Permit Application Status

PRCOM20142412


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20142412
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
NEW TENANT FINISH
TENANT FINISH FOR WEIGHT WATCHERS - USE IS EDUCATIONAL WITH SOME OFFICE AND MERCANTILE
08/25/2014
10/21/2014
02/24/2015
12/05/2014
Locations
Contacts
FMS, Address:5721 THEDEN, Phone:(913) 260-8216  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
FMS, Address:5721 THEDEN, Phone:(913) 260-8216  
FMS, Address:5721 THEDEN, Phone:(913) 260-8216  
POOR JOHN'S PLUMBING LLC, Address:6524 NW GRADEN RD, Phone:(816) 455-5420  
SCHARHAG ARCHITECTS, Address:310 ARMOUR RD #202, Phone:(816) 221-9297  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/15/2014 10/21/2014
Development Center
LC - General Contractor
Corrective Action Required
09/15/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
09/15/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Approved with Conditions 09/22/2014 09/22/2014
Joe Frogge
License Tax Application
Corrective Action Required
09/15/2014

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Resolved
09/16/2014

Action Required: Submit wall construction types and details. Submit door schedule.
Bldg - Illumination required 1006.1
Resolved
09/22/2014

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide illumination at exit discharges. 9/22/14 - provided
Mech - Outdoor air required 403.2
Resolved
09/16/2014

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Revise drawings to show outside air calculations as well as method of delivery.
Plumb - Minimum number of fixtures 403.1
Resolved
09/16/2014

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide drinking fountain(s) and mop/utility sink.
Fire Plan Review Approved 09/22/2014 09/17/2014
Brian Austerman
Misc
Corrective Action Required
09/16/2014

Add an exit sign on the north side of the meeting room space, either over the door or on the south wall with a directional arrow pointing toward the west exit RESOLVED 9-17
Address numbers required
Corrective Action Required
09/16/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). All exterior doors to the space shall have proper addressing. Verified at inspection
Portable fire extinguishers - general
Corrective Action Required
09/16/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type fire extinguisher
Fire Plan Review Rejected 09/05/2014 09/16/2014
Joe Frogge
Misc
Corrective Action Required
08/25/2014

Add an exit sign on the north side of the meeting room space, either over the door or on the south wall with a directional arrow pointing toward the west exit
Address numbers required
Corrective Action Required
08/25/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). All exterior doors to the space shall have proper addressing. Verified at inspection
Portable fire extinguishers - general
Corrective Action Required
08/25/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 5lb ABC type fire extinguisher
Building Plan Review Rejected 09/05/2014 08/28/2014
Joe Frogge
License Tax Application
Corrective Action Required
08/28/2014

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
08/28/2014

Action Required: Submit wall construction types and details. Submit door schedule.
Bldg - Illumination required 1006.1
Corrective Action Required
08/28/2014

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Provide illumination at exit discharges.
Mech - Outdoor air required 403.2
Corrective Action Required
08/28/2014

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Action required: Revise drawings to show outside air calculations as well as method of delivery.
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
08/28/2014

2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required: Provide drinking fountain(s) and mop/utility sink.
Licensed Contractors Rejected 09/05/2014 08/28/2014
Joe Frogge
LC - General Contractor
Corrective Action Required
08/28/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
08/28/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $92.32 $92.32 Paid 10/21/2014
8331507-Sewer Connection Fee $90.00 $90.00 Paid 10/21/2014
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 10/31/2014 at 12:00 AM 10/31/2014
In-wall Inspection Failed 11/10/2014 11/10/2014 at 12:00 AM 11/10/2014
Misc
Corrective Action Required
11/10/2014
NEW WALLS AT FLOOR SINK: IPC - PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Corrective Action Required
11/10/2014
OTHER NEW WALLS APPARENTLY CONSTRUCTED AND COVERED WITHOUT INSPECTION AND APPROVAL.
In-wall Inspection Partial 11/10/2014 at 12:00 AM 11/10/2014
Misc
Corrective Action Required
11/10/2014
NEW WALLS AT FLOOR SINK: IPC - PROTECTION OF COPPER PIPING AT PENETRATION OF STEEL FRAMING MEMBERS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Resolved
11/10/2014
OTHER NEW WALLS APPARENTLY CONSTRUCTED AND COVERED WITHOUT INSPECTION AND APPROVAL.
In-wall Inspection Passed 11/11/2014 11/11/2014 at 12:00 AM 11/11/2014
Misc
Resolved
11/11/2014
NEW WALLS AT FLOOR SINK OK TO COVER WHEN READY.
Above Ceiling Inspection Not Ready 11/20/2014 11/20/2014 at 12:00 AM 11/20/2014
Above Ceiling Inspection Not Ready 11/24/2014 11/20/2014 at 12:00 AM 11/23/2014
Misc
Corrective Action Required
11/23/2014
REMOVE ALL ABANDONED MATERIALS. SEAL UNUSED OPENINGS TO ATMOSPHERE (VENT PIPES, ETC)
Misc
Corrective Action Required
11/23/2014
COMPLETE ALL NEW WORK.
Misc
Corrective Action Required
11/23/2014
MAKE UP AND CLOSE ALL ELECTRICAL BOXES.
Misc
Corrective Action Required
11/23/2014
PROPERLY SUPPORT ELECTRIAL CONDUIT -- NEW AND EXISTING.
Misc
Corrective Action Required
11/23/2014
SECURE MC ELECTRICAL CABLE WITHIN 12" OF ENTRY TO BOXES WHEREVER POSSIBLE.
Misc
Corrective Action Required
11/23/2014
PLUG UNUSED OPENINGS IN ELECTRICAL BOXES.
Misc
Corrective Action Required
11/23/2014
RECESSED LUMINARES REQUIRE TWO SLACK WIRES AT OPPOSITE DIAGONAL CORNERS.
Misc
Corrective Action Required
11/23/2014
CEILING GRID MUST SUPPORTED TO STRUCTURE -- NOT TO DUCTWORK OR OTHER M/E/P SYSTEMS.
Misc
Corrective Action Required
11/23/2014
MINIMUM WIDTH OF FLEX DUCT HANGERS IS 1-1/2" PER SMACNA.
Above Ceiling Inspection Passed 11/24/2014 at 12:00 AM 11/24/2014
Misc
Resolved
11/24/2014
REMOVE ALL ABANDONED MATERIALS. SEAL UNUSED OPENINGS TO ATMOSPHERE (VENT PIPES, ETC)
Misc
Resolved
11/24/2014
COMPLETE ALL NEW WORK.
Misc
Resolved
11/24/2014
MAKE UP AND CLOSE ALL ELECTRICAL BOXES.
Misc
Resolved
11/24/2014
PROPERLY SUPPORT ELECTRIAL CONDUIT -- NEW AND EXISTING.
Misc
Resolved
11/24/2014
SECURE MC ELECTRICAL CABLE WITHIN 12" OF ENTRY TO BOXES WHEREVER POSSIBLE.
Misc
Resolved
11/24/2014
PLUG UNUSED OPENINGS IN ELECTRICAL BOXES.
Misc
Resolved
11/24/2014
RECESSED LUMINARES REQUIRE TWO SLACK WIRES AT OPPOSITE DIAGONAL CORNERS.
Misc
Resolved
11/24/2014
CEILING GRID MUST SUPPORTED TO STRUCTURE -- NOT TO DUCTWORK OR OTHER M/E/P SYSTEMS.
Misc
Resolved
11/24/2014
MINIMUM WIDTH OF FLEX DUCT HANGERS IS 1-1/2" PER SMACNA.
Occupancy Inspection - Codes Commercial Temporary C of O 12/2/2014 12/2/2014 at 12:00 AM 12/02/2014
Misc
Corrective Action Required
12/02/2014
ANSI/ICC 604.5.1: 18" HORIZONTAL GRAB BARS @ RR105 NOT PER CODE & APPROVED DRAWING.
Misc
Corrective Action Required
12/02/2014
IPC 420.3: WATER CLOSET SEAT(S) MUST BE COMMERCIAL TYPE WITH OPEN FRONT. SEE WC @ RR106
Misc
Corrective Action Required
12/02/2014
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE CLEARLY NUMBERED.
Misc
Corrective Action Required
12/02/2014
NEC 110-12: UNUSED BREAKER OPENINGS AT ELECTRICAL PANELS MUST BE CLOSED WITH LISTED PLUG.
Occupancy Inspection - Fire Temporary C of O 12/2/2014 at 12:00 AM 12/02/2014
Misc
Corrective Action Required
12/02/2014
install blanks in electrical panels as needed - remove all hardware from front door that will not be utilized
Occupancy Inspection - Codes Commercial Full C of O 12/5/2014 12/5/2014 at 12:00 AM 12/05/2014
Misc
Resolved
12/05/2014
ANSI/ICC 604.5.1: 18" HORIZONTAL GRAB BARS @ RR105 NOT PER CODE & APPROVED DRAWING.
Misc
Resolved
12/05/2014
IPC 420.3: WATER CLOSET SEAT(S) MUST BE COMMERCIAL TYPE WITH OPEN FRONT. SEE WC @ RR106
Misc
Resolved
12/05/2014
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE CLEARLY NUMBERED.
Misc
Resolved
12/05/2014
NEC 110-12: UNUSED BREAKER OPENINGS AT ELECTRICAL PANELS MUST BE CLOSED WITH LISTED PLUG.
Occupancy Inspection - Fire Passed 12/5/2014 12/5/2014 at 12:00 AM 12/31/2015
Misc
Corrective Action Required
12/02/2014
install blanks in electrical panels as needed - remove all hardware from front door that will not be utilized
Documents & Images
Date Uploaded File Type Document Name
08/25/2014 Letter Fire Building Plan Review
08/28/2014 Letter Codes P/R Corrections Document
09/17/2014 Letter Fire Building Plan Review
10/21/2014 Letter Codes Plan Review Conditions
10/21/2014 Letter Codes Building Permit
10/21/2014 Receipt Receipt for transaction: 2014-002037
10/31/2014 Letter Inspection Summary
11/10/2014 Letter Inspection Summary
11/11/2014 Letter Inspection Summary
11/20/2014 Letter Inspection Summary
11/24/2014 Letter Inspection Summary
12/02/2014 Letter Codes Temporary Certificate of Occupancy
12/05/2014 Letter Field Certificate of Occupancy
12/08/2014 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide: