Review Type |
Outcome |
Est. Completion Date |
Completed |
Health Department Review
|
Approved
|
02/23/2016
|
04/12/2016
|
|
Development Center
|
|
|
Building Plan Review
|
Approved with Conditions
|
04/11/2016
|
04/11/2016
|
|
Joe Frogge
|
|
Gen - Submittal documents 7-137
Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in three (3) sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri.
Action required: Provide complete MEP designs prepared and sealed by MO State design professional. Information to include, but not be limited to-- Gas piping, Wire and Circuitry information, Grease ducts, Plumbing material schedule, piping diagrams, etc
3/28/16 - Provide plumbing material schedule. Provide verification that replacement rooftop HVAC equipment is equal or less weight than original. If heavier provide letter from structural engineer stating that existing structure is sufficient or provide design to strengthen roof.
4/11/16 - drawings updated
|
|
Misc
2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface.
Action required: Clarify on drawings.
3/28/16 - Unable to locate information on drawings.
4/11/16 - covered by adding a note
|
|
Bldg - Occupant load posting 1004.3
Corrective Action Required
2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Comment is for informational purposes. (to be verified at occupancy)
3/28/16 - acknowledged in letter
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
3/28/16 - acknowledged in letter
|
|
Health Dept Review
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
3/28/16 - acknowledged in letter
|
|
|
Licensed Contractors
|
Approved
|
04/04/2016
|
04/11/2016
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
04/11/2016
|
04/06/2016
|
|
Joe Dir
|
|
Posting of occupant load
Corrective Action Required
2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
ONLY ONE OCCUPANT LOAD SIGN NEEDED, POST THE SIGN BY THE MAIN ENTRANCE
(VERIFIED AT INSPECTION)
|
|
Misc
Corrective Action Required
ALL OTHER PREVIOUS CONDITIONS WERE ADDRESSED IN LETTER.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
03/30/2016
|
03/29/2016
|
|
Joe Dir
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Posting of occupant load
Corrective Action Required
2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
ONLY ONE OCCUPANT LOAD SIGN NEEDED, POST THE SIGN BY THE MAIN ENTRANCE
(VERIFIED AT INSPECTION)
(VERIFIED AT INSPECTION)
|
|
Misc
Corrective Action Required
ALL OTHER PREVIOUS CONDITIONS WERE ADDRESSED IN LETTER.
|
|
|
Building Plan Review
|
Rejected
|
03/30/2016
|
03/29/2016
|
|
Joe Frogge
|
|
Gen - Submittal documents 7-137
Corrective Action Required
Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in three (3) sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri.
Action required: Provide complete MEP designs prepared and sealed by MO State design professional. Information to include, but not be limited to-- Gas piping, Wire and Circuitry information, Grease ducts, Plumbing material schedule, piping diagrams, etc
3/28/16 - Provide plumbing material schedule. Provide verification that replacement rooftop HVAC equipment is equal or less weight than original. If heavier provide letter from structural engineer stating that existing structure is sufficient or provide design to strengthen roof.
|
|
Misc
Corrective Action Required
2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface.
Action required: Clarify on drawings.
3/28/16 - Unable to locate information on drawings.
|
|
Bldg - Occupant load posting 1004.3
Corrective Action Required
2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Comment is for informational purposes. (to be verified at occupancy)
3/28/16 - acknowledged in letter
|
|
Bldg - Door swing 1008.1.2
2012 IBC 1008.1.2 – Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for possible exceptions.) Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Action required: Modify drawings. Door #100 must swing outward.
3/28/16 - drawings revised to comply
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
3/28/16 - acknowledged in letter
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
3/28/16 - acknowledged in letter
|
|
|
Licensed Contractors
|
Approved
|
03/23/2016
|
03/28/2016
|
|
Joe Frogge
|
|
LC - MEP Subs
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
(contractors listed on application do not have current licenses)
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
(the request to waive Class B requirements was denied)
|
|
|
Building Plan Review
|
Rejected
|
02/23/2016
|
02/16/2016
|
|
Joe Frogge
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Bldg - Door swing 1008.1.2
Corrective Action Required
2012 IBC 1008.1.2 – Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for possible exceptions.) Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Action required: Modify drawings. Door #100 must swing outward.
|
|
Bldg - Occupant load posting 1004.3
Corrective Action Required
2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Comment is for informational purposes. (to be verified at occupancy)
|
|
Misc
Corrective Action Required
2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface.
Action required: Clarify on drawings.
|
|
Gen - Submittal documents 7-137
Corrective Action Required
Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in three (3) sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri.
Action required: Provide complete MEP designs prepared and sealed by MO State design professional. Information to include, but not be limited to-- Gas piping, Wire and Circuitry information, Grease ducts, Plumbing material schedule, piping diagrams, etc
|
|
|
Licensed Contractors
|
Rejected
|
02/23/2016
|
02/16/2016
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
(the request to waive Class B requirements was denied)
|
|
LC - MEP Subs
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
(contractors listed on application do not have current licenses)
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/23/2016
|
02/12/2016
|
|
Joe Dir
|
|
Misc
Corrective Action Required
THE EXSISTING HOOD SHALL BE CURRENT WITH ALL OF THE SERVICING & MAINTINANCE REQUIRED FOR A TYPE-1 HOOD AND SUPRESSION SYSTEM.
(INFOMATION PURPOSES) (VERIFED AT INSPECTION)
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
PROVIDE THE SPECS ON THE TYPE-1 SUPRESSION HOOD SYSTEM AND HOOD.
(INFROMATION PURPOSES)
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACCEPTANCE TESTING SHALL BE REQUIRED FOR THE NEW HOOD. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
PROVIDE RATED (5POUND) 2A-10BC FIRE EXTINGUISHERS IF NOT ALREADY EXSISTING. EXSISTING FIRE EXTINGUISHERS SHALL BE CURRENT WITH ANY REQUIRED MAINTINANCE AOR SERVICE. VERFIED AT INSPECTION
|
|
Posting of occupant load
Corrective Action Required
2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
POST THE OCCUPANT LOAD AS FIGURED ON THE PLANS. POST SIGNAGE ON THE INTERIOR CLOSE TO THE MAIN ENTRANCE. VERIFIED AT INSPECTION.
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
IF NOT EXSISTING POST THE NUMERIC ADDRESS ON THE BUILDING READABLE FROM THE ROADWAY.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
PROVIDE A K CLASS FIRE EXTINGUISHER FOR EACH HOOD. VERIFIED AT INSPECTION.
|
|
Misc
Corrective Action Required
EACH KITCHEN HOOD AND REMOTE EMERGENCY PULL SHALL BE ADDRESSED SEPERATELY WITH EITHER NUMERIC OR ALBETIC DESIGNATIONS. VERIFIED AT INSPECTION.
|
|
|