Permit Application Status

PRCOM20141078


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20141078
Building Permit - Commercial
Certificate of Occupancy
RESIDENCES AT NEW LONGVIEW LLC
NEW MULTI-FAMILY
APARTMENT BUILDING #1 - TYPE A4/5
05/08/2014
07/10/2014
11/18/2014
03/18/2016
Locations
Contacts
NEIGHBORS CONSTRUCTION COMPANY INC, Address:1708 E 123RD ST, Phone:(913) 422-5555  
MINICK GAMBRELL CONTRACTORS LLC, Address:11528 W 90TH ST, Phone:(913) 538-5391  
LYNN ELECTRIC & COMMUNICATIONS INC, Address:725 N 2ND ST STE K, Phone:(785) 843-5709  
BLUE RIVER PLUMBING INC, Address:9125 BARTON ST, Phone:(913) 701-6410  
NSPJ ARCHITECTS, Address:3515 W 75TH ST, SUITE 201  
RESIDENCES AT NEW LONGVIEW LLC, Address:5015 NW CANAL ST  
OLSSON ASSOCIATES, Address:1251 NW BRIARCLIFF PKWY, STE. 50, Phone:(816) 361-1177  
CITY OF LEES SUMMIT, Address:220 S MAIN  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 11/12/2014
Brian Austerman
Misc
Corrective Action Required
11/12/2014

Riser diagram shows a check valve before the risers on the FDC line. A check valve at the base of the riser from the underground is also required.
Installation acceptance testing
Corrective Action Required
11/12/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow testing
Misc
Corrective Action Required
11/12/2014

Drain points shall be routed to the exterior or to a suitable floor drain
Misc
Corrective Action Required
11/12/2014

The air compressor for the dry system shall be listed for fire service use
Misc
Corrective Action Required
11/12/2014

Expansion chamber for antifreeze system not shown, if used it shall be rated for fire service use
Alarm Plan Review Released for Construction 10/10/2014
Brian Austerman
Misc
Corrective Action Required
10/10/2014

Relabel CO2 to CO on all sets of plans Resolved 10/10/2104
Installation acceptance testing
Corrective Action Required
10/10/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule flow and alarm testing
Alarms connected to automatic sprinkler system
Corrective Action Required
10/10/2014

2012 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Outside horn strobe to activate on waterflow only
Misc
Corrective Action Required
10/10/2014

Add monitor modules to the garage CO detectors to relay a supervisory signal to the alarm panel Resolved 10/10/2014
Misc
Corrective Action Required
10/10/2014

3rd floor plans did not show smoke/CO detection Resolved 10/10/14
Misc
Corrective Action Required
10/10/2014

Add an annunciator panel in the sprinkler room Resolved 10/10/14
Alarm Plan Review Rejected 08/22/2014
Brian Austerman
Misc
Corrective Action Required
08/22/2014

Relabel CO2 to CO on all sets of plans
Installation acceptance testing
Corrective Action Required
08/22/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule flow and alarm testing
Alarms connected to automatic sprinkler system
Corrective Action Required
08/22/2014

2012 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Outside horn strobe to activate on waterflow only
Misc
Corrective Action Required
08/22/2014

Add monitor modules to the garage CO detectors to relay a supervisory signal to the alarm panel
Misc
Corrective Action Required
08/22/2014

3rd floor plans did not show smoke/CO detection
Misc
Corrective Action Required
08/22/2014

Add an annunciator panel in the sprinkler room
Licensed Contractors Approved 06/11/2014 07/09/2014
Mike Weisenborn
Business License
Corrective Action Required
06/04/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
06/04/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Final Development Plan Review Approved 07/22/2014 07/09/2014
Mike Weisenborn
Building Plan Review Approved with Conditions 06/11/2014 06/10/2014
Joe Frogge
Misc
Corrective Action Required
06/04/2014

2012 IBC Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ram connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be location 5 feet above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. (see code section for specific requirements) Action required: Comment for informational purposes. May be verified at inspections.
Misc
Resolved
06/10/2014

2012 IBC 1107.6.2 Group R-2. Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 and 1107.6.2.2. Action required: Clarify which units will be Type A and demonstrate how they will meet ICC A117.1 requirements. Clarify how remaining (Type B) units will meet ICC A117.1 requirements. 6/10/14 - provided on drawing
Misc
Corrective Action Required
06/04/2014

2009 ANSI ICC A117.1 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met. 6/10/14 - Acknowledged - to be verified at inspection
Misc
Resolved
06/10/2014

2012 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting detail. Cleanout on vent side to either be above flood rim level or be bi-directional. 6/10/14 - provided on drawing
Misc
Resolved
06/10/2014

2011 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Modify documents to demonstrate how this requirement will be met. 6/10/14 - provided on drawing
r
Fire Plan Review Approved with Conditions 06/11/2014 06/10/2014
Brian Austerman
Misc
Corrective Action Required
06/04/2014

Elevator must be capable of accomodating a stretcher, NFPA 5000.54.3. Plans appear to show this, comment is for information only
Misc
Corrective Action Required
06/04/2014

Standpipes. IFC 905.3.1 has been ammended locally to read; Class 1 standpipe systems shall be installed throughout buildings where the floor of the highest story is located more than two stories above the lowest level of fire department vehicle access. Provide standpipes on each floor level in the stairwells
Construction documents - Fire protection systems
Corrective Action Required
06/04/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
06/04/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Knox box required
Corrective Action Required
06/04/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Misc
Corrective Action Required
06/04/2014

[B] 1022.8 Discharge identification. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1011. Provide a gate on the stairway at the landing on ground level APPROVED 6/10/14 RESOLVED. GROUND LEVEL IDENTIFICATION SHALL BE PROVIDED IN THE STAIRWAY
Misc
Corrective Action Required
06/04/2014

908.7 Carbon monoxide alarms. Group I or R occupancies located in a building containing a fuel-burning appliance or in a building which has an attached garage shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer’s instructions. An open parking garage, as defined in Chapter 2 of the International Building Code, or an enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. Exception: Sleeping units or dwelling units which do not themselves contain a fuel-burning appliance or have an attached garage, but which are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that: 1. The sleeping unit or dwelling unit is located more than one story above or below any story which contains a fuel-burning appliance or an attached garage; 2. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance or to an attached garage; and 3. The building is equipped with a common area carbon monoxide alarm system. Provide carbon monoxide alarms per the code above 6/10/14 RESOLVED. CO DETECTION AND ALARM PLANS RECEIVED AND APPROVED FOR GARAGES AND COMMON AREAS
Misc
Corrective Action Required
06/04/2014

[B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. Provide remote emergency egress illumination on the exterior of the exits
Portable fire extinguishers - general
Corrective Action Required
06/04/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. For information only
Misc
Corrective Action Required
06/04/2014

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. To be located in the knox box
Special Inspections Review Approved 06/20/2014 05/30/2014
Mike Weisenborn
Building Plan Review Rejected 05/22/2014 05/22/2014
Joe Frogge
Misc
Corrective Action Required
05/22/2014

2012 IBC Stairway identification signs. A sign shall be provided at each floor landing in an interior exit stairway and ram connecting more than three stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be location 5 feet above the floor landing in a position that is readily visible when the doors are in the open and closed positions. In addition to the stairway identification sign, a floor-level sign in raised characters and Braille complying with ICC A117.1 shall be located at each floor-level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor to identify the floor level. (see code section for specific requirements) Action required: Comment for informational purposes. May be verified at inspections.
Misc
Corrective Action Required
05/22/2014

2012 IBC 1107.6.2 Group R-2. Accessible units, Type A units and Type B units shall be provided in Group R-2 occupancies in accordance with Sections 1107.6.2.1 and 1107.6.2.2. Action required: Clarify which units will be Type A and demonstrate how they will meet ICC A117.1 requirements. Clarify how remaining (Type B) units will meet ICC A117.1 requirements.
Misc
Corrective Action Required
05/22/2014

2009 ANSI ICC A117.1 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Modify documents to demonstrate how this requirement will be met.
Misc
Corrective Action Required
05/22/2014

2012 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting detail. Cleanout on vent side to either be above flood rim level or be bi-directional.
Misc
Corrective Action Required
05/22/2014

2011 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Modify documents to demonstrate how this requirement will be met.
r
Licensed Contractors Rejected 05/22/2014 05/22/2014
Joe Frogge
Business License
Corrective Action Required
05/22/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
05/22/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 05/22/2014 05/13/2014
Brian Austerman
Misc
Corrective Action Required
05/13/2014

Elevator must be capable of accomodating a stretcher, NFPA 5000.54.3. Plans appear to show this, comment is for information only
Misc
Corrective Action Required
05/13/2014

Standpipes. IFC 905.3.1 has been ammended locally to read; Class 1 standpipe systems shall be installed throughout buildings where the floor of the highest story is located more than two stories above the lowest level of fire department vehicle access. Provide standpipes on each floor level in the stairwells
Construction documents - Fire protection systems
Corrective Action Required
05/13/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
05/13/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Knox box required
Corrective Action Required
05/13/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application
Misc
Corrective Action Required
05/13/2014

[B] 1022.8 Discharge identification. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1011. Provide a gate on the stairway at the landing on ground level
Misc
Corrective Action Required
05/13/2014

908.7 Carbon monoxide alarms. Group I or R occupancies located in a building containing a fuel-burning appliance or in a building which has an attached garage shall be equipped with single-station carbon monoxide alarms. The carbon monoxide alarms shall be listed as complying with UL 2034 and be installed and maintained in accordance with NFPA 720 and the manufacturer’s instructions. An open parking garage, as defined in Chapter 2 of the International Building Code, or an enclosed parking garage ventilated in accordance with Section 404 of the International Mechanical Code shall not be considered an attached garage. Exception: Sleeping units or dwelling units which do not themselves contain a fuel-burning appliance or have an attached garage, but which are located in a building with a fuel-burning appliance or an attached garage, need not be equipped with single-station carbon monoxide alarms provided that: 1. The sleeping unit or dwelling unit is located more than one story above or below any story which contains a fuel-burning appliance or an attached garage; 2. The sleeping unit or dwelling unit is not connected by duct work or ventilation shafts to any room containing a fuel-burning appliance or to an attached garage; and 3. The building is equipped with a common area carbon monoxide alarm system. Provide carbon monoxide alarms per the code above
Misc
Corrective Action Required
05/13/2014

[B] 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. Provide remote emergency egress illumination on the exterior of the exits
Portable fire extinguishers - general
Corrective Action Required
05/13/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. For information only
Misc
Corrective Action Required
05/13/2014

607.4 Elevator key location. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the fire department. To be located in the knox box
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Multi-Family $13,812.10 $13,812.10 Paid 07/10/2014
8331507-Sewer Connection Fee $3,000.00 $3,000.00 Paid 07/10/2014
$3,000.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection Partial 7/21/2014 (1:00) 7/21/2014 at 12:00 AM 07/21/2014
Misc
Corrective Action Required
07/21/2014
MAIN TO WITHIN 5' OF BUILDING
Footing Inspection - Commercial Partial 8/20/2014 (1:00) 8/20/2014 at 12:00 AM 08/20/2014
Underslab Plumbing Inspection - Commercial Partial 8/26/2014 8/26/2014 at 12:00 AM 08/26/2014
Misc
Corrective Action Required
08/26/2014
SOUTH SIDE APPROVED
Underslab Plumbing Inspection - Commercial Passed 9/3/2014 9/3/2014 at 12:00 AM 09/03/2014
Underground Electrical Inspection - Residential Passed 9/5/2014 9/5/2014 at 12:00 AM 09/05/2014
Water Service Inspection Passed 9/10/2014 9/10/2014 at 12:00 AM 09/10/2014
Underslab Plumbing Inspection - Commercial Passed 10/27/2014 10/27/2014 at 12:00 AM 10/30/2014
Misc
Corrective Action Required
10/27/2014
SOUTH SIDE APPROVED
Footing Inspection - Commercial Passed 10/31/2014 (1:00) 10/31/2014 at 12:00 AM 10/31/2014
Underslab Plumbing Inspection - Commercial Passed 11/13/2014 11/13/2014 at 12:00 AM 11/13/2014
Footing Inspection - Commercial Passed 11/19/2014 (1:00) 11/19/2014 at 12:00 AM 11/19/2014
Underground Electrical Inspection - Commercial Partial 1/30/2015 1/30/2015 at 12:00 AM 01/30/2015
Rated Assembly Inspection Partial 1/30/2015 at 12:00 AM 01/30/2015
Misc
Corrective Action Required
01/30/2015
STAIR WALLS- 1ST LAYER GROUND TO 3RD FLOOR.
Rated Assembly Inspection Partial 2/9/2015 2/9/2015 at 12:00 AM 02/09/2015
Misc
Partial Correction
02/09/2015
SECOND LAYOR OF FOR FIRST 3 FLOORS IN BOTH STAIRWELLS APPROVED
Sewer Service Inspection Passed 02/10/2015
Rough Framing Inspection - Commercial Failed 2/20/2015 at 12:00 AM 02/12/2015
Misc
Corrective Action Required
02/12/2015
GARAGE-JOIST HANGER NAILS 1ST -HOLD DOWN NE CORNER EXTERIOR WALL 2ND- 3RD- 4TH-
In-wall Inspection Failed 1/30/2015 2/20/2015 at 12:00 AM 02/20/2015
B705 FIRE WALLS
Corrective Action Required
02/10/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- IT &ELECT ROOM OK TO ONE SIDE 1ST- 2ND- 3RD- 4TH-
Rough Framing Inspection - Commercial Failed 02/25/2015
Misc
Corrective Action Required
02/12/2015
GARAGE-fraimng 1ST -partial 2ND-partial 3RD- 4TH-
In-wall Inspection Failed 2/26/2015 2/27/2015 at 12:00 AM 02/27/2015
B705 FIRE WALLS
Corrective Action Required
02/20/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- 1ST-1101 ,1103,1106 OK FOR PREROCK ALL OTHER UNITS FAILED NOT READY FOR INSPECTION. PLEASE HAVE ENTIRE FLOOR COMPLETE WHEN CALLED IN FOR INSPECTION. 2ND- 3RD- 4TH-
Rough Framing Inspection - Commercial Partial 3/2/2015 3/2/2015 at 12:00 AM 03/02/2015
Misc
Corrective Action Required
02/25/2015
GARAGE-fraimng 1ST -partial 2ND-partial 3RD- 4TH-
Misc
Partial Correction
03/02/2015
MIKE COPELAND 03/02/2015 11:18 AM -LOWER LEVEL SHEAR WALL AT ELEVATOR SHAFT NEED TO INSTALL HOLD DOWNS PER PLANS. OTHER SHEAR WALLS APPROVED. -FIRST FLOOR MECHANICAL ROOMS OKAY TO ONE SIDE ROCK. NEED TO FIRESTOP SPRINKLER
In-wall Inspection Failed 3/5/2015 3/5/2015 at 12:00 AM 03/05/2015
B705 FIRE WALLS
Corrective Action Required
02/27/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- 1ST-OK-PRE FRAMING 2ND-OK- PRE FRAMING 3RD-OK- PRE-FRAMING PREROCK IN MECHANICAL ROOMS AT ELEVATOR 1ST,2ND,3RD OK
Rough Framing Inspection - Commercial Failed 3/5/2015 3/5/2015 at 12:00 AM 03/05/2015
Misc
Corrective Action Required
03/02/2015
GARAGE-fraimng 1ST -partial, HOLD DOWN 2ND-partial, HOLD DOWN 3RD-PARTIAL HOD DOWN FLOOR TRUSS DRILLED CHECK FIX. 4TH-( NOTE:SCREWS NOT HOLD DOWNS) SHEAR WALL NAILING - EXTERIOR -OK INTERIOR- PARTIAL CHECK REMAINING AT ALL TRADES INSPECTION
Misc
Partial Correction
03/02/2015
MIKE COPELAND 03/02/2015 11:18 AM -LOWER LEVEL SHEAR WALL AT ELEVATOR SHAFT NEED TO INSTALL HOLD DOWNS PER PLANS. OTHER SHEAR WALLS APPROVED. -FIRST FLOOR MECHANICAL ROOMS OKAY TO ONE SIDE ROCK. NEED TO FIRESTOP SPRINKLER
Rough Framing Inspection - Commercial Failed 3/6/2015 3/6/2015 at 12:00 AM 03/06/2015
Misc
Corrective Action Required
03/05/2015
GARAGE-fraimng 1ST -partial, HOLD DOWN 2ND-partial, HOLD DOWN 3RD-PARTIAL HOD DOWN FLOOR TRUSS DRILLED CHECK FIX. 4TH-( NOTE:SCREWS NOT HOLD DOWNS) SHEAR WALL NAILING - EXTERIOR -OK INTERIOR- PARTIAL CHECK REMAINING AT ALL TRADES INSPECTION
Above Ceiling Inspection Failed 3/16/2015 3/16/2015 at 12:00 AM 03/16/2015
LOWER LEVEL
Corrective Action Required
03/16/2015
GARAGE - CORRIDOR PLUMIBNG PLATES NEEDED WHERE 3" DVW ENTERS WALL AND CEILING -SPRINKLER PIPING SCREWED TO FLOOR JOIST NEED TO MOVE OR LOWER FOR ROCK. - EAST END :WATER PIPING, 3" DWV , AGAINST FLOOR JOIST REMOVE TO INSTALL ROCK OR PROVIDE APPROVED FIRE COLLARS AND LISTING FOR INSPECTION.
Rough Framing Inspection - Commercial Partial 3/16/2015 3/16/2015 at 12:00 AM 03/16/2015
Misc
Corrective Action Required
03/06/2015
GARAGE-fraimng 1ST -partial, HOLD DOWN 2ND-partial, HOLD DOWN 3RD-PARTIAL HOD DOWN FLOOR TRUSS DRILLED CHECK FIX. 4TH-( NOTE:SCREWS NOT HOLD DOWNS) MISSING 1 SCREW EAST EXTERIOR WALL, 1 SCREW NOT FULLY SEATED WEST END SHEAR WALL NAILING - EXTERIOR -OK INTERIOR- PARTIAL CHECK REMAINING AT ALL TRADES INSPECTION
Rated Assembly Inspection Failed 3/19/2015 at 12:00 AM 03/19/2015
Misc
Partial Correction
02/09/2015
SECOND LAYOR OF FOR FIRST 3 FLOORS IN BOTH STAIRWELLS APPROVED
B705 FIRE WALLS
Corrective Action Required
03/19/2015
RATED WALL-1-2-3 SHOWER WALLS- PLUMBING ENTERING SHEETROCK AT AN ANGLE, GAPS IN ROCK, SCREW PATTERN OVER 16" OC. STUDS. MISSUNG SCREWS BEHIND SHOWER VALVES. . PLUMBING PIPE IN LINE OF WALL WHERE ROCK IS TO BE. FAILED ALL FLOORS
In-wall Inspection Partial 3/23/2015 3/23/2015 at 12:00 AM 03/23/2015
B705 FIRE WALLS
Corrective Action Required
03/05/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE-IT&ELECT ROOM 1ST-OK-PRE FRAMING 2ND-OK- PRE FRAMING 3RD-OK- PRE-FRAMING 4TH-
Rough Framing Inspection - Commercial Partial 3/23/2015 3/23/2015 at 12:00 AM 03/23/2015
Misc
Corrective Action Required
03/16/2015
GARAGE-fraimng 1ST -partial, HOLD DOWN 2ND-partial, HOLD DOWN 3RD-PARTIAL HOLD DOWN FLOOR TRUSS DRILLED CHECK FIX. 4TH-PARTAIL HOLD DOWN SHEAR WALL NAILING - EXTERIOR -OK INTERIOR- PARTIAL CHECK REMAINING AT ALL TRADES INSPECTION
Sprinkler - Hydrostatic Test Passed 3/24/2015 3/24/2015 at 9:00 AM 03/24/2015
In-wall Inspection Partial 3/24/2015 3/24/2015 at 12:00 AM 03/24/2015
Misc
Corrective Action Required
03/23/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- IT &ELECT ROOM OK TO ONE SIDE 1ST- 2ND- 3RD- 4TH-
FRAMING/STRUCTURE
Corrective Action Required
03/24/2015
SOFIT CEILING OVER DECK/ BALCONYS 1ST FLOOR SOUTH SIDE 2ND FLOOR SOUTH SIDE FIRE CAULKING ON INTERIOR. OK TO COVER
In-wall Inspection Failed 3/26/2015 3/26/2015 at 12:00 AM 03/26/2015
Misc
Corrective Action Required
03/24/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- IT &ELECT ROOM OK TO ONE SIDE 1ST- 2ND- 3RD- 4TH-
FRAMING/STRUCTURE
Corrective Action Required
03/24/2015
SOFIT CEILING OVER DECK/ BALCONYS 1ST FLOOR SOUTH SIDE 2ND FLOOR SOUTH SIDE FIRE CAULKING ON INTERIOR. OK TO COVER
Misc
Corrective Action Required
03/26/2015
covered canopies- fireccaulking inside and out, no turn downs on vents and ducts. specify if you are cauling inside or outside, all turn downs must be complete.
In-wall Inspection Partial 3/27/2015 3/27/2015 at 12:00 AM 03/27/2015
Misc
Corrective Action Required
03/26/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- IT &ELECT ROOM OK TO ONE SIDE 1ST- 2ND- 3RD- 4TH-
FRAMING/STRUCTURE
Corrective Action Required
03/26/2015
SOFIT CEILING OVER DECK/ BALCONYS 1ST FLOOR SOUTH SIDE 2ND FLOOR SOUTH SIDE FIRE CAULKING ON INTERIOR. OK TO COVER
Misc
Corrective Action Required
03/26/2015
covered canopies- fireccaulking inside and out, no turn downs on vents and ducts. specify if you are cauling inside or outside, all turn downs must be complete. soffits ok to cover 1-2-3 floors
Electrical Service Inspection Failed 3/31/2015 3/31/2015 at 12:00 AM 03/31/2015
Misc
Corrective Action Required
03/31/2015
MAIN DISCONNECT- UFER GROUND NEEDS TO LAND ON THE NEUTRAL BUS OF THE DISCONNECT. CON NOT USE THE CABINET AS A BONDING JUMPER.
All Rough Inspection - Commercial Failed 3/31/2015 3/31/2015 at 12:00 AM 03/31/2015
Misc
Corrective Action Required
03/31/2015
ALL-ROUGH 1ST FLOOR- WALKED WIHT SHAWN, MARCUS, ALL TRADES. NUMEROUS ISSUES- -PREROCK FAILED - INCOMPLETE, PLUMNING NAIL PLATES MISSING, -FIRESSTOPPING BETWEEN UNIT AT FLOOR CEILING. -NO TRUSS REPAIRS FOR DRILLED FLOOR TRUSS -END UNITS"D" - ABOVE CEILING, INSULATION INSTALLED IN CEILING AND WALL OF UNIT WAS ASKED TO BE REMOVED WEEKS AGO. -HVAC TRUNK LINE INSTALLED IN THE CLOSET WITH NO ROCK ABOVE WAS ASKED TO BE REMOVED ALSO. - BATH FANS INCOMPLETE - MICRO VENT DUCT INCOMPLET IN CEILING NEEDS TO BE TERIMNATED TO WHERE THE MICRO IS -BLOCKING AND SHEETROCK AROUND DRYER VENTS IN SHEAR WALL IS INCOMPLETE AND NOT APPROVED -SEAL ALL PENETRATIONS IN CORRIDOR - 1000SQFT DRAFTSTOP AT UNITS WHERE OVER 1000SQFT -SECURITY BLOCKING ON ALL UNITS - STRAP CUT PLATES BOREDMORE THATN 50% INCOMPLET -PROTECT NM AT FURNACE ROOM WHERE STUDS AR TUNRED FLAT - SEAL IN FIREWALL AT STAIRS WHERE LVL FOR STAIR LANDING HAS BEEN CUT IN -SHOWER TRAPS INCOMPLETE -DO NOT COVER DO NOT INSULATE DO NOT SCHEDULE UNTIL ALL ITEMS ARE COMPLETE WILL NOT DO AM OR PM INSPECTION.
All Rough Inspection - Commercial Not Ready 4/1/2015 4/1/2015 at 12:00 AM 04/01/2015
Misc
Corrective Action Required
03/31/2015
ALL-ROUGH 1ST FLOOR- WALKED WIHT SHAWN, MARCUS, ALL TRADES. NUMEROUS ISSUES- -PREROCK FAILED - INCOMPLETE, PLUMNING NAIL PLATES MISSING, -FIRESSTOPPING BETWEEN UNIT AT FLOOR CEILING. -NO TRUSS REPAIRS FOR DRILLED FLOOR TRUSS -END UNITS"D" - ABOVE CEILING, INSULATION INSTALLED IN CEILING AND WALL OF UNIT WAS ASKED TO BE REMOVED WEEKS AGO. -HVAC TRUNK LINE INSTALLED IN THE CLOSET WITH NO ROCK ABOVE WAS ASKED TO BE REMOVED ALSO. - BATH FANS INCOMPLETE - MICRO VENT DUCT INCOMPLET IN CEILING NEEDS TO BE TERIMNATED TO WHERE THE MICRO IS -BLOCKING AND SHEETROCK AROUND DRYER VENTS IN SHEAR WALL IS INCOMPLETE AND NOT APPROVED -SEAL ALL PENETRATIONS IN CORRIDOR - 1000SQFT DRAFTSTOP AT UNITS WHERE OVER 1000SQFT -SECURITY BLOCKING ON ALL UNITS - STRAP CUT PLATES BOREDMORE THATN 50% INCOMPLET -PROTECT NM AT FURNACE ROOM WHERE STUDS AR TUNRED FLAT - SEAL IN FIREWALL AT STAIRS WHERE LVL FOR STAIR LANDING HAS BEEN CUT IN -SHOWER TRAPS INCOMPLETE -DO NOT COVER DO NOT INSULATE DO NOT SCHEDULE UNTIL ALL ITEMS ARE COMPLETE WILL NOT DO AM OR PM INSPECTION.
FIRST FLOOR
Corrective Action Required
04/01/2015
4-1-15see previous list- NOT READY- PLATE STRAPS INSTALLED ARE WITH SHEETROCK SCREWS. BATH VENTS INCOMPLETE INSULATION STILL NOT REMOVED PLUMBING RUNNING IN WRONG DIRECTION 1103 STRUCTURAL STRAP FOR CUT PLATES MORE THAN 50% INCOMPLETE INSULATION STILL IN IN CEILING AND WALL AT END UNIT. PLUMBING NOT SUPPORTED - MET WITH SHAWN AND TOLD HIM THE INSPECTION WAS NOT READY.
Electrical Service Inspection Partial 4/2/2015 4/2/2015 at 12:00 AM 04/02/2015
Misc
Corrective Action Required
03/31/2015
MAIN DISCONNECT- approved to release main on each side of building - sub panels are not approved.
In-wall Inspection Partial 4/3/2015 4/3/2015 at 12:00 AM 04/03/2015
Misc
Corrective Action Required
03/27/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- IT &ELECT ROOM OK TO ONE SIDE-BSM 1ST-all pre-rock behind shower ok except 1106,1101,1102 2ND- 3RD- 4TH-
FRAMING/STRUCTURE
Corrective Action Required
03/27/2015
SOFIT CEILING OVER DECK/ BALCONYS 1ST FLOOR SOUTH SIDE 2ND FLOOR SOUTH SIDE FIRE CAULKING ON INTERIOR. OK TO COVER
Rated Assembly Inspection Partial 4/6/2015 at 12:00 AM 04/06/2015
Misc
Partial Correction
03/19/2015
SECOND LAYOR OF FOR FIRST 3 FLOORS IN BOTH STAIRWELLS APPROVED
B705 FIRE WALLS
Partial Correction
04/06/2015
ALL WALLS BEHIND SHOWERS APPROVED
Above Ceiling Inspection Failed 4/7/2015 4/7/2015 at 12:00 AM 04/07/2015
FIRST FLOOR
Corrective Action Required
04/07/2015
Corridor-holes need caulked
SECOND FLOOR
Corrective Action Required
04/07/2015
corridor- holes need caulked and joist hanger nail holes filled
THIRD FLOOR
Corrective Action Required
04/07/2015
corridor- holes need caulked and joist hanger nail holes filled
FOURTH FLOOR
Corrective Action Required
04/07/2015
corridor - ok to install rock on bottome of truss in corridor
LOWER LEVEL
Corrective Action Required
04/07/2015
corridor-incomplete
Above Ceiling Inspection Partial 4/8/2015 4/8/2015 at 12:00 AM 04/08/2015
LOWER LEVEL
Corrective Action Required
04/07/2015
GARAGE - CORRIDOR PLUMIBNG PLATES NEEDED WHERE 3" DVW ENTERS WALL AND CEILING -SPRINKLER PIPING SCREWED TO FLOOR JOIST NEED TO MOVE OR LOWER FOR ROCK. - EAST END :WATER PIPING, 3" DWV , AGAINST FLOOR JOIST REMOVE TO INSTALL ROCK OR PROVIDE APPROVED FIRE COLLARS AND LISTING FOR INSPECTION.
FIRST FLOOR
Corrective Action Required
04/08/2015
HARD LID- CORRIDOR OK TO ROCK
SECOND FLOOR
Corrective Action Required
04/08/2015
CORRIDOR OR TO ROCK CEILING
THIRD FLOOR
Corrective Action Required
04/08/2015
CORRIDOR OR TO ROCK CEILING
FIRST FLOOR
Corrective Action Required
04/08/2015
CORRIDOR OR TO ROCK CEILING- UNIT CEILING - OK TO ROCK RIBBON STRIP FOR DUCTS WHERE DROP CEILING ARE.
All Rough Inspection - Commercial Partial 4/8/2015 4/8/2015 at 12:00 AM 04/08/2015
Misc
Resolved
04/08/2015
FIRST FLOOR
Corrective Action Required
04/01/2015
UNIT "D" INSTALL DUCT AND DAMPER FURNACE ROOM CEILING NEED ROCK AND TRAP LOWERED OR FLOOR CEILING ASSEMBLY LOWERED -SECURITY BLOCKING CORRIDOR WALLS - COMPLETE SHOWER TRAPS WHEN SHOWERS ARE INSTALLED. OK TO INSULATE 1ST FLOOR ONLY.
In-wall Inspection Partial 4/8/2015 4/8/2015 at 12:00 AM 04/08/2015
Misc
Corrective Action Required
04/03/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- IT &ELECT ROOM OK TO ONE SIDE-BSM 1ST-PRE-ROCK SHOWER OK TO COVER 2ND-PRE-ROCK SHOWER OK TO COVER 3RD-PRE-ROCK SHOWER OK TO COVER 4TH-PRE-ROCK SHOWER OK TO COVER
FRAMING/STRUCTURE
Corrective Action Required
04/03/2015
SOFIT CEILING OVER DECK/ BALCONYS OK TO COVER NEED TO CHECK BLOCKING OVER GARAGES TO SOFIT.
All Rough Inspection - Commercial Partial 4/9/2015 4/9/2015 at 12:00 AM 04/09/2015
FIRST FLOOR
Corrective Action Required
04/08/2015
UNIT "D" INSTALL DUCT AND DAMPER FURNACE ROOM CEILING NEED ROCK AND TRAP LOWERED OR FLOOR CEILING ASSEMBLY LOWERED -SECURITY BLOCKING CORRIDOR WALLS - COMPLETE SHOWER TRAPS WHEN SHOWERS ARE INSTALLED. OK TO INSULATE 1ST FLOOR ONLY.
SECOND FLOOR
Partial Correction
04/09/2015
OK TO COVER WALLS AND CEILINGS AT 2ND FLOOR EXCEPT 1) LEAVE CEILINGS OPEN AT SHOWER TRAPS YET TO BE INSTALLED 2) BATH VENT FAN DUCTING AND DAMPERS SUBJECT TO APPROVAL BY MARK HARDING
All Rough Inspection - Commercial Partial 4/10/2015 4/10/2015 at 12:00 AM 04/10/2015
FIRST FLOOR
Corrective Action Required
04/09/2015
UNIT "D" INSTALL DUCT AND DAMPER FURNACE ROOM CEILING NEED ROCK AND TRAP LOWERED OR FLOOR CEILING ASSEMBLY LOWERED -SECURITY BLOCKING CORRIDOR WALLS - COMPLETE SHOWER TRAPS WHEN SHOWERS ARE INSTALLED. OK TO INSULATE 1ST FLOOR ONLY.
SECOND FLOOR
Partial Correction
04/09/2015
OK TO COVER WALLS AND CEILINGS AT: 2ND FLOOR 3RD FLOOR EXCEPT 1) LEAVE CEILINGS OPEN AT SHOWER TRAPS YET TO BE INSTALLED 2) BATH VENT FAN DUCTING AND DAMPERS SUBJECT TO APPROVAL BY MARK HARDING
All Rough Inspection - Commercial Partial 4/10/2015 at 12:00 AM 04/10/2015
FIRST FLOOR
Corrective Action Required
04/10/2015
UNIT "D" INSTALL DUCT AND DAMPER FURNACE ROOM CEILING NEED ROCK AND TRAP LOWERED OR FLOOR CEILING ASSEMBLY LOWERED -SECURITY BLOCKING CORRIDOR WALLS - COMPLETE SHOWER TRAPS WHEN SHOWERS ARE INSTALLED. OK TO INSULATE 1ST FLOOR ONLY.
SECOND FLOOR
Partial Correction
04/10/2015
OK TO COVER WALLS AND CEILINGS AT 2ND FLOOR EXCEPT 1) LEAVE CEILINGS OPEN AT SHOWER TRAPS YET TO BE INSTALLED 2) BATH VENT FAN DUCTING AND DAMPERS SUBJECT TO APPROVAL BY MARK HARDING
THIRD FLOOR
Corrective Action Required
04/10/2015
OK TO COVER WALLS AND CEILINGS AT 3RD FLOOR EXCEPT 1) LEAVE CEILINGS OPEN AT SHOWER TRAPS YET TO BE INSTALLED 2) BATH VENT FAN DUCTING AND DAMPERS SUBJECT TO APPROVAL BY MARK HARDING
Rated Assembly Inspection Failed 4/13/2015 4/13/2015 at 12:00 AM 04/13/2015
Misc
Partial Correction
04/06/2015
SECOND LAYER OF FOR FIRST 3 FLOORS IN BOTH STAIRWELLS APPROVED
B705 FIRE WALLS
Partial Correction
04/06/2015
ALL WALLS BEHIND SHOWERS APPROVED; CORRIDOR CEILING- ALL LEVELS FAILED, HOLES TO BIG , NOT CAULKED, NILLING SCREWS, AND SCREW PATTERN , NO BACKING AT ROCK SPLICES.
FIRST FLOOR
Corrective Action Required
04/13/2015
SECOND FLOOR
Corrective Action Required
04/13/2015
THIRD FLOOR
Corrective Action Required
04/13/2015
FOURTH FLOOR
Corrective Action Required
04/13/2015
Above Ceiling Inspection Partial 4/14/2015 at 12:00 AM 04/14/2015
LOWER LEVEL
Corrective Action Required
04/08/2015
GARAGE - CORRIDOR -SPRINKLER PIPING SCREWED TO FLOOR JOIST NEED TO MOVE OR LOWER FOR ROCK **.--OK TO ROCK 2ND LAYER UPTHI THIS POINT OUTSIDE UNIT#5 STORAGE. - EAST END :WATER PIPING, 3" DWV , AGAINST FLOOR JOIST REMOVE TO INSTALL ROCK OR PROVIDE APPROVED FIRE COLLARS AND LISTING FOR INSPECTION.
FIRST FLOOR
Corrective Action Required
04/08/2015
HARD LID- CORRIDOR , 1ST LAYER OK
SECOND FLOOR
Corrective Action Required
04/08/2015
CORRIDOR OR TO ROCK CEILING
THIRD FLOOR
Corrective Action Required
04/08/2015
CORRIDOR OR TO ROCK CEILING
FIRST FLOOR
Corrective Action Required
04/08/2015
CORRIDOR OR TO ROCK CEILING- UNIT CEILING - OK TO ROCK RIBBON STRIP FOR DUCTS WHERE DROP CEILING ARE.
Rated Assembly Inspection Partial 4/14/2015 4/14/2015 at 12:00 AM 04/14/2015
Misc
Partial Correction
04/13/2015
SECOND LAYER OF FOR FIRST 3 FLOORS IN BOTH STAIRWELLS APPROVED
B705 FIRE WALLS
Partial Correction
04/13/2015
ALL WALLS BEHIND SHOWERS APPROVED;2ND LAYER AT SHOWERS APPROVED CORRIDOR CEILING- ALL LEVELS FAILED, HOLES TO BIG , NOT CAULKED, NILLING SCREWS, AND SCREW PATTERN , NO BACKING AT ROCK SPLICES.
FIRST FLOOR
Corrective Action Required
04/13/2015
SECOND FLOOR
Corrective Action Required
04/13/2015
THIRD FLOOR
Corrective Action Required
04/13/2015
FOURTH FLOOR
Corrective Action Required
04/13/2015
All Rough Inspection - Commercial Partial 4/17/2015 4/16/2015 at 12:00 AM 04/16/2015
FIRST FLOOR
Corrective Action Required
04/10/2015
UNIT "D" INSTALL DUCT AND DAMPER FURNACE ROOM CEILING NEED ROCK AND TRAP LOWERED OR FLOOR CEILING ASSEMBLY LOWERED
SECOND FLOOR
Partial Correction
04/10/2015
OK TO COVER WALLS AND CEILINGS AT 2ND FLOOR EXCEPT
Misc
Corrective Action Required
04/16/2015
THIRD FLOOR
Corrective Action Required
04/16/2015
OK TO ROCK UNITS AND WALLS TUB TRAPS INSPECTED
LOWER LEVEL
Corrective Action Required
04/16/2015
FOURTH FLOOR
Corrective Action Required
04/16/2015
All Rough Inspection - Commercial Partial 4/17/2015 at 12:00 AM 04/17/2015
FIRST FLOOR
Corrective Action Required
04/16/2015
UNIT "D" INSTALL DUCT AND DAMPER FURNACE ROOM CEILING NEED ROCK AND TRAP LOWERED OR FLOOR CEILING ASSEMBLY LOWERED
SECOND FLOOR
Partial Correction
04/16/2015
OK TO COVER WALLS AND CEILINGS AT 2ND FLOOR EXCEPT
Misc
Corrective Action Required
04/16/2015
THIRD FLOOR
Corrective Action Required
04/16/2015
OK TO ROCK UNITS AND WALLS TUB TRAPS INSPECTED
LOWER LEVEL
Corrective Action Required
04/16/2015
FOURTH FLOOR
Corrective Action Required
04/16/2015
OK to rock ceiling only for mechanical drops and soffits
Rated Assembly Inspection Partial 4/20/2015 4/20/2015 at 12:00 AM 04/20/2015
Misc
Resolved
04/20/2015
SECOND LAYER OF FOR FIRST 3 FLOORS IN BOTH STAIRWELLS APPROVED
B705 FIRE WALLS
Carried Forward
04/20/2015
ELEVATOR SHAFT- 1ST OK 2ND OK FROM 1-4TH FLOOR NEED MORE NAILS OVER 4TH FLOOR BSMT LEVEL NEED NAILED AT BOTTOM ROW. CORRIDOR- LOWER LEVEL NEEDS INSPECTED SPRINKLER LINE IN 2ND LAYER, COVERED 1ST LAYER AT WEST END WITHOUT INSPECTION.
FIRST FLOOR
Corrective Action Required
04/14/2015
ROOMS- ALL EXEPT 1103,1106,1112 CORRIDOR- CAULK EDGES
SECOND FLOOR
Corrective Action Required
04/14/2015
CORRIDOR- CAULK 2ND LAYER
THIRD FLOOR
Corrective Action Required
04/14/2015
CORRIDOR-2ND OK
FOURTH FLOOR
Corrective Action Required
04/14/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND
Rated Assembly Inspection Partial 4/22/2015 4/22/2015 at 12:00 AM 04/22/2015
FIRST FLOOR
Corrective Action Required
04/20/2015
ROOMS- ALL EXEPT 1103,1106,1112 CORRIDOR- CAULK EDGES- USED FOAM,
SECOND FLOOR
Corrective Action Required
04/20/2015
CORRIDOR- CAULK 2ND LAYER- USED FOAM FOR GAPS , PROVIDE LISTING OR CUT BACK ROCK AND FIT TIGHT
THIRD FLOOR
Corrective Action Required
04/20/2015
CORRIDOR-2ND LAYER OK
FOURTH FLOOR
Corrective Action Required
04/20/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND ROOMS - CEILING OF 4TH FLOOR OK EXECPT 1406 GAP IN ROCK
LOWER LEVEL
Corrective Action Required
04/22/2015
RATED CEILING - OK TO ROCK 2ND LAYER OVER WHERE SPRINKLER HEAD WAS REMOVED. SEAL GAP AROUND HEAD FAR WEST CLOSET AREA. BOTH LAYERS
B705 FIRE WALLS
Corrective Action Required
04/22/2015
1ST LAYER CORRIDOR AND STAIR WALL OK 1-4 ON EAST STAIR WAY 4TH FLOOR WEST STAIRS AT LADDER TO ROOF NEEDS INSPECTED. ELEVATOR 2ND LAYER OK, 2ND LAYER OF CEILING ELEVATOR OK
All Rough Inspection - Commercial Partial 4/22/2015 4/22/2015 at 12:00 AM 04/22/2015
FIRST FLOOR
Corrective Action Required
04/17/2015
UNIT "D" INSTALL DUCT AND DAMPER FURNACE ROOM CEILING NEED ROCK AND TRAP LOWERED OR FLOOR CEILING ASSEMBLY LOWERED
SECOND FLOOR
Partial Correction
04/17/2015
OK TO COVER WALLS AND CEILINGS AT 2ND FLOOR EXCEPT
Misc
Corrective Action Required
04/17/2015
THIRD FLOOR
Corrective Action Required
04/17/2015
OK TO ROCK UNITS AND WALLS TUB TRAPS INSPECTED
LOWER LEVEL
Corrective Action Required
04/17/2015
LOWER GARAGE LEVEL- GARAGE CEILING OK TO INSULATE AND INSTALL RC CHANNEL. WALL HAVE NOT BEEN INSPECTED, NOR THE CORRIDOR WALLS.
FOURTH FLOOR
Corrective Action Required
04/17/2015
OK to rock ceiling only for mechanical drops and soffits
Rated Assembly Inspection Partial 4/24/2015 4/24/2015 at 12:00 AM 04/24/2015
FIRST FLOOR
Corrective Action Required
04/22/2015
1ST LAYER
SECOND FLOOR
Corrective Action Required
04/22/2015
CORRIDOR-1ST OK
THIRD FLOOR
Corrective Action Required
04/22/2015
CORRIDOR-2ND LAYER OK
FOURTH FLOOR
Corrective Action Required
04/22/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND ROOMS - CEILING OF 4TH FLOOR OK EXECPT 1406 GAP IN ROCK
LOWER LEVEL
Corrective Action Required
04/22/2015
RATED CEILING - 2ND LAYER OK , EXCEPT OUTSIDE IT ROOM. EAST END OF CORRIDOR NEEDS SHEETROCKED WHEN PIPES ARE DROPED FROM CEILING.
B705 FIRE WALLS
Corrective Action Required
04/22/2015
1ST LAYERS CORRIDORS APPROVED 2ND LAYER -ELEVATOR SHAFT EXTERIOR 2ND LAYER APPROVED 1,2,3 FLOORS ELEVATOR- 3RD LAYER CEILING NEED FIXEDS AND NAILED NORTH STAIR-2ND LAYER AT EACH LEVEL OK 1 OF 4 CEILING APPROVED SOUTH STAIR- OK TO INSTALL 1 OF 4 LAYER ON CEILING
Rated Assembly Inspection Partial 4/27/2015 4/27/2015 at 12:00 AM 04/27/2015
FIRST FLOOR
Corrective Action Required
04/24/2015
1ST LAYER
SECOND FLOOR
Corrective Action Required
04/24/2015
CORRIDOR-1ST OK 2ND LAYER AT 2HR WALLS EXTERIOR SIDE IT ROOM FAILED
THIRD FLOOR
Corrective Action Required
04/24/2015
2ND LAYER AT 2HR WALLS EXTERIOR SIDE SOUTH STAIRS- 2ND LAYER OK
FOURTH FLOOR
Corrective Action Required
04/24/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND ROOMS - 1ST LAYER STAIR WALLS ABOVE 4TH FLOOR -1ST LAYER STAIRS CEILING - -
LOWER LEVEL
Corrective Action Required
04/24/2015
RATED CEILING - 2ND LAYER OK , EXCEPT OUTSIDE IT ROOM. EAST END OF CORRIDOR NEEDS SHEETROCKED WHEN PIPES ARE DROPED FROM CEILING. ALCOVES IN CORRIDOR NEEDS 1ST LAYER (INSTALLED CHANNEL ON CEILINGS NEEDS REMOVED)
Rated Assembly Inspection Failed 4/29/2015 4/29/2015 at 12:00 AM 04/29/2015
FIRST FLOOR
Corrective Action Required
04/27/2015
1ST LAYER
SECOND FLOOR
Corrective Action Required
04/27/2015
CORRIDOR-1ST OK 2ND LAYER AT 2HR WALLS EXTERIOR SIDE IT ROOM FAILED
THIRD FLOOR
Corrective Action Required
04/27/2015
2ND LAYER AT 2HR WALLS EXTERIOR SIDE SOUTH STAIRS- 2ND LAYER OK
FOURTH FLOOR
Corrective Action Required
04/27/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND ROOMS - 1ST LAYER STAIR WALLS ABOVE 4TH FLOOR -1ST LAYER STAIRS CEILING - -
LOWER LEVEL
Corrective Action Required
04/27/2015
RATED CEILING - 2ND LAYER OK , EXCEPT OUTSIDE IT ROOM. EAST END OF CORRIDOR NEEDS SHEETROCKED WHEN PIPES ARE DROPED FROM CEILING. ALCOVES IN CORRIDOR NEEDS 1ST LAYER (INSTALLED CHANNEL ON CEILINGS NEEDS REMOVED)
Misc
Corrective Action Required
04/29/2015
1ST FLOOR CORRIDOR OK, "D" UNIT OK 2ND FLOOR IT ROOM 6" DUCT TO FLOOR SPACE NEEDS FIXED 2ND FLOOR "D" UNIT 3RD FLOOR CAULK PLUMBING LINES TO FLOOR SPACE 3RD FLOOR OK 4TH DRYER VENTS NEED FIXED AND CAULKED
Rated Assembly Inspection Partial 4/30/2015 4/30/2015 at 12:00 AM 04/30/2015
FIRST FLOOR
Corrective Action Required
04/29/2015
1ST LAYER
SECOND FLOOR
Corrective Action Required
04/29/2015
CORRIDOR-1ST OK 2ND LAYER AT 2HR WALLS EXTERIOR SIDE IT ROOM FAILED
THIRD FLOOR
Corrective Action Required
04/29/2015
2ND LAYER AT 2HR WALLS EXTERIOR SIDE SOUTH STAIRS- 2ND LAYER OK
FOURTH FLOOR
Corrective Action Required
04/29/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND ROOMS - 1ST LAYER STAIR WALLS ABOVE 4TH FLOOR -1ST LAYER STAIRS CEILING - -
LOWER LEVEL
Corrective Action Required
04/29/2015
RATED CEILING - 2ND LAYER OK , EXCEPT OUTSIDE IT ROOM. EAST END OF CORRIDOR NEEDS SHEETROCKED WHEN PIPES ARE DROPED FROM CEILING. ALCOVES IN CORRIDOR NEEDS 1ST LAYER (INSTALLED CHANNEL ON CEILINGS NEEDS REMOVED)
Misc
Corrective Action Required
04/29/2015
1ST FLOOR CORRIDOR OK, "D" UNIT OK 2ND FLOOR IT ROOM 6" DUCT TO FLOOR SPACE NEEDS FIXED 2ND FLOOR "D" UNIT 3RD FLOOR CAULK PLUMBING LINES TO FLOOR SPACE 3RD FLOOR OK 4TH DRYER VENTS ok
Rated Assembly Inspection Partial 5/1/2015 5/1/2015 at 12:00 AM 05/01/2015
FIRST FLOOR
Corrective Action Required
04/30/2015
1ST LAYER
SECOND FLOOR
Corrective Action Required
04/30/2015
CORRIDOR-1ST OK 2ND LAYER AT 2HR WALLS EXTERIOR SIDE IT ROOM FAILED
THIRD FLOOR
Corrective Action Required
04/30/2015
2ND LAYER AT 2HR WALLS EXTERIOR SIDE SOUTH STAIRS- 2ND LAYER OK
FOURTH FLOOR
Corrective Action Required
04/30/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND ROOMS - 1ST LAYER STAIR WALLS ABOVE 4TH FLOOR -1ST LAYER STAIRS CEILING - -
LOWER LEVEL
Corrective Action Required
04/30/2015
RATED CEILING - 2ND LAYER OK , EXCEPT OUTSIDE IT ROOM. EAST END OF CORRIDOR NEEDS SHEETROCKED WHEN PIPES ARE DROPED FROM CEILING. ALCOVES IN CORRIDOR NEEDS 1ST LAYER (INSTALLED CHANNEL ON CEILINGS NEEDS REMOVED)
Misc
Corrective Action Required
04/30/2015
1ST FLOOR CORRIDOR OK, "D" UNIT OK 2ND FLOOR IT ROOM 6" DUCT TO FLOOR SPACE NEEDS FIXED 2ND FLOOR "D" UNIT 3RD FLOOR CAULK PLUMBING LINES TO FLOOR SPACE 3RD FLOOR OK 4TH DRYER VENTS ok BSMT - 1ST OF 2HR WALLS 3RD OF 4 AT EAST STAIR TOWER IT ROOMS 2ND
Rated Assembly Inspection Partial 5/4/2015 5/4/2015 at 12:00 AM 05/04/2015
Misc
Partial Correction
05/04/2015
-2nd LAYER LOWER LEVEL CORRIDOR CEILING SCREW ONLY -2ND LAYER SCREW LOWER LEVEL CORRIDOR WALLS -GARAGES 1,2,3 FIRST LAYER APPROVED -2ND LAYER LOWER LEVEL 2 HOUR CONDITONS ROOMS - EAST AND WEST TOWER 4TH FLOOR 4TH LAYER LID APPROVED -WALLS BETWEEN UNITS ONLY 4TH FLOOR
Rated Assembly Inspection Partial 5/5/2015 5/5/2015 at 12:00 AM 05/05/2015
Misc
Partial Correction
05/05/2015
-2nd LAYER LOWER LEVEL CORRIDOR CEILING SCREW ONLY -2ND LAYER SCREW LOWER LEVEL CORRIDOR WALLS -GARAGES 1,2,3 FIRST LAYER APPROVED -2ND LAYER LOWER LEVEL 2 HOUR CONDITONS ROOMS - EAST AND WEST TOWER 4TH FLOOR 4TH LAYER LID APPROVED -WALLS BETWEEN UNITS ONLY 4TH FLOOR
Misc
Partial Correction
05/05/2015
WALLS & CEILINGS @ 1ST FLR STORAGE ROOMS: GWB OK TO TAPE, MUD AND FIRE-SEAL. ALL FIRE SEALING AND FIRE ISOLATION OF PVC PIPE, ETC SUBJECT TO APPROVAL.
Rated Assembly Inspection Partial 5/6/2015 5/6/2015 at 12:00 AM 05/06/2015
FIRST FLOOR
Corrective Action Required
05/01/2015
1ST LAYER
SECOND FLOOR
Corrective Action Required
05/01/2015
CORRIDOR-1ST OK 2ND LAYER AT 2HR WALLS EXTERIOR SIDE IT ROOM FAILED
THIRD FLOOR
Corrective Action Required
05/01/2015
2ND LAYER AT 2HR WALLS EXTERIOR SIDE SOUTH STAIRS- 2ND LAYER OK
FOURTH FLOOR
Corrective Action Required
05/01/2015
CORRIDOR 1,2, OK CAULK GAPS ON 2ND ROOMS - 1ST LAYER STAIR WALLS ABOVE 4TH FLOOR -1ST LAYER STAIRS CEILING - -
LOWER LEVEL
Corrective Action Required
05/01/2015
RATED CEILING - 2ND LAYER OK , EXCEPT OUTSIDE IT ROOM. EAST END OF CORRIDOR NEEDS SHEETROCKED WHEN PIPES ARE DROPED FROM CEILING. ALCOVES IN CORRIDOR NEEDS 1ST LAYER (INSTALLED CHANNEL ON CEILINGS NEEDS REMOVED)
Misc
Corrective Action Required
05/01/2015
1ST FLOOR CORRIDOR OK, "D" UNIT OK 2ND FLOOR IT ROOM 6" DUCT TO FLOOR SPACE NEEDS FIXED 2ND FLOOR "D" UNIT 3RD FLOOR CAULK PLUMBING LINES TO FLOOR SPACE 3RD FLOOR OK 4TH DRYER VENTS ok BSMT - 1ST OF 2HR WALLS 3RD OF 4 AT EAST STAIR TOWER 4-WEST,3RD EAST TOWER IT ROOMS 2ND
Rated Assembly Inspection Partial 5/7/2015 5/7/2015 at 12:00 AM 05/07/2015
Misc
Partial Correction
05/06/2015
-2nd LAYER LOWER LEVEL CORRIDOR CEILING SCREW ONLY -2ND LAYER SCREW LOWER LEVEL CORRIDOR WALLS -GARAGES 1,2,3 FIRST LAYER APPROVED -2ND LAYER LOWER LEVEL 2 HOUR CONDITONS ROOMS - EAST AND WEST TOWER 4TH FLOOR 4TH LAYER LID APPROVED -WALLS BETWEEN UNITS ONLY 4TH FLOOR
Misc
Partial Correction
05/06/2015
WALLS & CEILINGS @ 1ST FLR STORAGE ROOMS: GWB OK TO TAPE, MUD AND FIRE-SEAL. ALL FIRE SEALING AND FIRE ISOLATION OF PVC PIPE, ETC SUBJECT TO APPROVAL.
Rated Assembly Inspection Partial 5/8/2015 5/8/2015 at 12:00 AM 05/08/2015
Misc
Corrective Action Required
05/08/2015
WEST STAIR- 3RD LAYER CHANNEL INSPECTED
Rated Assembly Inspection Partial 5/11/2015 5/11/2015 at 12:00 AM 05/11/2015
Misc
Partial Correction
05/07/2015
-2nd LAYER LOWER LEVEL CORRIDOR CEILING SCREW ONLY -2ND LAYER SCREW LOWER LEVEL CORRIDOR WALLS -GARAGES 1,2,3 FIRST LAYER APPROVED -2ND LAYER LOWER LEVEL 2 HOUR CONDITONS ROOMS - EAST AND WEST TOWER 4TH FLOOR 4TH LAYER LID APPROVED -WALLS BETWEEN UNITS ONLY 4TH FLOOR elevator equipment room
Misc
Partial Correction
05/07/2015
WALLS & CEILINGS @ 1ST FLR STORAGE ROOMS: GWB OK TO TAPE, MUD AND FIRE-SEAL. ALL FIRE SEALING AND FIRE ISOLATION OF PVC PIPE, ETC SUBJECT TO APPROVAL.
Above Ceiling Inspection Not Ready 5/11/2015 5/11/2015 at 12:00 AM 05/11/2015
LOWER LEVEL
Corrective Action Required
04/14/2015
GARAGE - CORRIDOR -SPRINKLER PIPING SCREWED TO FLOOR JOIST NEED TO MOVE OR LOWER FOR ROCK **.--OK TO ROCK 2ND LAYER UPTHI THIS POINT OUTSIDE UNIT#5 STORAGE. - EAST END :WATER PIPING, 3" DWV , AGAINST FLOOR JOIST REMOVE TO INSTALL ROCK OR PROVIDE APPROVED FIRE COLLARS AND LISTING FOR INSPECTION.
FIRST FLOOR
Corrective Action Required
04/14/2015
HARD LID- CORRIDOR , 1ST LAYER OK
SECOND FLOOR
Corrective Action Required
04/14/2015
CORRIDOR OR TO ROCK CEILING
THIRD FLOOR
Corrective Action Required
04/14/2015
CORRIDOR OR TO ROCK CEILING
FIRST FLOOR
Corrective Action Required
04/14/2015
CORRIDOR OR TO ROCK CEILING- UNIT CEILING - OK TO ROCK RIBBON STRIP FOR DUCTS WHERE DROP CEILING ARE.
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
05/11/2015
not ready for inspection all floors for above ceiling corridor-above ceiling. 1st 2nd 3dr 4th ground
Rated Assembly Inspection Partial 5/12/2015 5/12/2015 at 12:00 AM 05/12/2015
Misc
Corrective Action Required
05/11/2015
WEST STAIR- 3RD LAYER CHANNEL INSPECTED 3RD LAYER - IT ROOM LID
Underground Electrical Inspection - Commercial Partial 5/13/2015 5/13/2015 at 12:00 AM 05/13/2015
Misc
Corrective Action Required
05/13/2015
light pole base-#5 bases clubhouse and building #1
Above Ceiling Inspection Failed 5/13/2015 5/13/2015 at 12:00 AM 05/13/2015
LOWER LEVEL
Corrective Action Required
05/11/2015
GARAGE - CORRIDOR north stair replace rock where sprinkler line was moved caulk all penetrartions in corridor ceiling
FIRST FLOOR
Corrective Action Required
05/11/2015
D" unit ok to cover ceiling
SECOND FLOOR
Corrective Action Required
05/11/2015
CORRIDOR ceiling failed holes cut in both layers holes cut in D unit ceiling
THIRD FLOOR
Corrective Action Required
05/11/2015
3rd floor corridor ok to rock D unit ok to cover
FOURTH FLOOR
Corrective Action Required
05/11/2015
CORRIDOR OR TO ROCK CEILING- UNIT CEILING - OK TO ROCK RIBBON STRIP FOR DUCTS WHERE DROP CEILING ARE. provide listing on 6" duct for penetrating ceiling 2x's provide damper each side of duct penetrating 1hr wall 2x's
THE FOLLOWING AREAS ARE APPROVED
Resolved
05/13/2015
not ready for inspection all floors for above ceiling corridor-above ceiling. 1st 2nd 3dr 4th ground
Rated Assembly Inspection Failed 5/13/2015 5/13/2015 at 12:00 AM 05/13/2015
Misc
Corrective Action Required
05/12/2015
WEST STAIR- 3RD LAYER CHANNEL INSPECTED 3RD LAYER - IT ROOM LID replace cut north stairs bsmt level where sprinkler line was moved
Above Ceiling Inspection Partial 5/18/2015 5/18/2015 at 12:00 AM 05/19/2015
LOWER LEVEL
Corrective Action Required
05/13/2015
GARAGE - CORRIDOR
FIRST FLOOR
Corrective Action Required
05/13/2015
COMPLETE
SECOND FLOOR
Corrective Action Required
05/13/2015
CORRIDOR ceiling failed holes cut in both layers CUT OUT AND PATCH , SHAWN -NICK
THIRD FLOOR
Corrective Action Required
05/13/2015
3rd floor corridor ok to rock
FOURTH FLOOR
Corrective Action Required
05/13/2015
DROP DOWNS AND CORRIDOR OK TO ROCK
Misc
Corrective Action Required
05/18/2015
FURNACE ROOMS ALL LEVELS, IT ROOMS , ELEVATOR ROOMS, ALL NEED INSPECTED FOR FINAL COVER AND CAULK. 2ND FLOOR CORRIDOR PATCH.
Above Ceiling Inspection Partial 5/19/2015 at 12:00 AM 05/19/2015
Misc
Corrective Action Required
05/19/2015
SEE INSPECTION 5-18 FOR 5-19 ITEMS WOULD NOT TRANSFER
Rated Assembly Inspection Partial 5/20/2015 5/20/2015 at 12:00 AM 05/20/2015
Misc
Corrective Action Required
05/20/2015
2ND FLOOR CORRIDOR PATCH EAST END CUT OUT REPLACE TO 1ST LAYER
Rated Assembly Inspection Partial 5/21/2015 at 12:00 AM 05/21/2015
Misc
Corrective Action Required
05/13/2015
2n floor coridor 4th floor plemumns
Miscellaneous Inspection Failed 5/27/2015 5/27/2015 at 12:00 AM 05/27/2015
Misc
Corrective Action Required
05/27/2015
PRE FINAL 1ST FLOOR- ELECTRICAL, BATH FANS, SMOKES,FURN ROOM, WATER HEATER, PREFINAL-6-5 1ST FLOOR PARTIAL INCOMPLETE
Miscellaneous Inspection Failed 6/5/2015 at 12:00 AM 06/05/2015
Misc
Corrective Action Required
05/27/2015
PRE FINAL 1ST FLOOR- ELECTRICAL, BATH FANS, SMOKES,FURN ROOM, WATER HEATER, PREFINAL-6-5 1ST FLOOR PARTIAL INCOMPLETE
Rated Assembly Inspection Partial 6/4/2015 6/5/2015 at 12:00 AM 06/05/2015
Misc
Corrective Action Required
05/21/2015
2ND LAYER ELEVATOR WALLS CORRIDOR SIDES BUILD IN.
Miscellaneous Inspection Failed 6/9/2015 6/9/2015 at 12:00 AM 06/09/2015
Misc
Corrective Action Required
06/09/2015
BUILDING #1 PRE-FINAL NOT COMPLETE LIST GARAGE LEVEL-EAST TO WEST- 1-HOLES IN CEILING 2,3,4,5, 6-ACCESS PANEL IN CEILING STORAGE ROOMS- 1,2,3,4 CAULK PLUMBING STACKS WHERE REQURIED 7,8,9 CAULK. ELEVATOR EQUIPMENT ROOM-OUTLET COVER, CAULK, LABEL DISCONNECTS FIRE PILLOWS CONDUIT BETWEEN FLOORS ALL, Fire extinguishers all corridors. Label all doors , floor leves, equipment rooms, unit rooms, north stair tower label gate. 1ST FLOOR-UNITS 1101 KIT ELECT, SINK 1102- KIT ELECT, SINK 1103- SINKS KIT. 1106-CHECK ALL 1105- KIT SINK 1108 - KIT ELECT, SINK 1110- PATIO BUBBLE COVER, ACCESS PANEL FURNACE 1112-PATIO GFCI 1109 CHECK ALL FLOOR#2 CHECK ALL- numerous breakers off throughout units for inspection. --Install all fire extinguishers, seal IT rooms. Caulk elevator ground floor penetrations. Gfci’s west ground level at panel. Sprinkler room heater. Check room top units and gfci’s
Occupancy Inspection - Planning Temporary C of O 06/11/2015
Corrective Action Required
06/11/2015
LANDSCAPING. Complete landscaping per the approved landscape plan.
Corrective Action Required
06/11/2015
MISCELLANEOUS EXTERIOR WORK. - The building's stone base shall be completed per the approved building elevations. The remaining side left to be completed is on the west building elevation. Completion of the work was in process at the time of inspeciton. - Installation of rain gutters was in the process of being completed on the north building elevation at the time of inspection. - Broken windows were in the process of being replaced at the time of inspection.
Sprinkler - Flow Test Passed 6/10/2015 at 12:00 AM 06/11/2015
Alarm Test Failed 6/10/2015 at 12:00 AM 06/11/2015
Occupancy Inspection - Fire Not Ready 6/11/2015 6/11/2015 at 12:00 AM 06/11/2015
Occupancy Inspection - Codes Commercial Failed 6/11/2015 6/11/2015 at 12:00 AM 06/11/2015
Misc
Corrective Action Required
06/11/2015
- SEE OTHER DEPARTMENTS FOR APPROVAL CAULK ALL FLOOR CEILING PENETRATIONS ON IT,MECHANICAL,ELECTRICAL, ELEVATOR ROOMS. INSTALL ALL REQURIED SIGNAGE. -CLEAN ROOF TOP. UNITS APPROVED 1ST FLOOR -
Alarm Test Partial 6/12/2015 at 12:00 AM 06/12/2015
Occupancy Inspection - Fire Temporary C of O 6/12/2015 at 12:00 AM 06/12/2015
Occupancy Inspection - Codes Commercial Temporary C of O 6/12/2015 at 12:00 AM 06/15/2015
Misc
Corrective Action Required
06/11/2015
APPROVED FOR TCO - SEE OTHER DEPARTMENTS FOR APPROVAL UNITS APPROVED 1ST FLOOR -1101,1102 ONLY 2 UNITS WITH OUT KITCHEN CABINETS AND COUNTERS. 2ND FLOOR-2 EAST END UNITS- OTHER OK NO INSPECTION ON 3,4 FLOORS NOT TO OCCUPY ANY UNITS 3-4 FLOORS ALL STAIRWAYS AND CORRIDORS MUST REMAIN CLEAR FOR OCCUPANTS.
Corrective Action Required
06/12/2015
Occupancy Inspection - Codes Commercial Failed 6/15/2015 at 12:00 AM 06/15/2015
Misc
Corrective Action Required
06/15/2015
APPROVED FOR TCO - SEE OTHER DEPARTMENTS FOR APPROVAL UNITS APPROVED 1ST FLOOR -1101,1102 ONLY 2 UNITS WITH OUT KITCHEN CABINETS AND COUNTERS. 2ND FLOOR-2 EAST END UNITS- OTHER OK NO INSPECTION ON 3,4 FLOORS NOT TO OCCUPY ANY UNITS 3-4 FLOORS ALL STAIRWAYS AND CORRIDORS MUST REMAIN CLEAR FOR OCCUPANTS.
Misc
Corrective Action Required
06/15/2015
Occupancy inspection for 1078 3351 sw kesselr. 1st floor model was complete, 1102 no cabinets or counter/sink. 2nd floor was incomplete 2-end units. 1202 faucet was in but drainage was incomplete. 1201 same
Occupancy Inspection - Codes Commercial Not Ready 6/22/2015 6/22/2015 at 12:00 AM 06/22/2015
Misc
Corrective Action Required
06/15/2015
APPROVED FOR TCO - SEE OTHER DEPARTMENTS FOR APPROVAL UNITS APPROVED 1ST FLOOR -1101,1102 ONLY 2 UNITS WITH OUT KITCHEN CABINETS AND COUNTERS. 2ND FLOOR-2 EAST END UNITS- OTHER OK NO INSPECTION ON 3,4 FLOORS NOT TO OCCUPY ANY UNITS 3-4 FLOORS ALL STAIRWAYS AND CORRIDORS MUST REMAIN CLEAR FOR OCCUPANTS.
Misc
Corrective Action Required
06/15/2015
Occupancy inspection for 1078 3351 sw kesselr. 1st floor model was complete, 1102 no cabinets or counter/sink. 2nd floor was incomplete 2-end units. 1202 faucet was in but drainage was incomplete. 1201 same
Misc
Corrective Action Required
06/22/2015
UNTI 1101-1102 4TH INSPECTION NOT READY SINK AND PLUMBING INCOMPLETE
Occupancy Inspection - Codes Commercial Partial 6/29/2015 6/29/2015 at 12:00 AM 06/29/2015
Misc
Corrective Action Required
06/22/2015
APPROVED FOR TCO - SEE OTHER DEPARTMENTS FOR APPROVAL UNITS APPROVED 1ST FLOOR -1101,1102 ONLY 2 UNITS WITH OUT KITCHEN CABINETS AND COUNTERS. 2ND FLOOR-2 EAST END UNITS- OTHER OK NO INSPECTION ON 3,4 FLOORS NOT TO OCCUPY ANY UNITS -4TH FLOORS ALL STAIRWAYS AND CORRIDORS MUST REMAIN CLEAR FOR OCCUPANTS. PER FD NO PARKING IN GARAGES UNIT SMOKES OR WORKING CORRECTLY.
Misc
Corrective Action Required
06/22/2015
Occupancy inspection for 1078 3351 sw kesselr. 1st floor model was complete, 1102 no cabinets or counter/sink. 2nd floor was incomplete 2-end units. 1202 faucet was in but drainage was incomplete. 1201 same
Misc
Corrective Action Required
06/29/2015
3RD FLOOR- ALL UNITS OK.
Occupancy Inspection - Fire Temporary C of O 6/29/2015 at 12:00 AM 06/30/2015
Occupancy Inspection - Codes Commercial Temporary C of O 7/1/2015 7/2/2015 at 12:00 AM 07/02/2015
Misc
Resolved
02/04/2016
Misc
Resolved
02/04/2016
Resolved
02/04/2016
Occupancy Inspection - Fire Temporary C of O 7/1/2015 at 12:00 AM 07/06/2015
Electrical Service Inspection Passed 8/26/2015 at 12:00 AM 08/26/2015
Misc
Resolved
08/26/2015
MAIN DISCONNECT- approved to release main on each side of building - sub panels are not approved.
Rough Framing Inspection - Commercial Passed 08/26/2015
Misc
Resolved
08/26/2015
GARAGE-fraimng 1ST -partial, HOLD DOWN 2ND-partial, HOLD DOWN 3RD-PARTIAL HOLD DOWN FLOOR TRUSS DRILLED CHECK FIX. 4TH-PARTAIL HOLD DOWN SHEAR WALL NAILING - EXTERIOR -OK INTERIOR- PARTIAL CHECK REMAINING AT ALL TRADES INSPECTION
In-wall Inspection Passed 08/26/2015
Misc
Resolved
08/26/2015
INWALL-PRE ROCK INSPECTION: GARAGE PLUMBING CHASE, SHOWER WALLS, FURNACE ROOM WALL GARAGE- IT &ELECT ROOM OK TO ONE SIDE-BSM 1ST-PRE-ROCK SHOWER OK TO COVER 2ND-PRE-ROCK SHOWER OK TO COVER 3RD-PRE-ROCK SHOWER OK TO COVER 4TH-PRE-ROCK SHOWER OK TO COVER
FRAMING/STRUCTURE
Resolved
08/26/2015
SOFIT CEILING OVER DECK/ BALCONYS OK TO COVER NEED TO CHECK BLOCKING OVER GARAGES TO SOFIT.
Underground Electrical Inspection - Commercial Passed 08/26/2015
Misc
Resolved
08/26/2015
light pole base-#5 bases clubhouse and building #1
Miscellaneous Inspection Passed 08/26/2015
Misc
Resolved
08/26/2015
BUILDING #1 PRE-FINAL NOT COMPLETE LIST GARAGE LEVEL-EAST TO WEST- 1-HOLES IN CEILING 2,3,4,5, 6-ACCESS PANEL IN CEILING STORAGE ROOMS- 1,2,3,4 CAULK PLUMBING STACKS WHERE REQURIED 7,8,9 CAULK. ELEVATOR EQUIPMENT ROOM-OUTLET COVER, CAULK, LABEL DISCONNECTS FIRE PILLOWS CONDUIT BETWEEN FLOORS ALL, Fire extinguishers all corridors. Label all doors , floor leves, equipment rooms, unit rooms, north stair tower label gate. 1ST FLOOR-UNITS 1101 KIT ELECT, SINK 1102- KIT ELECT, SINK 1103- SINKS KIT. 1106-CHECK ALL 1105- KIT SINK 1108 - KIT ELECT, SINK 1110- PATIO BUBBLE COVER, ACCESS PANEL FURNACE 1112-PATIO GFCI 1109 CHECK ALL FLOOR#2 CHECK ALL- numerous breakers off throughout units for inspection. --Install all fire extinguishers, seal IT rooms. Caulk elevator ground floor penetrations. Gfci’s west ground level at panel. Sprinkler room heater. Check room top units and gfci’s
All Rough Inspection - Commercial Passed 5/11/2015 5/11/2015 at 12:00 AM 08/26/2015
FIRST FLOOR
Resolved
05/11/2015
ROUGH OK
SECOND FLOOR
Resolved
05/11/2015
OK TO COVER WALLS AND CEILINGS
Misc
Resolved
05/11/2015
THIRD FLOOR
Resolved
05/11/2015
OK TO ROCK UNITS AND WALLS TUB TRAPS INSPECTED
LOWER LEVEL
Resolved
05/11/2015
LOWER GARAGE LEVEL-
Above Ceiling Inspection Passed 8/20/2014 at 12:00 AM 08/26/2015
LOWER LEVEL
Resolved
08/26/2015
GARAGE - CORRIDOR north stair replace rock where sprinkler line was moved caulk all penetrartions in corridor ceiling
FIRST FLOOR
Resolved
08/26/2015
D" unit ok to cover ceiling
SECOND FLOOR
Resolved
08/26/2015
CORRIDOR ceiling failed holes cut in both layers holes cut in D unit ceiling
THIRD FLOOR
Resolved
08/26/2015
3rd floor corridor ok to rock D unit ok to cover
FOURTH FLOOR
Resolved
08/26/2015
CORRIDOR OR TO ROCK CEILING- UNIT CEILING - OK TO ROCK RIBBON STRIP FOR DUCTS WHERE DROP CEILING ARE. provide listing on 6" duct for penetrating ceiling 2x's provide damper each side of duct penetrating 1hr wall 2x's
Misc
Resolved
08/26/2015
BASEMENT CORRIDOR, 1ST, 2ND & 3RD FLOOR CORRIDORS; FLOORS 1, 2 & 3 IN THE MECHANICAL RMS IN THE UNITS (FIRE CAULKING AT THE PLEMS) / CALLED IN TODAY, MAY 18TH - METAL DROP - 4TH FLOOR CONTACT PERSON: MARCUS @ 785-332-4475 SALLY SARVADI 05/18/2015 8:07 AM
Rated Assembly Inspection Passed 08/26/2015
Occupancy Inspection - Engineering Passed 12/10/2015
Occupancy Inspection - Water Utilities Passed 12/16/2015
Occupancy Inspection - Planning Passed 01/28/2016
Occupancy Inspection - Fire Passed 3/17/2016 03/17/2016
Occupancy Inspection - Codes Commercial Full C of O 3/18/2016 03/18/2016
Misc
Resolved
03/18/2016
FIRE ONLY
Occupancy Inspection - Fire Passed 7/1/2015 7/1/2015 at 12:00 AM 03/18/2016
Alarm Test Passed 03/18/2016
Documents & Images
Date Uploaded File Type Document Name
05/13/2014 Letter Fire Building Plan Review
05/22/2014 Letter Codes P/R Corrections Document
05/30/2014 Letter PRCOM20141074 SIR Letter5.pdf
06/10/2014 Letter Fire Building Plan Review
07/09/2014 Letter Codes Plan Review Conditions
07/10/2014 Letter Codes Building Permit
07/21/2014 Letter Inspection Summary
08/20/2014 Letter Inspection Summary
08/22/2014 Letter Fire (Alarm) Plan Review Notice
08/26/2014 Letter Inspection Summary
09/03/2014 Letter Inspection Summary
09/05/2014 Letter Inspection Summary
09/10/2014 Letter Inspection Summary
10/10/2014 Letter Fire (Alarm) Plan Review Notice
10/31/2014 Letter Inspection Summary
11/13/2014 Letter Inspection Summary
11/19/2014 Letter Inspection Summary
12/19/2014 Letter Fire (Sprinkler) Plan Review
01/30/2015 Letter Inspection Summary
02/09/2015 Letter Inspection Summary
02/12/2015 Letter Inspection Summary
02/20/2015 Letter Inspection Summary
02/25/2015 Letter Inspection Summary
02/27/2015 Letter Inspection Summary
03/02/2015 Letter Inspection Summary
03/05/2015 Letter Inspection Summary
03/16/2015 Letter Inspection Summary
03/19/2015 Letter Inspection Summary
03/23/2015 Letter Inspection Summary
03/26/2015 Letter Inspection Summary
03/27/2015 Letter Inspection Summary
03/31/2015 Letter Inspection Summary
04/01/2015 Letter Inspection Summary
04/02/2015 Letter Inspection Summary
04/03/2015 Letter Inspection Summary
04/06/2015 Letter Inspection Summary
04/07/2015 Letter Inspection Summary
04/08/2015 Letter Inspection Summary
04/08/2015 Letter Inspection Summary
04/09/2015 Letter Inspection Summary
04/10/2015 Letter Inspection Summary
04/13/2015 Letter Inspection Summary
04/14/2015 Letter Inspection Summary
04/16/2015 Letter Inspection Summary
04/17/2015 Letter Inspection Summary
04/20/2015 Letter Inspection Summary
04/22/2015 Letter Inspection Summary
04/24/2015 Letter Inspection Summary
04/27/2015 Letter Inspection Summary
04/29/2015 Letter Inspection Summary
04/30/2015 Letter Inspection Summary
05/01/2015 Letter Inspection Summary
05/04/2015 Letter Inspection Summary
05/05/2015 Letter Inspection Summary
05/06/2015 Letter Inspection Summary
05/07/2015 Letter Inspection Summary
05/08/2015 Letter Inspection Summary
05/11/2015 Letter Inspection Summary
05/11/2015 Letter Inspection Summary
05/11/2015 Letter Inspection Summary
05/12/2015 Letter Inspection Summary
05/13/2015 Letter Inspection Summary
05/18/2015 Letter Inspection Summary
05/19/2015 Letter Inspection Summary
05/20/2015 Letter Inspection Summary
05/21/2015 Letter Inspection Summary
05/27/2015 Letter Inspection Summary
06/05/2015 Letter Inspection Summary
06/09/2015 Letter Inspection Summary
06/11/2015 Letter Planning Inspection Summary
06/12/2015 Letter Codes Temporary Certificate of Occupancy
06/15/2015 Letter Inspection Summary
06/29/2015 Letter Inspection Summary
07/02/2015 Letter Codes Temporary Certificate of Occupancy
03/18/2016 Letter Field Certificate of Occupancy
03/21/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home