Summary
PRCOM20142361
Building Permit - Commercial
Final Completion
NEWPORT INVESTMENTS INC
ALTERATION COMMERCIAL
ALTER CONVENIENCE STORE TO ACCOMODATE INSTALLATION OF FOOD PREP AND SALES AREA
08/20/2014
10/13/2014
02/17/2015
11/17/2014
Locations
Contacts
BLUE STAR SERVICES, Address:2125 E 155TH ST, Phone:(913) 638-7264  
TODCO, Address:1260 SE CENTURY DR, Phone:(816) 875-1941  
PRO CIRCUIT, Address:4925 DERAMUS AVE , Phone:(816) 474-9292  
NUMER PLUMBING, Address:11550 N PLATTE PURCHASE, Phone:(816) 734-4484  
NEWPORT INVESTMENTS INC, Address:PO BOX 3475  
LICKEL ARCHITECTURE, Address:14 WEST 3RD ST; SUITE 100, Phone:(816) 421-0707  
QUIKTRIP, Address:5725 FOXRIDGE DR, Phone:(913) 626-1576  
Reviews
Review Type Outcome Est. Completion Date Completed
Health Department Review Approved 02/17/2015 10/10/2014
Joe Frogge
Building Plan Review Approved with Conditions 09/01/2014 10/10/2014
Joe Frogge
Health Dept Inspection
Corrective Action Required
08/21/2014

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action Required: This comment is for information purposes.
Health Dept Review
Resolved
10/10/2014

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required: This comment is for information purposes.
Licensed Contractors Approved 09/01/2014 10/09/2014
Joe Frogge
LC - General Contractor
Resolved
10/09/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
10/09/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved 09/01/2014 08/20/2014
Brian Austerman
Misc
Corrective Action Required
08/20/2014

No Fire Dept comments
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $445.37 $445.37 Paid 10/13/2014
8331507-Sewer Connection Fee $120.00 $120.00 Paid 10/13/2014
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 10/21/2014 10/21/2014 at 12:00 AM 10/21/2014
Misc
Partial Correction
10/21/2014
OK TO COVER WHEN READY UNDER-SLAB PVC GREASE WASTE, SANITARY DRAIN, WASTE, & VENT PIPING AT LOCATIONS: SPACE 105 WEST; NOTE IPC 312 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Electrical Inspection - Commercial Partial 10/21/2014
Misc
Partial Correction
10/21/2014
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: SPACE 105 WEST WALL; NOTE IPC 312 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Partial 10/21/2014 10/21/2014 at 12:00 AM 10/21/2014
Misc
Partial Correction
10/21/2014
OK TO COVER WHEN READY UNDER-SLAB PVC GREASE WASTE, SANITARY DRAIN, WASTE, & VENT PIPING: SPACE 105 WEST; NOTE IPC 312 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
In-wall Inspection Partial 10/21/2014 at 12:00 AM 10/21/2014
Misc
Partial Correction
10/21/2014
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: SPACE 105 WEST WALL; NOTE IPC 312 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Passed 10/29/2014 10/29/2014 at 12:00 AM 10/29/2014
Misc
Partial Correction
10/21/2014
OK TO COVER WHEN READY UNDER-SLAB PVC GREASE WASTE, SANITARY DRAIN, WASTE, & VENT PIPING: SPACE 105 WEST; NOTE IPC 312 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
In-wall Inspection Passed 10/31/2014 10/31/2014 at 12:00 AM 10/31/2014
Misc
Resolved
10/31/2014
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING SPACES: SPACE 105 WEST WALL; NOTE IPC 312 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Sewer Service Inspection Partial 11/3/2014 at 12:00 AM 11/03/2014
Misc
Partial Correction
11/03/2014
G.W. AND SANITARY PIPING FROM BUILDING ENTRY, VENT, GREASE INTERCEPTOR, AND CONNECTION TO EXISTING SEWER SERVICE LINE APPROVED EXCEPT BEDDING ROCK YET TO BE PLACED.
Sewer Service Inspection Passed 11/3/2014 (3:30) 11/3/2014 at 12:00 AM 11/03/2014
Misc
Resolved
11/03/2014
G.W. AND SANITARY PIPING FROM BUILDING ENTRY, VENT, GREASE INTERCEPTOR, AND CONNECTION TO EXISTING SEWER SERVICE LINE APPROVED EXCEPT BEDDING ROCK YET TO BE PLACED.
Above Ceiling Inspection Partial 11/11/2014 11/11/2014 at 12:00 AM 11/11/2014
Misc
Partial Correction
11/11/2014
OK TO COVER WHEN READY ABOVE-CEILING SYSTEMS AT FOOD PREP AREA;
Gas Piping Inspection - Commercial Partial 11/14/2014 at 12:00 AM 11/14/2014
Misc
Corrective Action Required
11/14/2014
STAND-OFF NEEDED AT BOTTOM OF VERTICAL RUN AT REAR WALL.
Misc
Partial Correction
11/14/2014
PIPING PRESSURE TEST SAID TO HAVE BEEN WITNESSED PREVIOUSLY BY ANOTHER INSPECTOR.
Gas Piping Inspection - Commercial Passed 11/17/2014 11/17/2014 at 12:00 AM 11/17/2014
Misc
Resolved
11/17/2014
STAND-OFF NEEDED AT BOTTOM OF VERTICAL RUN AT REAR WALL.
Misc
Resolved
11/17/2014
PIPING PRESSURE TEST SAID TO HAVE BEEN WITNESSED PREVIOUSLY BY ANOTHER INSPECTOR.
Above Ceiling Inspection Passed 11/14/2014 11/17/2014 at 12:00 AM 11/17/2014
Misc
Resolved
11/17/2014
OK TO COVER WHEN READY ABOVE-CEILING SYSTEMS AT FOOD PREP AREA;
Occupancy Inspection - Fire Passed 11/17/2014 11/17/2014 at 12:00 AM 11/17/2014
Final Inspection - Commercial Passed 11/17/2014 11/17/2014 at 12:00 AM 11/17/2014
Documents & Images
Date Uploaded File Type Document Name
08/20/2014 Letter Fire Building Plan Review
08/21/2014 Letter Codes P/R Corrections Document
10/10/2014 Letter Codes Plan Review Conditions
10/13/2014 Receipt Receipt for transaction: 2014-001972
10/13/2014 Letter Codes Building Permit
10/21/2014 Letter Inspection Summary
10/29/2014 Letter Inspection Summary
10/31/2014 Letter Inspection Summary
11/03/2014 Letter Inspection Summary
11/03/2014 Letter Inspection Summary
11/11/2014 Letter Inspection Summary
11/14/2014 Letter Inspection Summary
11/17/2014 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home