201; 216; 219; 221; 225;
Rated Assembly Inspection Partial 6/19/2017 6/19/2017 06/19/2017
Misc
Partial Correction
06/16/2017
OK TO COVER WHEN READY PRE-ROCK GWB AT SHOWERS AT: 204; 205; 211; 212; 214; 215; 217; 222; 223; 224; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 404; 405; 411; 412; 414; 415; 417; 422; 423; 424;
Misc
Partial Correction
06/16/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AT: 201; 216; 219; 221;
Misc
Partial Correction
06/16/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214;
Misc
Partial Correction
06/16/2017
OK TO COVER WHEN READY FRAMING + SHAFT LINER BOARD AT STAIRWELLS -- WELL SIDE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314;
Misc
Partial Correction
06/19/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: 204; 223; 224;
All Rough Inspection - Commercial Partial 6/20/2017 6/20/2017 06/20/2017
Misc
Partial Correction
06/19/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/19/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; 215; 217; 222; 223; 224; 214; 304; 310; 311; 312;
Misc
Partial Correction
06/19/2017
OK TO INSTALL GWB CEILING AT CORRIDOR SPACES: 201; 216; 219; 221; 225;
All Rough Inspection - Commercial Partial 6/21/2017 6/21/2017 06/21/2017
Misc
Partial Correction
06/20/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/20/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; 215; 217; 222; 223; 224; 214; 305; 310; 311; 312; [304; 314; 315; 317; 322; 323;
Misc
Partial Correction
06/20/2017
OK TO INSTALL GWB CEILING AT CORRIDOR SPACES: 201; 216; 219; 221; 225;
Misc
Partial Correction
06/21/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Rated Assembly Inspection Partial 6/21/2017 06/21/2017
Misc
Resolved
06/21/2017
OK TO COVER WHEN READY PRE-ROCK GWB AT SHOWERS AT: 204; 205; 211; 212; 214; 215; 217; 222; 223; 224; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 404; 405; 411; 412; 414; 415; 417; 422; 423; 424;
Misc
Partial Correction
06/19/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AT: 201; 216; 219; 221;
Misc
Partial Correction
06/19/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214;
Misc
Partial Correction
06/19/2017
OK TO COVER WHEN READY FRAMING + SHAFT LINER BOARD AT STAIRWELLS -- WELL SIDE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314;
Misc
Partial Correction
06/19/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: 204; 223; 224; [205; 211; 215; 217; 222;
Rated Assembly Inspection Partial 6/22/2017 06/22/2017
Misc
Partial Correction
06/21/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AT: 201; 216; 219; 221;
Misc
Partial Correction
06/21/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214;
Misc
Partial Correction
06/21/2017
OK TO COVER WHEN READY FRAMING + SHAFT LINER BOARD AT STAIRWELLS -- WELL SIDE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314;
Misc
Partial Correction
06/21/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: 204; 205; 211; 215; 217; 222;223; 224; [212; 214; [314 GWB ABOVE CEILING AT STAIRWELL WALL
All Rough Inspection - Commercial Partial 6/22/2017 6/22/2017 06/22/2017
Misc
Resolved
06/22/2017
OK TO PRE-ROCK DESIGNATED WALL SECTIONS AT SHOWERS AT: 203 SW; 206; 211; 212; 214; 215; 217; 222; 224; 303; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324; 403; 404; 405; 411; 415; 422; 423; 424;
Misc
Partial Correction
06/21/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; 214; 215; 217; 222; 223; 224; 214;[208; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; [324;
Misc
Partial Correction
06/21/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; 325;
Misc
Partial Correction
06/21/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
All Rough Inspection - Commercial Partial 6/26/2017 6/26/2017 06/26/2017
Misc
Partial Correction
06/22/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 211; 212; 214; 215; 217; 222; 223; 224; 214; [206; 207; 208; 304; 305; 310; 311; 312; 314; 315; 317; 322; 323; 324;[306; 307; 308; [412; 414;
Misc
Partial Correction
06/22/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; 325; [401; 416;
Misc
Partial Correction
06/22/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Rated Assembly Inspection Partial 6/28/2017 6/28/2017 06/28/2017
Misc
Partial Correction
06/22/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AT: 201; 216; 219; 221;
Misc
Partial Correction
06/22/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
06/22/2017
OK TO COVER WHEN READY FRAMING + SHAFT LINER BOARD AT STAIRWELLS -- WELL SIDE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314;
Misc
Partial Correction
06/22/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: 204; 205; 211; 212; 214; 215; 217; 222; 223; 224; [208; CORR 216; [310; 312;
All Rough Inspection - Commercial Partial 6/28/2017 6/28/2017 06/28/2017
Misc
Partial Correction
06/26/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 206; 207; 208; 211; 212; 214; 215; 217; 222; 223; 224; 214; [209 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 322; 323; 324; 412; 414; [411; 415;
Misc
Partial Correction
06/26/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; [ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
06/26/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
All Rough Inspection - Commercial Partial 6/29/2017 6/29/2017 06/29/2017
Misc
Partial Correction
06/28/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 222; 223; 224; 214; [218; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 322; 323; 324; 411; 412; 414; 415; [417;
Misc
Partial Correction
06/28/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; [ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
06/28/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Rated Assembly Inspection Partial 6/29/2017 6/29/2017 06/29/2017
Misc
Resolved
06/29/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AT: 201; 216; 219; 221;
Misc
Partial Correction
06/28/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
06/28/2017
OK TO COVER WHEN READY FRAMING + SHAFT LINER BOARD AT STAIRWELLS -- WELL SIDE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314;
Misc
Partial Correction
06/28/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 208; 211; 212; 214; 215; CORR 216; 217; 222; 223; 224; [206; 207; 209; CORR 219; 221; 310; 312;
All Rough Inspection - Commercial Partial 7/3/2017 7/3/2017 07/03/2017
Misc
Partial Correction
06/29/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 222; 223; 224; 214; [218; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 322; 323; 324; 411; 412; 414; 415; 417; [405; 423; 424;
Misc
Partial Correction
06/29/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; [ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
06/29/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
All Rough Inspection - Commercial Partial 7/5/2017 7/5/2017 07/05/2017
Misc
Partial Correction
07/03/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 322; 323; 324; 405; 411; 412; 414; 415; 417; 423; 424; [404 (OSB CROSS-WALL AT EAST TO BE COMPLETED);
Misc
Partial Correction
07/03/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; [ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/03/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Rated Assembly Inspection Partial 7/6/2017 7/6/2017 07/06/2017
Misc
Partial Correction
06/29/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
06/29/2017
OK TO COVER WHEN READY FRAMING + SHAFT LINER BOARD AT STAIRWELLS -- WELL SIDE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314;
Misc
Partial Correction
06/29/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219; 221; 222; 223; 224; [ 310; 312; [CORR 301/316/325; 304; 306; 307; 308; 309; 311; 314; 315; 317;
All Rough Inspection - Commercial Partial 7/6/2017 7/6/2017 07/06/2017
Misc
Partial Correction
07/05/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 322; 323; 324; [318; 418; STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 405; 411; 412; 414; 415; 417; 423; 424; [404 (OSB);
Misc
Partial Correction
07/05/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; [ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/05/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
All Rough Inspection - Commercial Partial 7/7/2017 7/7/2017 07/07/2017
Misc
Partial Correction
07/06/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 405; 411; 412; 414; 415; 417; 418; 423; 424; [404 INCLUDING OSB @ EAST WALL ABOVE; 407;
Misc
Partial Correction
07/06/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/06/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Rated Assembly Inspection Partial 7/7/2017 7/7/2017 07/07/2017
Misc
Partial Correction
07/06/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
07/06/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT INTERIOR WALLS AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE AT: 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Partial Correction
07/06/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219; 221; 222; 223; 224; [ CORR 301/316/325; 304; 306; 307; 308; 309; 310; 311; 312; 314; 315; 317; [305; 322; 323; 324;
All Rough Inspection - Commercial Partial 7/10/2017 7/10/2017 07/10/2017
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 404; 405; 407; 411; 412; 414; 415; 417; 418; 423; 424; [406; 409; 422;
Misc
Partial Correction
07/07/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Misc
Partial Correction
07/10/2017
RATED CHASE AT SW CORNER OF 203, 303, 403: OK TO INSTALL TWO LAYERS OF 5/8" TYPE X GWB AT ROOM FACE OF CORRIDOR WALL;
Rated Assembly Inspection Partial 7/11/2017 7/11/2017 07/11/2017
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT INTERIOR WALLS AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE AT: 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Partial Correction
07/07/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219; 221; 222; 223; 224; [218; CORR 301/316/325; 304; 306; 307; 308; 309;310; 311; 312; 314; 315; 317; [318;
Rough Framing Inspection - Commercial Partial 7/11/2017 07/11/2017
B2304.6 Wall sheathing
Resolved
07/11/2017
OK TO APPLY BUILDING WRAP WHEN READY TO EXTERIOR WALL SHEATHING AT: COMPLETE PERIMETER FULL HEIGHT
Misc
Partial Correction
07/11/2017
PREVIOUSLY UN-GROUTED TUBE COLUMN BASE PLATES NOW FOUND TO BE GROUTED -- TWO AT NW STAIR TOWER AND TWO AT SE STAIR TOWER
All Rough Inspection - Commercial Partial 7/13/2017 7/13/2017 07/13/2017
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 405; 411; 412; 414; 415; 417; 418; 423; 424; [404 INCLUDING OSB @ EAST WALL ABOVE; 407;
Misc
Partial Correction
07/07/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Misc
Corrective Action Required
07/13/2017
INSTALLATION OF IMPSON HTT4 TENSION TIES AT BALCONY LEDGERS / FOUND INSTALLED AT: 312; 314; 323; 324;
Sprinkler - Hydrostatic Test Passed 7/13/2017 07/13/2017
All Rough Inspection - Commercial Partial 7/14/2017 07/14/2017
Misc
Partial Correction
07/13/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 405; 411; 412; 414; 415; 417; 418; 423; 424; [404 INCLUDING OSB @ EAST WALL ABOVE; 407;
Misc
Partial Correction
07/13/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/13/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Misc
Partial Correction
07/14/2017
INSTALLATION OF IMPSON HTT4 TENSION TIES AT BALCONY LEDGERS / FOUND INSTALLED AT: 314; 322; 323; 324; [304; 305; 310; 311; 312; 315; 317;
Rated Assembly Inspection Partial 7/17/2017 7/17/2017 07/17/2017
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
07/07/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT INTERIOR WALLS AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: FRAMING + SHAFT LINER BOARD INCLUDING CLIPS AND FIRE-BLOCKING -- WELL FACE AT 4TH FLOOR 5/8" TYPE X GWB AT STAIRWELL FACE AT: 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Partial Correction
07/07/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219; 221; 222; 223; 224; CORR 301/316/325; 304; 305; 306; 307; 308; 309; 310; 311; 312; 314; 315; 317; 322; 323; 324; [CORRIDOR COMPLETE + ALL UNITS/ROOMS
All Rough Inspection - Commercial Partial 7/17/2017 07/17/2017
Misc
Partial Correction
07/14/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 405; 411; 412; 414; 415; 417; 418; 423; 424; [404 INCLUDING OSB @ EAST WALL ABOVE; 407; [408;
Misc
Partial Correction
07/14/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/14/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Misc
Partial Correction
07/14/2017
INSTALLATION OF IMPSON HTT4 TENSION TIES AT BALCONY LEDGERS / FOUND INSTALLED AT: 314; 322; 323; 324; [304; 305; 310; 311; 312; 315; 317;
Rated Assembly Inspection Partial 7/18/2017 07/18/2017
Misc
Partial Correction
07/17/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
07/17/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT INTERIOR WALLS AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: FRAMING + SHAFT LINER BOARD INCLUDING CLIPS AND FIRE-BLOCKING -- WELL FACE + OPPOSITE FACE AT 4TH FLOOR SE STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE WEST WALL ABOVE LID AT 4TH FLR; 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Partial Correction
07/17/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219; 221; 222; 223; 224; CORR 301/316/325; 304; 305; 306; 307; 308; 309; 310; 311; 312; 314; 315; 317; 322; 323; 324; [4TH FLOOR CORRIDOR COMPLETE + ALL UNITS/ROOMS INCLUDING 408
Rated Assembly Inspection Partial 7/20/2017 07/20/2017
Misc
Resolved
07/20/2017
OK TO COVER WHEN READY 5/8" TYPE X GWB AT UNIT FACE OF STAIRWELL WALLS AT: 214; 314 GWB ABOVE CEILING ONLY
Misc
Partial Correction
07/18/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT INTERIOR WALLS AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: FRAMING + SHAFT LINER BOARD INCLUDING CLIPS AND FIRE-BLOCKING -- WELL FACE + OPPOSITE FACE AT 3RD FLOOR (303); [AT 4TH FLOOR (402) COMPLETE TO ROOF SE STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE WEST WALL ABOVE LID AT 4TH FLR; 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Partial Correction
07/18/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219; 221; 222; 223; 224; CORR 301/316/325; 304; 305; 306; 307; 308; 309; 310; 311; 312; 314; 315; 317; 322; 323; 324; 4TH FLOOR CORRIDOR COMPLETE + ALL UNITS/ROOMS INCLUDING 408
Misc
Partial Correction
07/20/2017
DUCT CHASE AT 303 SW CORNER: TWO LAYERS 5/8" TYOE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE, LEAVING OPENING FOR INSPECTION BEFORE COMPLETELY CLOSING CHASE. DUCT CHASE AT 306 SW CORNER: SIMILAR TO 303 ABOVE.
Rated Assembly Inspection Partial 7/21/2017 07/21/2017
Misc
Partial Correction
07/20/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT INTERIOR WALLS AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: FRAMING + SHAFT LINER BOARD INCLUDING CLIPS AND FIRE-BLOCKING -- WELL FACE + OPPOSITE FACE AT 3RD FLOOR (303); AT 4TH FLOOR (402) WELL FACE GWB COMPLETE TO ROOF; OPPOSITE FACE AT 2ND FLR (203) OK FOR 5/8" TYPE X; SE STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE WEST WALL ABOVE LID AT 4TH FLR; 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Partial Correction
07/20/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219 INCLUDING SOFFIT TO ENCLOSE ELECT CABLES; 221; 222; 223; 224; CORR 301/316/325; 304; 305; 306; 307; 308; 309; 310; 311; 312; 314; 315; 317; 322; 323; 324; 4TH FLOOR CORRIDOR COMPLETE + ALL UNITS/ROOMS INCLUDING 408
Misc
Partial Correction
07/20/2017
DUCT CHASE AT 303 SW CORNER: TWO LAYERS 5/8" TYOE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE, LEAVING OPENING FOR INSPECTION BEFORE COMPLETELY CLOSING CHASE. DUCT CHASE AT 306 SW CORNER: SIMILAR TO 303 ABOVE.
All Rough Inspection - Commercial Partial 7/24/2017 7/24/2017 07/24/2017
Misc
Partial Correction
07/17/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 103 EXCEPT ANCHORAGE OF EXTERIOR WALL SILL PLATE TO BE CHECKED AND COMPLETED PER DRWGS; ROOF STRUCTURE AT 101 & 104 -- ADD TRUSS HANGERS; STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 405; 411; 412; 414; 415; 417; 418; 423; 424; [404 INCLUDING OSB @ EAST WALL ABOVE; 407; [408;
Misc
Partial Correction
07/17/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/17/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Misc
Partial Correction
07/17/2017
INSTALLATION OF IMPSON HTT4 TENSION TIES AT BALCONY LEDGERS / FOUND INSTALLED AT: 314; 322; 323; 324; [304; 305; 310; 311; 312; 315; 317;
Rated Assembly Inspection Partial 7/26/2017 07/26/2017
Misc
Partial Correction
07/21/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: FRAMING + SHAFT LINER BOARD INCLUDING CLIPS AND FIRE-BLOCKING -- WELL FACE + OPPOSITE FACE AT 3RD FLOOR (303); AT 4TH FLOOR (402) WELL FACE GWB COMPLETE TO ROOF; OPPOSITE FACE AT 2ND FLR (203) OK FOR 5/8" TYPE X; [5/8" TYPE X OK TO TAPE, MUD AND FIRE-STOP AT 402 UP TO ROOF; OPPOSITE FACE AT 403 OK TO HANG 5/8" TYPE X; SE STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE WEST WALL ABOVE LID AT 4TH FLR; 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Resolved
07/26/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB CEILINGS AND WALLS AT: CEILING ONLY AT 201; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; CORR 216; 217; CORR 219 INCLUDING SOFFIT TO ENCLOSE ELECT CABLES; 221; 222; 223; 224; CORR 301/316/325; 304; 305; 306; 307; 308; 309; 310; 311; 312; 314; 315; 317; 322; 323; 324; 4TH FLOOR CORRIDOR COMPLETE + ALL UNITS/ROOMS INCLUDING 408
Misc
Partial Correction
07/21/2017
DUCT CHASE AT 303 SW CORNER: TWO LAYERS 5/8" TYOE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE, LEAVING OPENING FOR INSPECTION BEFORE COMPLETELY CLOSING CHASE. DUCT CHASE AT 306 SW CORNER: SIMILAR TO 303 ABOVE.
Rated Assembly Inspection Partial 7/27/2017 7/27/2017 07/27/2017
Misc
Partial Correction
07/26/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: FRAMING + SHAFT LINER BOARD -- WELL FACE + UNIT SIDE AT: 102; 202; 203; 213; 302; 303; 313; 314; WEST STAIRWELL: FRAMING + SHAFT LINER BOARD INCLUDING CLIPS AND FIRE-BLOCKING -- WELL FACE + OPPOSITE FACE AT 3RD FLOOR (303); AT 4TH FLOOR (402) WELL FACE GWB COMPLETE TO ROOF; OPPOSITE FACE AT 2ND FLR (203) OK FOR 5/8" TYPE X; [5/8" TYPE X OK TO TAPE, MUD AND FIRE-STOP AT 402 UP TO ROOF; OPPOSITE FACE AT 403 OK TO HANG 5/8" TYPE X; SE STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE WEST WALL ABOVE LID AT 4TH FLR; 5/8" TYPE X GWB AT BACK FACE AT: WALLS ABOVE 4TH FLR CEILING AT ATTIC;
Misc
Partial Correction
07/26/2017
DUCT CHASE AT 303 SW CORNER: TWO LAYERS 5/8" TYOE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE, LEAVING OPENING FOR INSPECTION BEFORE COMPLETELY CLOSING CHASE. DUCT CHASE AT 306 SW CORNER: SIMILAR TO 303 ABOVE.
Misc
Partial Correction
07/27/2017
[OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB AT WALLS AND CEILING IN 203 & 303
Electrical Service Inspection Passed 7/24/2017 7/27/2017 07/27/2017
Misc
Resolved
07/27/2017
RELEASE TEMPORARY ELECTRICAL SERVICE
Rough Electrical Inspection - Commercial Partial 7/28/2017 07/28/2017
Misc
Partial Correction
07/28/2017
MAKE-UP OF ELECTRICAL GEAR
Rated Assembly Inspection Partial 7/28/2017 7/28/2017 07/28/2017
Misc
Partial Correction
07/27/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: NORTHWEST STAIRWELL & SOUTHEAST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE OK TO TAPE, MUD, AND FIRE-STOP.
Misc
Partial Correction
07/27/2017
DUCT CHASE AT 303 SW CORNER: TWO LAYERS 5/8" TYOE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE, LEAVING OPENING FOR INSPECTION BEFORE COMPLETELY CLOSING CHASE. DUCT CHASE AT 306 SW CORNER: SIMILAR TO 303 ABOVE.
Misc
Partial Correction
07/27/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB AT WALLS AND CEILING IN: 203; 303; [103; 403; STAIRWELL 202/302/402 AND 213/313/413;
Gas Piping Inspection - Commercial Partial 7/28/2017 07/28/2017
Misc
Partial Correction
07/28/2017
NATURAL GAS FEEDER PIPE TRENCHED FROM MOORE ST / HOPE LN SW TO BUILDING ENTRY AT SOUTH ELEVATION. TRENCH DEPTH ~ 28"; TRACER WIRE IN PLACE. PRESURE TEST TO BE WITNESSED SUSEQUENTLY.
Gas Piping Inspection - Commercial Partial 8/1/2017 08/01/2017
Misc
Partial Correction
07/28/2017
NATURAL GAS FEEDER PIPE TRENCHED FROM MOORE ST / HOPE LN SW TO BUILDING ENTRY AT SOUTH ELEVATION. TRENCH DEPTH ~ 28"; TRACER WIRE IN PLACE. 8/1/17 PRESURE TEST HELD STEADY AT 100 PSI FOR 60 MINUTES.
Above Ceiling Inspection Not Ready 8/1/2017 8/1/2017 08/01/2017
Above Ceiling Inspection Not Ready 8/2/2017 8/2/2017 08/02/2017
Above Ceiling Inspection Partial 8/3/2017 8/3/2017 08/03/2017
Misc
Partial Correction
08/03/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4TH FLOOR: CORRIDOR 401/416 EXCEPT ELEVATOR LOBBY AFTER ALL TENSION STUDS ARE SCREWED BOTH FLANGES; 418;
Above Ceiling Inspection Partial 8/4/2017 08/04/2017
Misc
Partial Correction
08/03/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4TH FLOOR: CORRIDOR 401/416 EXCEPT ELEVATOR LOBBY; 418; CORRIDOR 301/316 EXCEPT ELEVATOR LOBBY; 318; CORRIDOR 201/216 EXCEPT ELEVATOR LOBBY;
Gas Piping Inspection - Commercial Partial 8/4/2017 08/04/2017
Misc
Partial Correction
08/01/2017
NATURAL GAS FEEDER PIPE TRENCHED FROM MOORE ST / HOPE LN SW TO BUILDING ENTRY AT SOUTH ELEVATION. TRENCH DEPTH ~ 28"; TRACER WIRE IN PLACE. 8/1/17 PRESURE TEST HELD STEADY AT 100 PSI FOR 60 MINUTES. 8/4/17 PRESURE TEST OF INTERIOR PIPING HELD STEADY AT 29 PSI FOR >10 MINUTES.
Rated Assembly Inspection Partial 8/4/2017 08/04/2017
Misc
Partial Correction
07/28/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: NORTHWEST STAIRWELL & SOUTHEAST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE OK TO TAPE, MUD, AND FIRE-STOP; [INCLUDING 1ST FLOOR LEVEL AT NW STAIR
Misc
Partial Correction
07/28/2017
DUCT CHASE AT 303 SW CORNER: TWO LAYERS 5/8" TYOE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE, LEAVING OPENING FOR INSPECTION BEFORE COMPLETELY CLOSING CHASE. DUCT CHASE AT 306 SW CORNER: SIMILAR TO 303 ABOVE.
Misc
Partial Correction
07/28/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB AT WALLS AND CEILING IN: 203; 303; [103; 403; STAIRWELL 202/302/402 AND 213/313/413;
Rated Assembly Inspection Partial 8/9/2017 8/9/2017 08/09/2017
Misc
Partial Correction
08/04/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: NORTHWEST STAIRWELL & SOUTHEAST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE OK TO TAPE, MUD, AND FIRE-STOP; 1ST FLOOR LEVEL AT NW STAIR
Misc
Partial Correction
08/04/2017
DUCT CHASE AT 303/403 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE, THEN APPLY ONE LAYER 5/8" TYPE X GWB; DUCT CHASE AT 306/406 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE, THEN APPLY ONE LAYER 5/8" TYPE X GWB;
Misc
Partial Correction
08/04/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB AT WALLS AND CEILING IN: 203; 303; [103; 403; STAIRWELL 202/302/402 AND 213/313/413;
Rated Assembly Inspection Partial 8/11/2017 08/11/2017
Misc
Partial Correction
08/09/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: NORTHWEST STAIRWELL & SOUTHEAST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE OK TO TAPE, MUD, AND FIRE-STOP; 1ST FLOOR LEVEL AT NW STAIR
Misc
Partial Correction
08/09/2017
DUCT CHASE AT 303/403 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-STOP DUCT CHASE AT 306/406 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-STOP
Misc
Partial Correction
08/09/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB AT WALLS AND CEILING IN: 203; 303; [103; 403; STAIRWELL 202/302/402 AND 213/313/413;
All Rough Inspection - Commercial Not Ready 7/26/2017 8/14/2017 08/14/2017
Misc
Partial Correction
07/24/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 103 EXCEPT ANCHORAGE OF EXTERIOR WALL SILL PLATE TO BE CHECKED AND COMPLETED PER DRWGS; ROOF STRUCTURE AT 101 & 104 -- ADD TRUSS HANGERS; STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 405; 411; 412; 414; 415; 417; 418; 423; 424; [404 INCLUDING OSB @ EAST WALL ABOVE; 407; [408;
Misc
Partial Correction
07/24/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Partial Correction
07/24/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Misc
Partial Correction
07/24/2017
INSTALLATION OF IMPSON HTT4 TENSION TIES AT BALCONY LEDGERS / FOUND INSTALLED AT: 314; 322; 323; 324; [304; 305; 310; 311; 312; 315; 317;
Rated Assembly Inspection Partial 8/14/2017 8/15/2017 at 10:25 AM 08/15/2017
Misc
Partial Correction
08/11/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: NORTHWEST STAIRWELL & SOUTHEAST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE OK TO TAPE, MUD, AND FIRE-STOP; 1ST FLOOR LEVEL AT NW STAIR
Misc
Partial Correction
08/11/2017
DUCT CHASE AT 303/403 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-STOP DUCT CHASE AT 306/406 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-STOP
Misc
Partial Correction
08/11/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB AT WALLS AND CEILING IN: 203; 303; 103; 403; STAIRWELL 202/302/402 AND 213/313/413; [CORR 104;
All Rough Inspection - Commercial Partial 8/24/2017 at 3:45 PM 08/24/2017
Misc
Resolved
08/24/2017
OK TO COVER WHEN READY FRAMING OF WALLS AND CEILINGS + SYSTEMS TO BE ENCLOSED AT SPACES: 103 EXCEPT ANCHORAGE OF EXTERIOR WALL SILL PLATE TO BE CHECKED AND COMPLETED PER DRWGS; ROOF STRUCTURE AT 101 & 104 -- ADD TRUSS HANGERS; STAIRWELLS COMPLETE 102/202/302 & 213/313/413; 204; 205; 206; 207; 208; 209; 211; 212; 214; 215; 217; 218; 222; 223; 224; 304; 305; 306; 307; 308; 310; 311; 312; 314; 315; 317; 318; 322; 323; 324; 405; 411; 412; 414; 415; 417; 418; 423; 424; [404 INCLUDING OSB @ EAST WALL ABOVE; 407; [408;
Misc
Resolved
08/24/2017
OK TO INSTALL GWB CEILING AND WALLS AT CORRIDOR SPACES: 201; 216; 219; 221; 225; 301; 316; 324; ELEVATOR LOBBY 325; 401; 416;
Misc
Resolved
08/24/2017
OK TO COVER WHEN READY WALL FRAMING & IN-WALL SYSTEMS AT ELEVATOR LOBBIES AT: 2ND FLR; 3RD FLR;
Misc
Resolved
08/24/2017
INSTALLATION OF IMPSON HTT4 TENSION TIES AT BALCONY LEDGERS / FOUND INSTALLED AT: 314; 322; 323; 324; [304; 305; 310; 311; 312; 315; 317;
Misc
Partial Correction
08/24/2017
ELEVATOR LID: OK TO APPLY 1ST LAYER 5/8" TYPE X GWB;
All Rough Inspection - Commercial Partial 8/25/2017 at 7:20 AM 08/25/2017
Misc
Partial Correction
08/24/2017
ELEVATOR LID: OK TO APPLY 1ST LAYER 5/8" TYPE X GWB;
Misc
Partial Correction
08/25/2017
OK TO COVER WHEN READY CEILING AND WALL FRAMING & ENCLOSED SYSTEMS AT LINK CORRIDOR 103
All Rough Inspection - Commercial Partial 9/1/2017 at 2:40 PM 09/01/2017
Misc
Resolved
09/01/2017
ELEVATOR LID: OK TO APPLY 1ST LAYER 5/8" TYPE X GWB;
Misc
Resolved
09/01/2017
OK TO COVER WHEN READY CEILING AND WALL FRAMING & ENCLOSED SYSTEMS AT LINK CORRIDOR 103
Misc
Partial Correction
09/01/2017
OK TO COVER WHEN READY FRAMING AND SYSTEMS TO BE CONCEALED AT SOFFITS AT ELEVATOR LOBBIES
Rated Assembly Inspection Partial 9/1/2017 9/1/2017 at 3:10 PM 09/01/2017
Misc
Resolved
09/01/2017
OK TO COVER WHEN READY RATED ASSEMBLIES AT STAIRWELLS: NORTHWEST STAIRWELL & SOUTHEAST STAIRWELL: 5/8" TYPE X GWB AT STAIRWELL FACE OK TO TAPE, MUD, AND FIRE-STOP; 1ST FLOOR LEVEL AT NW STAIR
Misc
Resolved
09/01/2017
DUCT CHASE AT 303/403 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-STOP DUCT CHASE AT 306/406 SW CORNER: TWO LAYERS 5/8" TYPE X GWB AT CORRIDOR WALL -- OK TO TAPE & MUD, THEN TO INSTALL DUCT, THEN TO INSTALL PART OF SHAFT LINER ENCLOSURE; DUCT & FRAMING OK TO COMPLETE SHAFT LINER ENCLOSURE; TWO LAYERS 5/8" TYPE X GWB OK TO TAPE, MUD, AND FIRE-STOP
Misc
Resolved
09/01/2017
OK TO TAPE, MUD AND FIRE-STOP 5/8" TYPE X GWB AT WALLS AND CEILING IN: 203; 303; 103; 403; STAIRWELL 202/302/402 AND 213/313/413; [CORR 104;
Misc
Partial Correction
09/01/2017
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT LID OF ELEVATOR SHAFT: FRAMING AND SHAFT LINER BOARD;
Miscellaneous Inspection Partial 9/1/2017 at 3:30 PM 09/01/2017
Misc
Partial Correction
09/01/2017
PRE-FINAL INSPECTION/TEST OF REFRIGERATOR AND DISHWASHER ELECTRICAL RECEPTACLES AT LOCATIONS: 2ND FLOOR; 3RD FLOOR; OK TO SET AND PLUG IN APPLIANCES WHEN READY.
Rated Assembly Inspection Partial 9/6/2017 9/6/2017 at 11:10 AM 09/06/2017
Misc
Partial Correction
09/01/2017
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT LID OF ELEVATOR SHAFT: FRAMING AND SHAFT LINER BOARD; 1ST LAYER 5/8" TYPE X GWB;
Rated Assembly Inspection Partial 9/7/2017 9/7/2017 at 10:25 AM 09/07/2017
Misc
Partial Correction
09/06/2017
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLY AT LID OF ELEVATOR SHAFT: FRAMING AND SHAFT LINER BOARD; 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X GWB;
Misc
Partial Correction
09/07/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT: WALLS AT LINK 101/104
Above Ceiling Inspection Partial 9/13/2017 9/13/2017 at 9:40 AM 09/13/2017
Misc
Partial Correction
08/04/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4TH FLOOR: CORRIDOR 401/416 EXCEPT ELEVATOR LOBBY; 418; CORRIDOR 301/316 EXCEPT ELEVATOR LOBBY; 318; CORRIDOR 201/216 EXCEPT ELEVATOR LOBBY;
Misc
Partial Correction
09/13/2017
OK TO PLACE ACT CUT BORDER TILE LESS THAN 2' ONLY AT: 4TH, 3RD, 2ND FLOORS;
Above Ceiling Inspection Partial 9/22/2017 9/25/2017 at 8:45 AM 09/25/2017
Misc
Partial Correction
09/13/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4TH FLOOR: CORRIDOR 401/416 EXCEPT ELEVATOR LOBBY; 418; CORRIDOR 301/316 EXCEPT ELEVATOR LOBBY; 318; CORRIDOR 201/216 EXCEPT ELEVATOR LOBBY; CORR 101;
Misc
Partial Correction
09/13/2017
OK TO PLACE ACT CUT BORDER TILE LESS THAN 2' ONLY AT: CORRIDORS @ 4TH, 3RD, 2ND FLOORS;
Above Ceiling Inspection Partial 9/28/2017 at 1:30 PM 09/28/2017
Misc
Partial Correction
09/28/2017
SPACE ABOVE DROP-CEILING: 2ND AND 3RD FLOOR CORRIDOR-OK
Above Ceiling Inspection Partial 10/2/2017 10/2/2017 at 2:45 PM 10/02/2017
Misc
Partial Correction
09/25/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 4TH FLOOR: CORRIDOR 401/416 EXCEPT ELEVATOR LOBBY; 418; CORRIDOR 301/316 EXCEPT ELEVATOR LOBBY; 318; CORRIDOR 201/216 EXCEPT ELEVATOR LOBBY; CORR 104;
Misc
Partial Correction
09/25/2017
OK TO PLACE ACT CUT BORDER TILE LESS THAN 2' ONLY AT: CORRIDORS @ 4TH, 3RD, 2ND FLOORS; SPACE ABOVE DROP-CEILING: 2ND, 3RD, AND 4TH FLOOR CORRIDORS; RM 318 & 418
Alarm Test Passed 10/3/2017 10/03/2017
Sprinkler - Flow Test Passed 10/3/2017 10/03/2017
Occupancy Inspection - Fire Temporary C of O 10/4/2017 10/04/2017
Occupancy Inspection - Codes Commercial Temporary C of O 10/3/2017 10/4/2017 at 2:00 PM 10/04/2017
Misc
Corrective Action Required
10/03/2017
-APPROVAL FROM THE FOLLOWING DEPT. REQUIRED: FIRE, DEV. ENGINEERING, PLANNING, WATER, 3RD PARTY SPECIAL INSPECTION, ELEVATOR INSPECTION -JOHN BORN TO CLEAR ALL INSPECTIONS NOT APPROVED -COMPLETE ALL EXTERIOR -BOTTOM EXIT LEVEL NOT READY FOR INSPECTION. COMPLETE ABOVE-CEILING, HANDRAILS FOR RAMP, ETC -WINDOW GLAZING ADJACENT TO RAMP AND WITHIN 60" OF RAMP WALKING SURFACE SHALL BE SAFETY TEMPERED GLAZING -INSTALL STAIR ENCLOSURE DOORS GLAZING -LOOP UP AND SECURE DISH WASHER DRAINS -INSTALL SECURITY STRIKE PLATES FOR ALL GRADE LEVEL EXTERIOR DOORS -FIRECAULK DUCT PENETRATION OF CEILING IN ALL MECHANICAL CLOSETS 1019: GFCI IN BATHROOM NOT TRIPPING 1020: INSTALL GRAB BARS IN ACCESSIBLE TOILET RM; OPEN BOX IN MECHANICAL CLOSET 1056: FIRECAULK SE CABLES CEILING PENETRATIONS 1011: OPEN ELECTRICAL BOX IN MECHANICAL CLOSET 2010: INSTALL LIGHT ABOVE SHOWER; INSTALL SPRINKLER HEAD AT OUTDOOR PATIO 2013: LOOSE SPRINKLER HEAD IN MECHANICAL CLOSET. FIRECAULK CEILING 2056: PROVIDE PANEL BREAKERS SCHEDULE 2054: REMOUNT CEILING ELECTRICAL BOX; CLOSE ALL OPEN ELECTRICAL BOXES 2015: NAIL JOIST HANGERS ABOVE PATIO 3019: SWITCHBOX AT MECHANICAL CLOSET DOOR-WIRING EXPOSED TO COMBUSTIBLE 3018: FIX ARC FAULT FOR BEDROOM AFCI BREAKER TRIPPING 3056: PANEL BREAKERS LABELING ATTIC SPACE: DRAFT WALL NOT COMPLETED. PROVIDE DRAFTSTOP DIVIDE PER PLAN; PROVIDE SELF-CLOSING ATTIC ACCESS TO ALL ROOF SPACE; PROVIDE WALKING SURFACE PER CODE TO ALL MECHANICAL UNIT; PROVIDE RECEPTACLES WITHIN 25 FT OF ALL MECHNICAL UNITS; COMPLETE WIRING TO ALL ROOF VENTING UNITS; SECURELY FASTEN ALL NM CABLES WITHIN 8" OF BOX AND AT INTERVAL NO LONGER THAN 4.5 FT; TAKE TRASH OUT
Foundation Inspection - Commercial Passed 10/6/2017 at 7:00 AM 10/06/2017
Above Ceiling Inspection Partial 10/6/2017 10/6/2017 at 7:30 AM 10/06/2017
Misc
Partial Correction
10/02/2017
SPACE ABOVE DROP-CEILING: 2ND AND 3RD FLOOR CORRIDOR-OK D101;104
Occupancy Inspection - Engineering Passed 10/11/2017 10/11/2017
Miscellaneous Inspection Partial 10/11/2017 10/11/2017 at 9:00 AM 10/11/2017
Occupancy Inspection - Codes Commercial Partial 10/13/2017 10/13/2017 at 7:10 AM 10/13/2017
Misc
Corrective Action Required
10/04/2017
-APPROVAL FROM THE FOLLOWING DEPT. REQUIRED: FIRE, DEV. ENGINEERING, PLANNING, WATER, 3RD PARTY SPECIAL INSPECTION, ELEVATOR INSPECTION
Misc
Corrective Action Required
10/13/2017
- COMPLETE ALL FINISH SITEWORK INCLUDING HANDRAILS AT STEPS AT SW
Misc
Corrective Action Required
10/13/2017
- BOTTOM EXIT LEVEL: HANDRAILS FOR RAMP - GLAZING AT HAZARDOUS LOCATIONS? - LOOP UP AND SECURE DISH WASHER DRAINS - FIRECAULK DUCT PENETRATION OF CEILING IN ALL MECHANICAL CLOSETS
Misc
Corrective Action Required
10/13/2017
1056: LABELING OF BREAKER/SWITCH POSITIONS 2010: INSTALL PERMANENT SPRINKLER HEAD AT OUTDOOR PATIO; SEAL PENETRATION 2056: LABELING OF BREAKER/SWITCH POSITIONS 2015: NAIL JOIST HANGERS ABOVE PATIO 3056: LABELING OF BREAKER/SWITCH POSITIONS
Misc
Corrective Action Required
10/13/2017
ATTIC SPACE: DRAFT WALL NOT COMPLETED. PROVIDE DRAFTSTOP DIVIDE PER PLAN; PROVIDE SELF-CLOSING ATTIC ACCESS TO ALL ROOF SPACE; PROVIDE WALKING SURFACE PER CODE TO ALL MECHANICAL UNIT; PROVIDE RECEPTACLES WITHIN 25 FT OF ALL MECHNICAL UNITS; COMPLETE WIRING TO ALL ROOF VENTING UNITS; SECURELY FASTEN ALL NM CABLES WITHIN 8" OF BOX AND AT INTERVAL NO LONGER THAN 4.5 FT; TAKE TRASH OUT
Occupancy Inspection - Fire Passed 10/24/2017 10/24/2017
Occupancy Inspection - Water Utilities Passed 10/12/2017 10/25/2017
Occupancy Inspection - Codes Commercial Partial 10/25/2017 10/25/2017 at 1:20 PM 10/25/2017
Misc
Corrective Action Required
10/13/2017
-APPROVAL FROM THE FOLLOWING DEPT. REQUIRED: ELEVATOR INSPECTION
Misc
Corrective Action Required
10/13/2017
- COMPLETE ALL FINISH SITEWORK INCLUDING HANDRAILS AT STEPS AT SW
Misc
Corrective Action Required
10/13/2017
2010: INSTALL PERMANENT SPRINKLER HEAD AT OUTDOOR PATIO; SEAL PENETRATION
Misc
Resolved
10/25/2017
- BOTTOM EXIT LEVEL: HANDRAILS FOR RAMP - GLAZING AT HAZARDOUS LOCATIONS? - LOOP UP AND SECURE DISH WASHER DRAINS - FIRECAULK DUCT PENETRATION OF CEILING IN ALL MECHANICAL CLOSETS
Misc
Corrective Action Required
10/25/2017
ATTIC: - SEAL OPENINGS IN DRAFTSTOP WALLS - INSULATION TO BE FULL 12"
Occupancy Inspection - Codes Commercial Temporary C of O 11/15/2017 at 3:40 PM 11/15/2017
Misc
Corrective Action Required
10/13/2017
-APPROVAL FROM THE FOLLOWING DEPT. REQUIRED: DEV. ENGINEERING PLANNING
Misc
Resolved
11/15/2017
- COMPLETE ALL FINISH SITEWORK INCLUDING HANDRAILS AT STEPS AT SW
Misc
Resolved
11/15/2017
1056: LABELING OF BREAKER/SWITCH POSITIONS 2010: INSTALL PERMANENT SPRINKLER HEAD AT OUTDOOR PATIO; SEAL PENETRATION 2056: LABELING OF BREAKER/SWITCH POSITIONS 2015: NAIL JOIST HANGERS ABOVE PATIO 3056: LABELING OF BREAKER/SWITCH POSITIONS
Misc
Resolved
11/15/2017
- BOTTOM EXIT LEVEL: HANDRAILS FOR RAMP - GLAZING AT HAZARDOUS LOCATIONS? - LOOP UP AND SECURE DISH WASHER DRAINS - FIRECAULK DUCT PENETRATION OF CEILING IN ALL MECHANICAL CLOSETS
Misc
Resolved
11/15/2017
ATTIC SPACE: DRAFT WALL NOT COMPLETED. PROVIDE DRAFTSTOP DIVIDE PER PLAN; PROVIDE SELF-CLOSING ATTIC ACCESS TO ALL ROOF SPACE; PROVIDE WALKING SURFACE PER CODE TO ALL MECHANICAL UNIT; PROVIDE RECEPTACLES WITHIN 25 FT OF ALL MECHNICAL UNITS; COMPLETE WIRING TO ALL ROOF VENTING UNITS; SECURELY FASTEN ALL NM CABLES WITHIN 8" OF BOX AND AT INTERVAL NO LONGER THAN 4.5 FT; TAKE TRASH OUT
Occupancy Inspection - Planning Temporary C of O 11/22/2017
Corrective Action Required
11/22/2017
Landscaping shall be completed per the approved plans. Shrubs appear to be all in. However, planting of trees is not complete.
Occupancy Inspection - Codes Commercial Full C of O 12/15/2017 12/15/2017
Misc
Resolved
12/15/2017
-APPROVAL FROM THE FOLLOWING DEPT. REQUIRED: DEV. ENGINEERING PLANNING
Documents & Images
Date Uploaded File Type Document Name
06/01/2016 Letter Fire Building Plan Review
06/03/2016 Letter Codes P/R Corrections Document
06/23/2016 Letter Fire Building Plan Review
08/26/2016 Letter Fire Building Plan Review
11/21/2016 Receipt Receipt for transaction: 2016-006901
11/21/2016 Letter Codes Building Permit
11/21/2016 Letter Codes Plan Review Conditions
11/22/2016 Receipt Receipt for transaction: 2016-006927
12/07/2016 Letter Inspection Summary
12/09/2016 Letter Inspection Summary
12/13/2016 Letter Inspection Summary
12/16/2016 Letter Inspection Summary
01/18/2017 Letter Inspection Summary
01/19/2017 Letter Inspection Summary
01/20/2017 Letter Inspection Summary
01/23/2017 Letter Inspection Summary
02/02/2017 Letter Inspection Summary
02/03/2017 Letter Inspection Summary
02/06/2017 Letter Inspection Summary
02/09/2017 Letter Inspection Summary
02/13/2017 Letter Inspection Summary
02/15/2017 Letter Inspection Summary
02/28/2017 Letter Fire (Sprinkler) Plan Review
03/01/2017 Letter Inspection Summary
04/10/2017 Letter Inspection Summary
05/19/2017 Letter Inspection Summary
06/01/2017 Letter Inspection Summary
06/05/2017 Letter Inspection Summary
06/06/2017 Letter Inspection Summary
06/08/2017 Letter Inspection Summary
06/12/2017 Letter Inspection Summary
06/13/2017 Letter Inspection Summary
06/15/2017 Letter Inspection Summary
06/16/2017 Letter Inspection Summary
06/19/2017 Letter Inspection Summary
06/20/2017 Letter Inspection Summary
06/21/2017 Letter Inspection Summary
06/22/2017 Letter Inspection Summary
06/26/2017 Letter Inspection Summary
06/28/2017 Letter Inspection Summary
06/29/2017 Letter Inspection Summary
07/03/2017 Letter Inspection Summary
07/05/2017 Letter Inspection Summary
07/06/2017 Letter Inspection Summary
07/07/2017 Letter Inspection Summary
07/10/2017 Letter Inspection Summary
07/11/2017 Letter Inspection Summary
07/13/2017 Letter Inspection Summary
07/14/2017 Letter Inspection Summary
07/17/2017 Letter Inspection Summary
07/18/2017 Letter Inspection Summary
07/20/2017 Letter Inspection Summary
07/21/2017 Letter Inspection Summary
07/24/2017 Letter Inspection Summary
07/26/2017 Letter Inspection Summary
07/27/2017 Letter Inspection Summary
07/28/2017 Letter Inspection Summary
07/28/2017 Letter Inspection Summary
07/28/2017 Letter Inspection Summary
08/01/2017 Letter Inspection Summary
08/03/2017 Letter Inspection Summary
08/04/2017 Letter Inspection Summary
08/09/2017 Letter Inspection Summary
08/11/2017 Letter Inspection Summary
08/15/2017 Letter Inspection Summary
08/24/2017 Letter Inspection Summary
08/25/2017 Letter Inspection Summary
09/01/2017 Letter Inspection Summary
09/06/2017 Letter Inspection Summary
09/07/2017 Letter Inspection Summary
09/13/2017 Letter Inspection Summary
09/25/2017 Letter Inspection Summary
09/28/2017 Letter Inspection Summary
10/02/2017 Letter Inspection Summary
10/04/2017 Letter Codes Temporary Certificate of Occupancy
10/06/2017 Letter Inspection Summary
10/13/2017 Letter Inspection Summary
10/25/2017 Letter Inspection Summary
11/15/2017 Letter Codes Temporary Certificate of Occupancy
12/15/2017 Letter Field Certificate of Occupancy
12/19/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home