Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
07/10/2015
|
07/10/2015
|
|
Joe Dir
|
|
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
Hydrosattic testing and acceptance flow testing required, call 816-969-1300 to schedule a test.
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
11/14/2014
|
04/30/2015
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Plan review for adding in rack sprinklers
|
|
Misc
Corrective Action Required
Modifications to existing systems involving 20 or more heads requires a hydrostatic test, call (816) 969-1300 to schedule
|
|
|
Building Plan Review
|
Approved with Conditions
|
11/14/2014
|
11/10/2014
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Shell building is currently under construction.
Action required: Comment for informational purposes. No type of occupancy may be granted until permit for shell building is completed.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
11/14/2014
|
11/10/2014
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Rack storage shall comply with Chapter 57 of the International Fire Code. For information only. Provide a storage plan for the use of the warehouse
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide alarm plans for approval
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Provide addressing on front and rear doors
|
|
Fire protection equipment identification
Corrective Action Required
2012 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Rooms containing fire sprinkler riser, fan controls, electrical service etc shall be marked
|
|
Construction documents - Fire protection systems
Corrective Action Required
2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans for approval
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Provide 5lb ABC type extinguishers
|
|
|
Licensed Contractors
|
Approved
|
11/14/2014
|
11/04/2014
|
|
Joe Frogge
|
|
|