Fire Plan Review
|
Approved with Conditions
|
12/30/2015
|
12/30/2015
|
|
Jim Eden
|
|
Address numbers required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 5050 ON THE EXTERIOR OF THE BUILDING, READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
TESTING WILL BE REQUIRED FOR ANY EMERGENCY PUMP SHUT OFF DEVICES RELOACTED AND OR REPLACED. INFORMATION PURPOSES.
|
|
Misc
PLANS DON'T SHOW LOCATION OF FIRE EXTINGUISHERS ON INTERIOR OR EXTERIOR.
(ADDRESSED IN RE-SUBMITTAL)
|
|
|
Licensed Contractors
|
Approved
|
11/23/2015
|
12/01/2015
|
|
Development Center
|
|
LC - MEP Subs
Corrective Action Required
MEP Subs:
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Health Department Review
|
Approved
|
05/10/2016
|
11/30/2015
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
12/02/2015
|
11/25/2015
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 5050 ON THE EXTERIOR OF THE BUILDING, READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
TESTING WILL BE REQUIRED FOR ANY EMERGENCY PUMP SHUT OFF DEVICES RELOACTED AND OR REPLACED. INFORMATION PURPOSES.
|
|
Misc
PLANS DON'T SHOW THE LOCATION OF THE EMERGENCY PUMP SHUT OFF SWITCHES ON THE INTERIOR OR EXTERIOR. lOCATIONS TO BE DETERMINED LATER BY SUB CONTRACTOR
|
|
Misc
Corrective Action Required
PLANS DON'T SHOW LOCATION OF FIRE EXTINGUISHERS ON INTERIOR OR EXTERIOR.
(ADDRESSED IN RE-SUBMITTAL)
|
|
|
Building Plan Review
|
Approved with Conditions
|
12/02/2015
|
11/24/2015
|
|
Joe Frogge
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Health Dept Review
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
|
Building Plan Review
|
Rejected
|
11/20/2015
|
11/12/2015
|
|
Joe Frogge
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
|
Licensed Contractors
|
Rejected
|
11/20/2015
|
11/12/2015
|
|
Joe Frogge
|
|
LC - MEP Subs
Corrective Action Required
MEP Subs:
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Fire Plan Review
|
Rejected
|
11/20/2015
|
11/12/2015
|
|
Joe Dir
|
|
Misc
Corrective Action Required
NO INFORMATION ADVISING IF STORE IS TO REMAIN OPEN DURING THE REFIT PROCESS. IF STORE IS TO REMAIN OPEN, ALL EMERGENCY PUMP SHUT OFF SWITCHES ARE TO REAMIN IN OPERATION. FIRE EXTINGUISHER TO REMAIN AVAILABLE
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 5050 ON THE EXTERIOR OF THE BUILDING, READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
TESTING WILL BE REQUIRED FOR ANY EMERGENCY PUMP SHUT OFF DEVICES RELOACTED AND OR REPLACED. INFORMATION PURPOSES.
|
|
Misc
Corrective Action Required
PLANS DON'T SHOW THE LOCATION OF THE EMERGENCY PUMP SHUT OFF SWITCHES ON THE INTERIOR OR EXTERIOR.
|
|
Misc
Corrective Action Required
PLANS DON'T SHOW LOCATION OF FIRE EXTINGUISHERS ON INTERIOR OR EXTERIOR.
|
|
Misc
Corrective Action Required
NO INFORMATION STATING IF THE STORE WILL BE A ATTENDED 24 HOUR STORE OR A UNATTENDED 24 HOUR STORE.
|
|
|