Permit Application Status

PRCOM20140977


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20140977
Building Permit - Commercial
Certificate of Occupancy
LBC DEVELOPMENT CORP
NEW COMMERCIAL
FRONTIER JUSTICE - NEW BUILDING - FIRING RANGE AND RETAIL STORE
05/02/2014
06/23/2014
11/10/2014
01/23/2015
Locations
Contacts
MEYER BROTHERS BUILDING COMPANY, Address:800 E 101ST TER STE 120, Phone:(816) 246-4800  
TEMP-CON LLC, Address:15670 S KEELER ST, Phone:(913) 768-4888  
WESTHUES ELECTRIC INC, Address:PO BOX 18220, Phone:(816) 356-5223  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
LIQUID DESIGN, Address:1430 SOUTH MINT STREET, Phone:(707) 877-8297  
LBC DEVELOPMENT CORP, Address:PO BOX 7258  
PROFESSIONAL SERVICE INDUSTRIES INC, Address:1211 W CAMBRIDGE CIR, Phone:(913) 310-1600  
BMB HOLDINGS LLC, Address:8611 S STILLHOUSE RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 09/22/2014
Brian Austerman
Installation acceptance testing
Corrective Action Required
09/22/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call 816-969-1300 to schedule hydro and flow testing
Misc
Corrective Action Required
09/22/2014

Rate of rise detectors are not allowed to be used for pre-action system actuation. Per phone conversation with KCFS (Micah Pruett) the rate of rise detectors will be changed to fixed temperature set at 135 degrees. Verifed at inspection, for information only
Misc
Corrective Action Required
09/22/2014

Per NFPA 7.3.2.3.1.2 water from a dry system shall be delivered to the test connection within 60 seconds. Listed quick opening devices and or accelerators are permitted if necessary. Water delivery time to be verified at flow testing.
Fire Plan Review Approved with Conditions 05/16/2014 07/24/2014
Brian Austerman
Misc
Corrective Action Required
07/24/2014

803.5.1 Textile wall or ceiling coverings. Textile wall or ceiling coverings shall comply with one of the following: 1. The wall or ceiling covering shall have a Class A flame spread index in accordance with ASTM E 84 or UL 723, and be protected by automatic sprinklers installed in accordance with Section 903.3.1.1 or 903.3.1.2; 2. The wall covering shall meet the criteria of Section 803.5.1.1 or 803.5.1.2 when tested in the manner intended for use in accordance with NFPA 265 using the product-mounting system, including adhesive, of actual use; or 3. The wall or ceiling covering shall meet the criteria of Section 803.1.2.1 when tested in accordance with NFPA 286 using the product-mounting system, including adhesive, of actual use. Provide flame spread rating for wall coverings in shooting range as well as the sonex material CLASS A FLAME SPREAD RATING PROVIDED IN RESUB
Construction documents - Fire protection systems
Corrective Action Required
07/24/2014

20012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval. FDC shall be a 4" STORTZ type and to be located under the outside horn strobe. For information only
Construction documents for fire alarm systems
Corrective Action Required
07/24/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval, outside horn strobe is to activate on waterflow ONLY. Also show duct detection on alarm plans. For information only
Misc
Corrective Action Required
07/24/2014

Label door to riser room, to be verified at inspection
Knox box required
Corrective Action Required
07/24/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. Knok box to be located by FDC and outside horn strobe
Misc
Corrective Action Required
07/24/2014

[B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. Provide exterior emergency lighting at exit doors per condition #5 listed above REVISED IN RESUB
Type I hood - Where required
Corrective Action Required
07/24/2014

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Information was provided for drink stations at the cafe, also provide information on food service at the facility, if there is to be any. If any grease laden vapors are created a type 1 hood will be required. PROVIDE A LETTER STATING USE OF KITCHEN, IF IT IS FOR FOOD WARMING AND NOT PRODUCING VAPORS A CLASS 1 HOOD IS NOT REQUIRED RESOLVED
Alarm Plan Review Released for Construction 07/17/2014
Brian Austerman
Misc
Corrective Action Required
07/17/2014

Per phone conversation with Micah Pruett on 7-17-14 the heat detectors in the archery range will be changed to smoke detectors
Misc
Corrective Action Required
07/17/2014

Outside horn strobe not shown on plans. This is to be located over the FDC and shall activate only on a waterflow alarm.
Final Development Plan Review Approved 11/10/2014 06/23/2014
Mike Weisenborn
Special Inspections Review Approved 11/10/2014 06/17/2014
Mike Weisenborn
Licensed Contractors Approved 05/30/2014 06/10/2014
Joe Frogge
License contractors
Resolved
06/10/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of Mechanical contractor.
Building Plan Review Approved with Conditions 06/11/2014 06/10/2014
Joe Frogge
Health Dept Review
Resolved
05/31/2014

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required: This comment is for information purposes.
Health Dept Inspection
Corrective Action Required
05/30/2014

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: This comment is for informational purposes.
Misc
Corrective Action Required
05/30/2014

2012 IBC 1110.1 Signs. Required accessible elements shall be identified by the international symbol of accessibility at the following locations: 1. Accessible parking spaces required by section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location. 4. Accessible entrances where not all entrances are accessible. 5. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 6. Family or assisted-use toilet and bathing rooms. 7. Accessible dressing, fitting and locker rooms where not all such rooms are accessible. 8. Accessible areas of refuge in accordance with Section 1007.9. 9. Exterior areas for assisted rescue in accordance with Section 1007.9. Action required: This comment is for informational purposes. Accessibility signage to be verified at inspection.
Accessibility - Fixed sidewall grab bars 604.5.1
Resolved
05/31/2014

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide dimension to vertical grab bar. provided
Bldg - Interior finish requirements 803.9
Resolved
06/10/2014

2012 IBC 803.9 Interior finish requirements based on group. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.9 for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286 and meeting the acceptance criteria of Section 803.1.2.1 shall be permitted to be used where a Class A Classification in accordance with ASTM E 84 or UL 723 is required. Action required: Provide verification that woven fabric acoustical wall panels meet flame spread requirements. provided in resub
Misc
Resolved
06/10/2014

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Revise drawings to show how access to upper roof and roof above gun ranges will comply with this section. I am unable to find access point for roof above gun ranges nor can I find specific informatin about how access is accomplished between switch-back stairs and roof hatch at upper roof. revised on resub
Misc
Resolved
05/31/2014

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Exit sign appears to route occupants into "Air Loc 101" in lieu of adjacent exit access. Relocate exit sign to appropriate location. Coordinate with Fire Department. exit sign relocated
Misc
Resolved
05/31/2014

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required. Revise drawings to show emergency lighting in the rooms at the ends of gun ranges as well as in the mercantile area. provided
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
05/30/2014

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Provide detailed information for the construction of retail area point of sale counters. 5/31/14 - requirements noted on drawings for owner provided furniture. Compliance to be verified during inspection.
Misc
Resolved
05/31/2014

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Required action: Modify drawings to show that this requirement is met for all HVAC equipment on roofs. receptacles provided at units
Misc
Resolved
05/31/2014

2012 IPC 608.1 General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from nonoptable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Backflow preventer applications shall conform to Table 608.1, except as specifically stated in Sections 608.2 through 608.16.10. Required action: Revise drawings to show that water system is has backflow preventer and pressure reducing valve at entry. provided
Misc
Resolved
05/31/2014

Water service clarifications needed. Required actions: - update civil drawings to depict 2" water meter as discussed. - clarify intention of the note on civil drawings showing another 3" meter and pit to the west of westernmost parking lot entry. provided
Fire Plan Review Approved with Conditions 06/11/2014 06/09/2014
Brian Austerman
Misc
Corrective Action Required
05/30/2014

803.5.1 Textile wall or ceiling coverings. Textile wall or ceiling coverings shall comply with one of the following: 1. The wall or ceiling covering shall have a Class A flame spread index in accordance with ASTM E 84 or UL 723, and be protected by automatic sprinklers installed in accordance with Section 903.3.1.1 or 903.3.1.2; 2. The wall covering shall meet the criteria of Section 803.5.1.1 or 803.5.1.2 when tested in the manner intended for use in accordance with NFPA 265 using the product-mounting system, including adhesive, of actual use; or 3. The wall or ceiling covering shall meet the criteria of Section 803.1.2.1 when tested in accordance with NFPA 286 using the product-mounting system, including adhesive, of actual use. Provide flame spread rating for wall coverings in shooting range as well as the sonex material CLASS A FLAME SPREAD RATING PROVIDED IN RESUB
Construction documents - Fire protection systems
Corrective Action Required
05/30/2014

20012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval. FDC shall be a 4" STORTZ type and to be located under the outside horn strobe. For information only
Construction documents for fire alarm systems
Corrective Action Required
05/30/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval, outside horn strobe is to activate on waterflow ONLY. Also show duct detection on alarm plans. For information only
Misc
Corrective Action Required
05/30/2014

Label door to riser room, to be verified at inspection
Knox box required
Corrective Action Required
05/30/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. Knok box to be located by FDC and outside horn strobe
Misc
Corrective Action Required
05/30/2014

[B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. Provide exterior emergency lighting at exit doors per condition #5 listed above REVISED IN RESUB
Type I hood - Where required
Corrective Action Required
05/30/2014

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Information was provided for drink stations at the cafe, also provide information on food service at the facility, if there is to be any. If any grease laden vapors are created a type 1 hood will be required. PROVIDE A LETTER STATING USE OF KITCHEN, IF IT IS FOR FOOD WARMING AND NOT PRODUCING VAPORS A CLASS 1 HOOD IS NOT REQUIRED
Health Department Review Approved 05/30/2014
Joe Frogge
Building Plan Review Rejected 05/21/2014
Mike Weisenborn
Health Dept Review
Corrective Action Required
05/21/2014

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required: This comment is for information purposes.
Health Dept Inspection
Corrective Action Required
05/21/2014

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: This comment is for informational purposes.
Misc
Corrective Action Required
05/21/2014

2012 IBC 1110.1 Signs. Required accessible elements shall be identified by the international symbol of accessibility at the following locations: 1. Accessible parking spaces required by section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location. 4. Accessible entrances where not all entrances are accessible. 5. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 6. Family or assisted-use toilet and bathing rooms. 7. Accessible dressing, fitting and locker rooms where not all such rooms are accessible. 8. Accessible areas of refuge in accordance with Section 1007.9. 9. Exterior areas for assisted rescue in accordance with Section 1007.9. Action required: This comment is for informational purposes. Accessibility signage to be verified at inspection.
Accessibility - Fixed sidewall grab bars 604.5.1
Corrective Action Required
05/21/2014

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide dimension to vertical grab bar.
Bldg - Interior finish requirements 803.9
Corrective Action Required
05/21/2014

2012 IBC 803.9 Interior finish requirements based on group. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.9 for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286 and meeting the acceptance criteria of Section 803.1.2.1 shall be permitted to be used where a Class A Classification in accordance with ASTM E 84 or UL 723 is required. Action required: Provide verification that woven fabric acoustical wall panels meet flame spread requirements.
Misc
Corrective Action Required
05/21/2014

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Revise drawings to show how access to upper roof and roof above gun ranges will comply with this section. I am unable to find access point for roof above gun ranges nor can I find specific informatin about how access is accomplished between switch-back stairs and roof hatch at upper roof.
Misc
Corrective Action Required
05/21/2014

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Exit sign appears to route occupants into "Air Loc 101" in lieu of adjacent exit access. Relocate exit sign to appropriate location. Coordinate with Fire Department.
Misc
Corrective Action Required
05/21/2014

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required. Revise drawings to show emergency lighting in the rooms at the ends of gun ranges as well as in the mercantile area.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
05/21/2014

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Provide detailed information for the construction of retail area point of sale counters.
Misc
Corrective Action Required
05/21/2014

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Required action: Modify drawings to show that this requirement is met for all HVAC equipment on roofs.
Misc
Corrective Action Required
05/21/2014

2012 IPC 608.1 General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from nonoptable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Backflow preventer applications shall conform to Table 608.1, except as specifically stated in Sections 608.2 through 608.16.10. Required action: Revise drawings to show that water system is has backflow preventer and pressure reducing valve at entry.
Misc
Corrective Action Required
05/21/2014

Water service clarifications needed. Required actions: - update civil drawings to depict 2" water meter as discussed. - clarify intention of the note on civil drawings showing another 3" meter and pit to the west of westernmost parking lot entry.
Fire Plan Review Approved with Conditions 05/21/2014
Mike Weisenborn
Misc
Corrective Action Required
05/21/2014

803.5.1 Textile wall or ceiling coverings. Textile wall or ceiling coverings shall comply with one of the following: 1. The wall or ceiling covering shall have a Class A flame spread index in accordance with ASTM E 84 or UL 723, and be protected by automatic sprinklers installed in accordance with Section 903.3.1.1 or 903.3.1.2; 2. The wall covering shall meet the criteria of Section 803.5.1.1 or 803.5.1.2 when tested in the manner intended for use in accordance with NFPA 265 using the product-mounting system, including adhesive, of actual use; or 3. The wall or ceiling covering shall meet the criteria of Section 803.1.2.1 when tested in accordance with NFPA 286 using the product-mounting system, including adhesive, of actual use. Provide flame spread rating for wall coverings in shooting range as well as the sonex material
Construction documents - Fire protection systems
Corrective Action Required
05/21/2014

20012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval. FDC shall be a 4" STORTZ type and to be located under the outside horn strobe. For information only
Construction documents for fire alarm systems
Corrective Action Required
05/21/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval, outside horn strobe is to activate on waterflow ONLY. Also show duct detection on alarm plans. For information only
Misc
Corrective Action Required
05/21/2014

Label door to riser roomm, to be verified at inspection
Knox box required
Corrective Action Required
05/21/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. Knok box to be located by FDC and outside horn strobe
Misc
Corrective Action Required
05/21/2014

[B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. Provide exterior emergency lighting at exit doors per condition #5 listed above
Type I hood - Where required
Corrective Action Required
05/21/2014

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Information was provided for drink stations at the cafe, also provide information on food service at the facility, if there is to be any. If any grease laden vapors are created a type 1 hood will be required.
Building Plan Review Rejected 05/16/2014 05/14/2014
Joe Frogge
Health Dept Review
Corrective Action Required
05/14/2014

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required: This comment is for information purposes.
Health Dept Inspection
Corrective Action Required
05/14/2014

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: This comment is for informational purposes.
Misc
Corrective Action Required
05/14/2014

2012 IBC 1110.1 Signs. Required accessible elements shall be identified by the international symbol of accessibility at the following locations: 1. Accessible parking spaces required by section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location. 4. Accessible entrances where not all entrances are accessible. 5. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 6. Family or assisted-use toilet and bathing rooms. 7. Accessible dressing, fitting and locker rooms where not all such rooms are accessible. 8. Accessible areas of refuge in accordance with Section 1007.9. 9. Exterior areas for assisted rescue in accordance with Section 1007.9. Action required: This comment is for informational purposes. Accessibility signage to be verified at inspection.
Bldg - Occupant load posting 1004.3
Resolved
05/15/2014

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Required action: This comment is for informational purposes. Posting verified at inspection. 5/15/14 - not relevant
Accessibility - Fixed sidewall grab bars 604.5.1
Corrective Action Required
05/14/2014

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide dimension to vertical grab bar.
Bldg - Interior finish requirements 803.9
Corrective Action Required
05/14/2014

2012 IBC 803.9 Interior finish requirements based on group. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.9 for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286 and meeting the acceptance criteria of Section 803.1.2.1 shall be permitted to be used where a Class A Classification in accordance with ASTM E 84 or UL 723 is required. Action required: Provide verification that woven fabric acoustical wall panels meet flame spread requirements.
Misc
Corrective Action Required
05/14/2014

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Revise drawings to show how access to upper roof and roof above gun ranges will comply with this section. I am unable to find access point for roof above gun ranges nor can I find specific informatin about how access is accomplished between switch-back stairs and roof hatch at upper roof.
Misc
Corrective Action Required
05/14/2014

2012 IBC Exit Signs 1011.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Exit sign appears to route occupants into "Air Loc 101" in lieu of adjacent exit access. Relocate exit sign to appropriate location. Coordinate with Fire Department.
Misc
Corrective Action Required
05/14/2014

2012 IBC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Action required. Revise drawings to show emergency lighting in the rooms at the ends of gun ranges as well as in the mercantile area.
Bldg - Accessibility - Point of sales and service counters 1109.12.3
Corrective Action Required
05/14/2014

2012 IBC 1109.12.3 – Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Provide detailed information for the construction of retail area point of sale counters.
Misc
Corrective Action Required
05/14/2014

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Required action: Modify drawings to show that this requirement is met for all HVAC equipment on roofs.
Misc
Corrective Action Required
05/14/2014

2012 IPC 608.1 General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from nonoptable liquids, solids or gases being introduced into the potable water supply through cross-connections or any other piping connections to the system. Backflow preventer applications shall conform to Table 608.1, except as specifically stated in Sections 608.2 through 608.16.10. Required action: Revise drawings to show that water system is has backflow preventer and pressure reducing valve at entry.
Misc
Corrective Action Required
05/14/2014

Water service clarifications needed. Required actions: - update civil drawings to depict 2" water meter as discussed. - clarify intention of the note on civil drawings showing another 3" meter and pit to the west of westernmost parking lot entry.
Licensed Contractors Rejected 05/16/2014 05/14/2014
Joe Frogge
License contractors
Corrective Action Required
05/14/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Fire Plan Review Approved with Conditions 05/16/2014 05/08/2014
Brian Austerman
Misc
Corrective Action Required
05/08/2014

803.5.1 Textile wall or ceiling coverings. Textile wall or ceiling coverings shall comply with one of the following: 1. The wall or ceiling covering shall have a Class A flame spread index in accordance with ASTM E 84 or UL 723, and be protected by automatic sprinklers installed in accordance with Section 903.3.1.1 or 903.3.1.2; 2. The wall covering shall meet the criteria of Section 803.5.1.1 or 803.5.1.2 when tested in the manner intended for use in accordance with NFPA 265 using the product-mounting system, including adhesive, of actual use; or 3. The wall or ceiling covering shall meet the criteria of Section 803.1.2.1 when tested in accordance with NFPA 286 using the product-mounting system, including adhesive, of actual use. Provide flame spread rating for wall coverings in shooting range as well as the sonex material
Construction documents - Fire protection systems
Corrective Action Required
05/08/2014

20012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval. FDC shall be a 4" STORTZ type and to be located under the outside horn strobe. For information only
Construction documents for fire alarm systems
Corrective Action Required
05/08/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval, outside horn strobe is to activate on waterflow ONLY. Also show duct detection on alarm plans. For information only
Misc
Corrective Action Required
05/08/2014

Label door to riser roomm, to be verified at inspection
Knox box required
Corrective Action Required
05/08/2014

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call (816) 969-1300 to obtain a knox box application. Knok box to be located by FDC and outside horn strobe
Misc
Corrective Action Required
05/08/2014

[B] 1006.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. Provide exterior emergency lighting at exit doors per condition #5 listed above
Type I hood - Where required
Corrective Action Required
05/08/2014

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Information was provided for drink stations at the cafe, also provide information on food service at the facility, if there is to be any. If any grease laden vapors are created a type 1 hood will be required.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $16,808.30 $16,808.30 Paid 06/23/2014
$16,808.30
8331507-Sewer Connection Fee $1,020.00 $1,020.00 Paid 06/23/2014
$1,020.00
9110073-Right of Way Permit Fee $60.00 $60.00 Paid 06/23/2014
$60.00
8331506-EFHB Maybrook, Full $1,448.74 $1,448.74 Paid 06/23/2014
$1,448.74
8331401-Water Tap Fee $20,773.00 $20,773.00 Paid 06/23/2014
$20,773.00
8350015-Water Meter Fee $1,795.35 $1,795.35 Paid 06/23/2014
$1,795.35
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection Partial 7/17/2014 (1:00) 7/17/2014 at 12:00 AM 07/17/2014
Misc
Corrective Action Required
07/17/2014
-WATER SERVICE LINE AND FIRE SPRINKLER LINE OK FROM BUILDING TO NEAR PIT
Footing Inspection - Commercial Partial 7/21/2014 (11:00) 7/22/2014 07/22/2014
Misc
Corrective Action Required
07/22/2014
FOOTING OK BELOW: -TRASH ENCLOSURE AND RECYCLING ENCLOSURE
Underground Electrical Inspection - Commercial Partial 7/24/2014 at 12:00 AM 07/24/2014
Misc
Corrective Action Required
07/24/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT
Water Service Inspection Partial 8/1/2014 (1:00) 8/1/2014 at 12:00 AM 08/01/2014
Misc
Corrective Action Required
07/17/2014
-WATER SERVICE LINE AND FIRE SPRINKLER LINE OK FROM BUILDING TO PIT AND METER TAP LOCATION
Underground Plumbing Inspection - Commercial Partial 8/7/2014 at 12:00 AM 08/07/2014
Misc
Corrective Action Required
08/07/2014
OK BELOW: -EAST SIDE DOWNSPOUT CONNECTIONS TO STORM DRAIN
Water Service Inspection Partial 8/19/2014 (1:00) 8/19/2014 at 12:00 AM 08/19/2014
Misc
Corrective Action Required
08/01/2014
-WATER SERVICE LINE AND FIRE SPRINKLER LINE OK FROM BUILDING TO PIT AND METER TAP LOCATION
Underground Plumbing Inspection - Commercial Partial 8/26/2014 at 12:00 AM 08/26/2014
Misc
Corrective Action Required
08/07/2014
OK BELOW: -WEST SIDE, SOUTH, AND EAST SIDE DOWNSPOUT CONNECTIONS TO STORM DRAIN
Water Service Inspection Passed 8/28/2014 (11:30) 8/28/2014 at 12:00 AM 08/28/2014
Misc
Resolved
08/28/2014
-WATER SERVICE LINE AND FIRE SPRINKLER LINE OK FROM BUILDING TO PIT AND METER TAP LOCATION
Driveway Inspection Passed 9/16/2014 at 11:30 AM 09/17/2014
Underground Electrical Inspection - Commercial Partial 9/19/2014 9/19/2014 at 12:00 AM 09/19/2014
Misc
Corrective Action Required
07/24/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT PARKING LOTS LIGHT POLES: -6 L. POLES ON EAST LOT **NEED TO VERIFY THE UNDERGROUND CONDUITS MIN. 24" BURIAL DEPTH
Underground Electrical Inspection - Commercial Partial 9/22/2014 9/22/2014 at 12:00 AM 09/22/2014
Misc
Corrective Action Required
09/19/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT PARKING LOTS LIGHT POLES: -6 L. POLES ON EAST LOT
Underground Electrical Inspection - Commercial Partial 9/23/2014 9/23/2014 at 12:00 AM 09/23/2014
Misc
Corrective Action Required
09/22/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT -CONDUITS BETWEEN LIGHT POLES PARKING LOTS LIGHT POLES: -6 L. POLES ON EAST LOT
Public Curb Inspection Passed 09/29/2014
In-wall Inspection Partial 9/30/2014 9/30/2014 at 12:00 AM 09/30/2014
Misc
Corrective Action Required
09/30/2014
IN-WALL OK: -PARAPET WALLS
Sidewalk Inspection Partial 10/7/2014 at 1:00 AM 10/08/2014
Corrective Action Required
10/08/2014
sidewalk on south side okay
In-wall Inspection Partial 10/9/2014 10/9/2014 at 12:00 AM 10/09/2014
Misc
Corrective Action Required
09/30/2014
IN-WALL OK: -PARAPET WALLS
Underground Plumbing Inspection - Commercial Partial 10/24/2014 at 12:00 AM 10/24/2014
Misc
Corrective Action Required
08/26/2014
OK BELOW: -WEST SIDE, SOUTH, AND EAST SIDE DOWNSPOUT CONNECTIONS TO STORM DRAIN -CHANGE OF ROOF DRAINAGE AT SOUTH SIDE
Underground Electrical Inspection - Commercial Partial 10/24/2014 at 12:00 AM 10/24/2014
Misc
Corrective Action Required
09/23/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT -CONDUITS BETWEEN LIGHT POLES PARKING LOTS LIGHT POLES: -6 L. POLES ON EAST LOT **THE REMAINING LP AT SOUTH AND WEST SIDES NEED GROUNDING. VERIFY LATER
Underslab Plumbing Inspection - Commercial Passed 10/28/2014 at 12:00 AM 10/28/2014
Underground Electrical Inspection - Commercial Partial 10/30/2014 10/30/2014 at 12:00 AM 10/30/2014
Misc
Corrective Action Required
10/24/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT -CONDUITS BETWEEN LIGHT POLES PARKING LOTS LIGHT POLES: -6 L. POLES ON EAST LOT **THE REMAINING LP AT WEST SIDE NEED GROUNDING.
In-wall Inspection Partial 10/24/2014 10/30/2014 at 12:00 AM 10/30/2014
Misc
Corrective Action Required
10/09/2014
IN-WALL ON 2ND FL: -FIRESTOP ALL FLOOR PENETRATIONS -INSTALL LISTED ANTI-HAMMERING ARRESTORS -COMPLETE DUCTING THROUGH CHASES AND FIRESTOP AS REQUIRED
Misc
Corrective Action Required
10/24/2014
IN-WALL OK: -PARAPET WALLS
Underground Electrical Inspection - Commercial Partial 10/31/2014 10/31/2014 at 12:00 AM 10/31/2014
Misc
Corrective Action Required
10/30/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT -CONDUITS BETWEEN LIGHT POLES PARKING LOTS LIGHT POLES
In-wall Inspection Partial 11/7/2014 11/7/2014 at 12:00 AM 11/07/2014
Misc
Corrective Action Required
10/30/2014
2ND FL IN-WALL: -FIRESTOP ALL FLOOR PENETRATIONS -COMPLETE DUCTING THROUGH CHASES AND FIRESTOP AS REQUIRED IN-WALL FOR ALL AREA NORTH OF NORTH STAIR WALL-OK
Electrical Service Inspection Passed 11/7/2014 11/7/2014 at 12:00 AM 11/07/2014
Gas Service Inspection - Commercial Passed 11/14/2014 11/14/2014 at 12:00 AM 11/14/2014
In-wall Inspection Partial 11/14/2014 at 12:00 AM 11/14/2014
Misc
Corrective Action Required
11/07/2014
2ND FL IN-WALL: -FIRESTOP ALL FLOOR PENETRATIONS -COMPLETE DUCTING THROUGH CHASES AND FIRESTOP AS REQUIRED IN-WALL OK BELOW: ALL AREA NORTH OF NORTH STAIR WALL; RESTROOMS AND AREA UNDER 2ND FL OFFICE
Footing Inspection - Commercial Passed 11/21/2014
Misc
Resolved
11/21/2014
FOOTING OK BELOW: -TRASH ENCLOSURE AND RECYCLING ENCLOSURE
Underground Electrical Inspection - Commercial Passed 11/21/2014
Misc
Resolved
11/21/2014
UNDERGROUND ELECTRICAL OK BELOW: -SECONDARY FROM TRANSFORMER TO CT -CONDUITS BETWEEN LIGHT POLES PARKING LOTS LIGHT POLES
Underground Plumbing Inspection - Commercial Passed 11/21/2014
Misc
Resolved
11/21/2014
OK BELOW: -WEST SIDE, SOUTH, AND EAST SIDE DOWNSPOUT CONNECTIONS TO STORM DRAIN -CHANGE OF ROOF DRAINAGE AT SOUTH SIDE
Above Ceiling Inspection Partial 11/21/2014 11/21/2014 at 12:00 AM 11/21/2014
Misc
Corrective Action Required
11/21/2014
ABOVE-CEILING OK BELOW: -HARD LID CEILING AT 2ND FL PRIVATE RESTROOM, RESTROOMS AREA BELOW AND HALL OUTSIDE
In-wall Inspection Partial 11/26/2014 11/26/2014 at 12:00 AM 11/26/2014
Misc
Corrective Action Required
11/14/2014
2ND FL IN-WALL: -COMPLETE DUCTING THROUGH CHASES AND FIRESTOP AS REQUIRED 1ST FL IN-WALL-OK
Above Ceiling Inspection Partial 12/2/2014 at 12:00 AM 12/02/2014
Misc
Corrective Action Required
11/21/2014
ABOVE-CEILING OK BELOW: -HARD LID CEILING AT 2ND FL PRIVATE RESTROOM, RESTROOMS AREA BELOW AND HALL OUTSIDE -SHOOTING RANGES ABOVE-CEILING
Above Ceiling Inspection Passed 12/12/2014 12/12/2014 at 12:00 AM 12/12/2014
Misc
Resolved
12/12/2014
ABOVE-CEILING OK BELOW: -HARD LID CEILING AT 2ND FL PRIVATE RESTROOM, RESTROOMS AREA BELOW AND HALL OUTSIDE -SHOOTING RANGES ABOVE-CEILING
Sprinkler - Hydrostatic Test Passed 12/16/2014 at 9:00 AM 12/16/2014
Sprinkler - Flow Test Passed 12/17/2014 at 9:00 AM 12/17/2014
Alarm Test Partial 12/17/2014 at 9:00 AM 12/17/2014
In-wall Inspection Passed 12/22/2014
Misc
Resolved
12/22/2014
2ND FL IN-WALL: -COMPLETE DUCTING THROUGH CHASES AND FIRESTOP AS REQUIRED 1ST FL IN-WALL-OK
Alarm Test Partial 12/23/2014 at 12:00 AM 12/23/2014
Occupancy Inspection - Fire Temporary C of O 12/23/2014 12/23/2014 at 12:00 AM 12/23/2014
Occupancy Inspection - Codes Commercial Not Ready 12/23/2014 12/23/2014 at 12:00 AM 12/23/2014
Misc
Corrective Action Required
12/23/2014
NOT READY FOR FINAL, BUT ONLY OK TO STOCK AND TRAIN EMPLOYEE. DO NOT OPEN TO PUBLIC
Occupancy Inspection - Codes Commercial Temporary C of O 1/5/2015 1/5/2015 at 12:00 AM 01/05/2015
Misc
Corrective Action Required
12/23/2014
-OBTAIN APPROVAL FROM: FIRE DEPT; PUBLIC WORKS; WATER DEPT; PLANNING & DEVELOPMENT; HEALTH DEPT -GROUND ALL LIGHT POLES-INSTALL PROPER LUGS FOR GROUNDING -VAN ACCESSIBLE SIGNAGE -COMPLETE LIGHTING ABOVE FOOD SERVING COUNTER -INSTALL ACCESS LADDER TO BIG RTUs ROOF AREA -PAINT ROOFTOP GAS LINES -COMPLETE PANEL BREAKERS LABELING
Occupancy Inspection - Fire Temporary C of O 1/6/2015 at 12:00 AM 01/06/2015
Alarm Test Passed 1/6/2015 at 12:00 AM 01/06/2015
Occupancy Inspection - Fire Passed 1/21/2015 at 12:00 AM 01/22/2015
Occupancy Inspection - Planning Passed 01/23/2015
Occupancy Inspection - Codes Commercial Full C of O 1/23/2015 1/23/2015 at 12:00 AM 01/23/2015
Misc
Resolved
01/23/2015
-OBTAIN APPROVAL FROM: FIRE DEPT; WATER DEPT; PLANNING & DEVELOPMENT; HEALTH DEPT -GROUND ALL LIGHT POLES-INSTALL PROPER LUGS FOR GROUNDING -VAN ACCESSIBLE SIGNAGE -COMPLETE LIGHTING ABOVE FOOD SERVING COUNTER -INSTALL ACCESS LADDER TO BIG RTUs ROOF AREA -PAINT ROOFTOP GAS LINES -COMPLETE PANEL BREAKERS LABELING
Documents & Images
Date Uploaded File Type Document Name
05/08/2014 Letter Fire Building Plan Review
05/14/2014 Letter Codes P/R Corrections Document
06/09/2014 Letter Fire Building Plan Review
06/10/2014 Letter Codes P/R Corrections Document
06/23/2014 Letter Codes Plan Review Conditions
06/23/2014 Letter Codes Building Permit
07/17/2014 Letter Inspection Summary
07/22/2014 Letter Inspection Summary
07/24/2014 Letter Inspection Summary
07/24/2014 Letter Fire Building Plan Review
07/28/2014 Letter Fire (Alarm) Plan Review Notice
08/01/2014 Letter Inspection Summary
08/07/2014 Letter Inspection Summary
08/26/2014 Letter Inspection Summary
08/28/2014 Letter Inspection Summary
09/19/2014 Letter Inspection Summary
09/22/2014 Letter Inspection Summary
09/23/2014 Letter Inspection Summary
09/24/2014 Letter Fire (Sprinkler) Plan Review
09/29/2014 Letter PW-Daily Inspection Summary
09/30/2014 Letter Inspection Summary
10/08/2014 Letter PW-Daily Inspection Summary
10/24/2014 Letter Inspection Summary
10/24/2014 Letter Inspection Summary
10/28/2014 Letter Inspection Summary
10/30/2014 Letter Inspection Summary
10/31/2014 Letter Inspection Summary
11/07/2014 Letter Inspection Summary
11/14/2014 Letter Inspection Summary
11/21/2014 Letter Inspection Summary
11/26/2014 Letter Inspection Summary
12/02/2014 Letter Inspection Summary
12/12/2014 Letter Inspection Summary
12/23/2014 Letter Inspection Summary
01/05/2015 Letter Codes Temporary Certificate of Occupancy
01/23/2015 Letter Field Certificate of Occupancy
01/26/2015 Letter Codes Final Certificate of Occupancy
02/05/2015 Letter DOC020515-004
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home