Permit Application Status

PRCOM20143105


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20143105
Building Permit - Commercial
Certificate of Occupancy
LBP V LLC
NEW TENANT FINISH
TENANT FINISH FOR NEW OFFICE/WAREHOUSE
11/04/2014
03/11/2015
10/02/2015
Locations
Contacts
CAPITAL CONSTRUCTION SERVICES LLC, Address:2642 NE HAGAN RD, Phone:(816) 875-0018  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
BLUE SPRINGS ELECTRICAL SERVICE, Address:3402 LAKE SHORE DR, Phone:(816) 224-9911  
CLEARLINE PLUMBING LLC, Address:14922 KNORPP RD, Phone:(816) 524-4449  
LBP V LLC, Address:3215 NE CARNEGIE DR STE 200, Phone:(816) 795-8100  
DAVIDSON ARCHITECTURE & ENGINEERING - PAUL MILLER, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/10/2015 07/10/2015
Joe Dir
07/10/2015

IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/10/2015

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Hydrosattic testing and acceptance flow testing required, call 816-969-1300 to schedule a test.
Sprinkler Plan Review Released for Construction 11/14/2014 04/30/2015
Brian Austerman
Misc
Corrective Action Required
04/30/2015

Plan review for adding in rack sprinklers
Misc
Corrective Action Required
04/30/2015

Modifications to existing systems involving 20 or more heads requires a hydrostatic test, call (816) 969-1300 to schedule
Building Plan Review Approved with Conditions 11/14/2014 11/10/2014
Joe Frogge
Misc
Corrective Action Required
11/10/2014

Shell building is currently under construction. Action required: Comment for informational purposes. No type of occupancy may be granted until permit for shell building is completed.
Fire Plan Review Approved with Conditions 11/14/2014 11/10/2014
Brian Austerman
Misc
Corrective Action Required
11/10/2014

Rack storage shall comply with Chapter 57 of the International Fire Code. For information only. Provide a storage plan for the use of the warehouse
Construction documents for fire alarm systems
Corrective Action Required
11/10/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Address numbers required
Corrective Action Required
11/10/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on front and rear doors
Fire protection equipment identification
Corrective Action Required
11/10/2014

2012 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Rooms containing fire sprinkler riser, fan controls, electrical service etc shall be marked
Construction documents - Fire protection systems
Corrective Action Required
11/10/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Portable fire extinguishers - general
Corrective Action Required
11/10/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide 5lb ABC type extinguishers
Licensed Contractors Approved 11/14/2014 11/04/2014
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $2,463.52 $2,463.52 Paid 03/11/2015
8331506-EFHB Maybrook, Full $894.81 $894.81 Paid 03/11/2015
8331507-Sewer Connection Fee $630.00 $630.00 Paid 03/11/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 3/12/2015 3/12/2015 at 12:00 AM 03/12/2015
PLUMBING
Corrective Action Required
03/12/2015
THE FOLLOWING U.P. ARE OK: -2 RESTROOMS&DRINKING FOUNTAINS; BREAK RM SINKS; SOUTH SINK
Underslab Electrical Inspection - Commercial Passed 3/16/2015 3/16/2015 at 12:00 AM 03/16/2015
In-wall Inspection Partial 3/23/2015 at 12:00 AM 03/23/2015
Misc
Corrective Action Required
03/23/2015
IN-WALL OK TO ROCK EXCEPT AT RESTROOMS, PRIVATE, AND JANITOR RMS
In-wall Inspection Passed 3/26/2015 3/26/2015 at 12:00 AM 03/26/2015
Misc
Resolved
03/26/2015
IN-WALL OK TO ROCK EXCEPT AT RESTROOMS, PRIVATE, AND JANITOR RMS; ALL SPACES AS OF 3/26
Underslab Plumbing Inspection - Commercial Partial 3/27/2015 at 12:00 AM 03/27/2015
PLUMBING
Corrective Action Required
03/12/2015
THE FOLLOWING U.P. ARE OK: -2 RESTROOMS&DRINKING FOUNTAINS; BREAK RM SINKS; SOUTH SINK -FLOOR DRAIN AND SINK BY SW OF BUILING
In-wall Inspection Partial 3/26/2015 4/6/2015 at 12:00 AM 04/06/2015
Misc
Partial Correction
04/06/2015
TENANT OFFICE SPACE IN-WALL-OK TO ROCK
In-wall Inspection Partial 4/10/2015 4/10/2015 at 12:00 AM 04/10/2015
Misc
Partial Correction
04/06/2015
TENANT OFFICE SPACE IN-WALL-OK TO ROCK **SPACE AT SW CORNER OF BUILDING: PROTECT PVC AND SUPPORT 3" PIPE AT MID-WALL
Underslab Plumbing Inspection - Commercial Passed 4/20/2015 4/20/2015 at 12:00 AM 04/10/2015
PLUMBING
Resolved
04/10/2015
THE FOLLOWING U.P. ARE OK: -2 RESTROOMS&DRINKING FOUNTAINS; BREAK RM SINKS; SOUTH SINK -FLOOR DRAIN AND SINK BY SW OF BUILING
Electrical Service Inspection Passed 4/10/2015 at 12:00 AM 04/10/2015
Above Ceiling Inspection Partial 4/16/2015 (8:00 to 5:00) 4/16/2015 at 12:00 AM 04/16/2015
Misc
Corrective Action Required
04/16/2015
ABOVE-CEILING OK BELOW: -SOUTH BIG ROOM AND TWO OFFICES
In-wall Inspection Passed 04/16/2015
Misc
Resolved
04/16/2015
TENANT OFFICE SPACE IN-WALL-OK TO ROCK **SPACE AT SW CORNER OF BUILDING: PROTECT PVC AND SUPPORT 3" PIPE AT MID-WALL
Above Ceiling Inspection Partial 4/20/2015 4/20/2015 at 12:00 AM 04/20/2015
Misc
Corrective Action Required
04/16/2015
ABOVE-CEILING OK BELOW: -SOUTH BIG ROOM AND TWO OFFICES **SUPPORT MC AT MAXIMUM 6FT INTERVAL
Underslab Plumbing Inspection - Commercial Passed 4/20/2015 at 12:00 AM 04/20/2015
Above Ceiling Inspection Partial 4/21/2015 at 12:00 AM 04/21/2015
Misc
Corrective Action Required
04/20/2015
ABOVE-CEILING OK BELOW: -SOUTH BIG ROOM AND TWO OFFICES **SUPPORT MC AT MAXIMUM 6FT INTERVAL AT NW ROOM
Above Ceiling Inspection Passed 4/22/2015 at 12:00 AM 04/22/2015
Misc
Resolved
04/22/2015
ABOVE-CEILING OK BELOW: -SOUTH BIG ROOM AND TWO OFFICES **SUPPORT MC AT MAXIMUM 6FT INTERVAL AT NW ROOM
Gas Service Inspection - Commercial Passed 4/24/2015 4/24/2015 at 12:00 AM 04/24/2015
Occupancy Inspection - Codes Commercial Temporary C of O 4/30/2015 4/30/2015 at 12:00 AM 04/30/2015
Misc
Corrective Action Required
04/30/2015
-APPROVAL FROM THE FOLLOWING DEPT: FIRE, PLANNING, WATER, PUBLIC WORKS -SUBMIT SPECIAL INSPECTION LETTER -COMPLETE SIDEWALK -COMPLETE PARKING LOT LIGHTING; TRASH ENCLOSURE; PARAPET FLASHING; GUTTERS&DOWNSPOUTS -POST NO-SMOKING SIGNAGE AT FRONT -COMPLETE ELECTRICAL AT REAR SPACE AND ALL EXTERIOR LIGHTING -SECURELY FASTEN ALL VERTICAL RUN OF EMTs EVERY 10 FT AT REAR SPACE -COMPLETE HANDRAIL&GUARDRAIL FOR EXTERIOR STAIR -PAINT GAS LINES -LABEL ALL RTUs -CLEAN CONSTRUCTION DEBRIS OFF ROOF
Occupancy Inspection - Fire Passed 7/9/2015 at 12:00 AM 07/08/2015
Occupancy Inspection - Codes Commercial Full C of O 7/9/2015 10/02/2015
Misc
Resolved
10/02/2015
-APPROVAL FROM THE FOLLOWING DEPT: PLANNING, WATER, PUBLIC WORKS
Documents & Images
Date Uploaded File Type Document Name
11/10/2014 Letter Fire Building Plan Review
11/10/2014 Letter Codes Plan Review Conditions
03/11/2015 Receipt Receipt for transaction: 2015-000345
03/11/2015 Letter Codes Building Permit
03/12/2015 Letter Inspection Summary
03/16/2015 Letter Inspection Summary
03/23/2015 Letter Inspection Summary
03/26/2015 Letter Inspection Summary
03/27/2015 Letter Inspection Summary
04/06/2015 Letter Inspection Summary
04/10/2015 Letter Inspection Summary
04/16/2015 Letter Inspection Summary
04/20/2015 Letter Inspection Summary
04/21/2015 Letter Inspection Summary
04/22/2015 Letter Inspection Summary
04/24/2015 Letter Inspection Summary
04/30/2015 Letter Codes Temporary Certificate of Occupancy
04/30/2015 Letter Fire (Sprinkler) Plan Review
06/30/2015 Engineer Report/Study 2884 NE INDEPENDENCE AVE SPECIAL INSPECTION REPORT
06/30/2015 Letter Codes 10 Day Letter
07/10/2015 Letter Fire (Sprinkler) Plan Review
10/02/2015 Letter Field Certificate of Occupancy
10/05/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home