Permit Application Status

PRCOM20140310


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20140310
Building Permit - Commercial
Certificate of Occupancy
EVANS JOHN S &
CHANGE OF TENANT
NEW TENANT - SPACE PREVIOUSLY USED FOR OFFICE
03/11/2014
04/03/2014
09/15/2014
06/06/2014
Locations
Contacts
RS MECHANICAL, Address:9005 N CENTRAL, Phone:(816) 436-7416  
RS MECHANICAL, Address:9005 N CENTRAL, Phone:(816) 436-7416  
RS MECHANICAL, Address:9005 N CENTRAL, Phone:(816) 436-7416  
C AND R PLUMBING CO LLC, Address:810 NW HAWTHORN CT  
EVANS JOHN S &, Address:208 SW ASPEN  
LEVERAGE CONSTRUCTION, Address:16216 W 124TH CIR, Phone:(913) 909-8744  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 03/31/2014 04/03/2014
Development Center
Business License
Resolved
04/03/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
03/31/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action Required: Provide the names of the MEP sub contractors. Permit will not be issued without this information.
Building Plan Review Approved with Conditions 04/07/2014 04/02/2014
Joe Frogge
License Tax Application
Corrective Action Required
03/31/2014

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Required Action: For informational purposes. The general contractor may complete form at the same time as paying for the permit.
Bldg - Occupant load calculations - Areas without fixed seating 1004.1.2
Resolved
03/31/2014

2012 IBC 1004.1.2 – Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as described in Table 1004.1.2. For areas without fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.1.2. Where an intended function is not listed in Table 1004.1.2, the building official shall establish a function based on a listed function that most nearly resembles the intended function. Required Action: Recalculate occupant load based on use and area. Calculations as listed are too low. Per my general calcs, I'm confident that the new load will still be under 25 which would allow the single restroom as well as maintain the B occupancy. (note: new load may not be less than the seating shown) 3/31/14 - occupant load raised from 14 to 22
Accessibility - Fixed sidewall grab bars 604.5.1
Resolved
03/31/2014

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Required Action: Revise drawings to show side grab bar. 3/31/14 - added
Misc
Resolved
03/31/2014

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Required Action: Revise drawings to show outside air calculations as well as method of delivery.
Misc
Resolved
03/31/2014

2012 IFGC 304 General. Air for combustion, ventilation and dilution of flue gases for appliances installed in buildings shall be provided by application of one of the methods prescribed in Sections 304.5 through 304.9. Where the requirements of Section 304.5 are not met, outdoor air shall be introduced in accordance with one of the methods prescribed in Sections 304.6 through 304.9. Direct-vent appliances, gas appliances of other than natural draft design and vented gas appliances other than Category I shall be provided with combustion, ventilation and dilution air in accordance with the appliance manufacturer’s instructions. (see code for exception) Required Action: Revise Drawings to provide combustion air method. 3/31/14 - original drawings compliant as clarified by engineer
Misc
Resolved
03/31/2014

2012 IFGC 501.2 General. Every appliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Required Action: Revise drawings to provide venting information. 3/31/14 - original drawings compliant as clarified by engineer
Misc
Resolved
03/31/2014

2012 IMC 506.3.9 Grease duct horizontal cleanouts. Cleanouts serving horizontal sections of grease ducts shall: (see code section for specific requirements) Required Action: Locate and specify required cleanouts. 3/31/14 - new detail specifies cleanout locations
Misc
Resolved
03/31/2014

2012 IMC 506.5 Exhaust equipment. Exhaust equipment, including fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.5 and shall be of an approved design or shall be listed for the application. Required Action: Revise fan detail to depict flexible electrical connection, 18" duct extension, etc. 3/31/14 - resolved via additional details
Misc
Resolved
03/31/2014

2012 IMC 507.9 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. (see code for exception) Required Action: Revise drawings. 3/31/14 - material behind hood to show stainless steel wall covering
Misc
Resolved
04/02/2014

2011 NEC Article 110.26 Spaces About Electrical Equipment. Access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation and maintenance of such equipment. (see code for details) Required Action: Dunnage racks may not be installed or stored in electrical equipment clearance areas. Revise drawing. 3/31/14 - Updated sheet A4.0 still shows the dunnage racks less than 36" in front of wall that holds electrical panels per sheet E3 4/2/14 - letter and drawing from architect attached to drawing.
Misc
Resolved
03/31/2014

2011 NEC Article 250.66 Size of Alternating-Current Grounding Electrode Conductor. The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66(A) through (C). Required Action: Provide size of Grounding Electrode Conductor.
Misc
Resolved
03/31/2014

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locates specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or protable lighitng equipment are to be used. (refer to code for exceptions) Required Action: Revise drawings.
Fire Plan Review Approved with Conditions 04/07/2014 04/01/2014
Brian Austerman
Installation acceptance testing
Corrective Action Required
04/01/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hood testing prior to scheduling final
Fire Plan Review Approved with Conditions 04/01/2014
Brian Austerman
Misc
Corrective Action Required
03/19/2014

Per local amendment Section 1008.1.9.3 is amended to read as follows: [B] 1008.1.9.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surfacemounted hardware. 3. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. 4. Fire doors after the minimum elevated temperature has disabled the unlatching mechanism in accordance with listed fire door test procedures Door 1 shall have a thumb latch or panic hardware on the egress side of the door, keyed locks on the egress side are not permitted. As a result the sign that reads the door shall remained unlocked during business hours is not required. Revised in resub of 4/1/14
Construction documents - Fire protection systems
Corrective Action Required
03/19/2014

901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation Prodive hood plans including fire suppression system and location of manual pull.. K class extinguisher is to be mounted under the manual pull Resolved 4/1/14
Misc
Corrective Action Required
03/19/2014

505.1 Address identification. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall be a minimum of 4 inches (101.6 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address numbers shall be maintained. For information only, posting of address on exterior doors to be verified at inspection
Misc
Corrective Action Required
03/19/2014

703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. For information only
Installation acceptance testing
Corrective Action Required
04/01/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hood test prior to scheduling final
Building Plan Review Rejected 03/21/2014 03/19/2014
Joe Frogge
License Tax Application
Corrective Action Required
03/19/2014

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Required Action: For informational purposes. The general contractor may complete form at the same time as paying for the permit.
Bldg - Occupant load calculations - Areas without fixed seating 1004.1.2
Corrective Action Required
03/19/2014

2012 IBC 1004.1.2 – Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as described in Table 1004.1.2. For areas without fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.1.2. Where an intended function is not listed in Table 1004.1.2, the building official shall establish a function based on a listed function that most nearly resembles the intended function. Required Action: Recalculate occupant load based on use and area. Calculations as listed are too low. Per my general calcs, I'm confident that the new load will still be under 25 which would allow the single restroom as well as maintain the B occupancy. (note: new load may not be less than the seating shown)
Accessibility - Fixed sidewall grab bars 604.5.1
Corrective Action Required
03/19/2014

ICC A117.1-2009 604.5.1 – Fixed side wall grab bars. Fixed side-wall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Required Action: Revise drawings to show side grab bar.
Misc
Corrective Action Required
03/19/2014

2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space. Required Action: Revise drawings to show outside air calculations as well as method of delivery.
Misc
Corrective Action Required
03/19/2014

2012 IFGC 304 General. Air for combustion, ventilation and dilution of flue gases for appliances installed in buildings shall be provided by application of one of the methods prescribed in Sections 304.5 through 304.9. Where the requirements of Section 304.5 are not met, outdoor air shall be introduced in accordance with one of the methods prescribed in Sections 304.6 through 304.9. Direct-vent appliances, gas appliances of other than natural draft design and vented gas appliances other than Category I shall be provided with combustion, ventilation and dilution air in accordance with the appliance manufacturer’s instructions. (see code for exception) Required Action: Revise Drawings to provide combustion air method.
Misc
Corrective Action Required
03/19/2014

2012 IFGC 501.2 General. Every appliance shall discharge the products of combustion to the outdoors, except for appliances exempted by Section 501.8. Required Action: Revise drawings to provide venting information.
Misc
Corrective Action Required
03/19/2014

2012 IMC 506.3.9 Grease duct horizontal cleanouts. Cleanouts serving horizontal sections of grease ducts shall: (see code section for specific requirements) Required Action: Locate and specify required cleanouts.
Misc
Corrective Action Required
03/19/2014

2012 IMC 506.5 Exhaust equipment. Exhaust equipment, including fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.5 and shall be of an approved design or shall be listed for the application. Required Action: Revise fan detail to depict flexible electrical connection, 18" duct extension, etc.
Misc
Corrective Action Required
03/19/2014

2012 IMC 507.9 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. (see code for exception) Required Action: Revise drawings.
Misc
Corrective Action Required
03/19/2014

2011 NEC Article 110.26 Spaces About Electrical Equipment. Access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation and maintenance of such equipment. (see code for details) Required Action: Dunnage racks may not be installed or stored in electrical equipment clearance areas. Revise drawing.
Misc
Corrective Action Required
03/19/2014

2011 NEC Article 250.66 Size of Alternating-Current Grounding Electrode Conductor. The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66(A) through (C). Required Action: Provide size of Grounding Electrode Conductor.
Misc
Corrective Action Required
03/19/2014

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locates specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or protable lighitng equipment are to be used. (refer to code for exceptions) Required Action: Revise drawings.
Licensed Contractors Rejected 03/21/2014 03/19/2014
Joe Frogge
Business License
Corrective Action Required
03/19/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Corrective Action Required
03/19/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action Required: Provide the names of the MEP sub contractors. Permit will not be issued without this information.
Fire Plan Review Rejected 03/21/2014 03/13/2014
Brian Austerman
Misc
Corrective Action Required
03/13/2014

Per local amendment Section 1008.1.9.3 is amended to read as follows: [B] 1008.1.9.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surfacemounted hardware. 3. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. 4. Fire doors after the minimum elevated temperature has disabled the unlatching mechanism in accordance with listed fire door test procedures Door 1 shall have a thumb latch or panic hardware on the egress side of the door, keyed locks on the egress side are not permitted. As a result the sign that reads the door shall remained unlocked during business hours is not required.
Construction documents - Fire protection systems
Corrective Action Required
03/13/2014

901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation Prodive hood plans including fire suppression system and location of manual pull.. K class extinguisher is to be mounted under the manual pull
Misc
Corrective Action Required
03/13/2014

505.1 Address identification. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall be a minimum of 4 inches (101.6 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address numbers shall be maintained. For information only, posting of address on exterior doors to be verified at inspection
Misc
Corrective Action Required
03/13/2014

703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. For information only
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $817.00 $817.00 Paid 04/03/2014
$817.00
8331507-Sewer Connection Fee $150.00 $150.00 Paid 04/03/2014
$150.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 4/9/2014 4/9/2014 at 12:00 AM 04/09/2014
Gas Service Inspection - Commercial Failed 4/15/2014 4/15/2014 at 12:00 AM 04/15/2014
Misc
Corrective Action Required
04/15/2014
-COMPLETE GAS PIPING TO RTU AND WATER HEATER
Gas Service Inspection - Commercial Failed 4/22/2014 4/22/2014 at 12:00 AM 04/22/2014
Misc
Corrective Action Required
04/15/2014
-PROVIDE MIN. 10 PSI FOR TESTING
Gas Service Inspection - Commercial Passed 4/23/2014 at 12:00 AM 04/23/2014
Misc
Resolved
04/23/2014
-PROVIDE MIN. 10 PSI FOR TESTING
In-wall Inspection Failed 4/30/2014 4/30/2014 at 12:00 AM 04/30/2014
Misc
Corrective Action Required
04/30/2014
-PROTECT PLUMBING PER CODE -INSTALL BACKINGS FOR RESTROOM GRAB BARS
In-wall Inspection Passed 5/1/2014 at 12:00 AM 05/01/2014
Misc
Resolved
05/01/2014
-PROTECT PLUMBING PER CODE -INSTALL BACKINGS FOR RESTROOM GRAB BARS
Hood/Duct Inspection Partial 5/7/2014 (8:00 to 5:00) 5/7/2014 at 12:00 AM 05/07/2014
Misc
Corrective Action Required
05/07/2014
LIGHT TESTED DUCTS ON THE GROUND. COMPLETE THE WHOLE DUCT INSTALLTION
Hood/Duct Inspection Failed 5/19/2014 (8:00 to 5:00) 5/19/2014 at 12:00 AM 05/19/2014
Misc
Corrective Action Required
05/07/2014
*LIGHT TESTED DUCTS ON THE GROUND. COMPLETE THE WHOLE DUCT INSTALLTION AND FIRE-WRAPPING. CHECK AT ABOVE-CEILING INSPECTION -THE TYPE I HOOD EXHAUST OPENING MUST BE MINIMUM 40" ABOVE THE ROOF SURFACE
Hood/Duct Inspection Passed 5/23/2014 5/23/2014 at 12:00 AM 05/23/2014
Misc
Resolved
05/23/2014
*LIGHT TESTED DUCTS ON THE GROUND. COMPLETE THE WHOLE DUCT INSTALLTION AND FIRE-WRAPPING. CHECK AT ABOVE-CEILING INSPECTION -THE TYPE I HOOD EXHAUST OPENING MUST BE MINIMUM 40" ABOVE THE ROOF SURFACE
Above Ceiling Inspection Passed 5/23/2014 5/23/2014 at 12:00 AM 05/23/2014
Occupancy Inspection - Codes Commercial Failed 5/27/2014 5/27/2014 at 12:00 AM 05/27/2014
Misc
Corrective Action Required
05/27/2014
-FIRE DEPT. APPROVAL REQUIRED -HEALTH DEPT. APPROVAL REQUIRED -WRAP RESTROOM SINK TRAP -INSTALL EM LIGHT IN RESTROOM -INSTALL RESTROOM SIGNAGE -COMPLETE INSTALLATION OF SINK -SUPPORT THE GAS LINE TO WATER HEATER -COMPLETE HOOKUP OF GAS SERVICE. PAINT TO PROTECT GAS SERVICE LINE FROM CORROSION -INSTALL AN APPROVED GREASE RESERVOIR FOR THE HOOD EXHAUST FAN -COMPLETE LABELING SERVICE PANEL BREAKERS -INSTALL MAXIMUM 15 AMP BREAKER FOR ROOFTOP UNIT FOR FREEZER -SUPPORT AND SECURE ELECTRICAL PER CODE AT KITCHEN HOOD -KITCHEN HOOD: COMPLETE KITCHEN HOOD AND TESTING BY FIRE DEPT.; HAVE 3RD PARTY SUBMIT TESTING REPORT FOR THE HOOD SYSTEM. ADJUST SYSTEM TO PERFORM PER CODE
Occupancy Inspection - Codes Commercial Temporary C of O 5/29/2014 5/29/2014 at 12:00 AM 05/29/2014
Misc
Corrective Action Required
05/27/2014
-FIRE DEPT. APPROVAL REQUIRED -INSTALL A NO-SMOKING SIGN AT FRONT
Alternate Protection Systems Inspection Passed 5/29/2014 at 12:00 AM 05/29/2014
Occupancy Inspection - Fire Temporary C of O 5/29/2014 5/29/2014 at 12:00 AM 05/29/2014
Misc
Corrective Action Required
05/29/2014
- post the occupant load of 22 in the dining area - lights under the hood need to terminate upon ansul activation
Occupancy Inspection - Fire Passed 6/6/2014 6/6/2014 at 12:00 AM 06/06/2014
Misc
Corrective Action Required
06/05/2014
- post the occupant load of 22 in the dining area - lights under the hood need to terminate upon ansul activation
Occupancy Inspection - Codes Commercial Full C of O 6/6/2014 6/6/2014 at 12:00 AM 06/06/2014
Misc
Resolved
06/06/2014
-FIRE DEPT. APPROVAL REQUIRED
Documents & Images
Date Uploaded File Type Document Name
03/13/2014 Letter Fire Building Plan Review
03/19/2014 Letter Codes P/R Corrections Document
04/01/2014 Letter Fire Building Plan Review
04/01/2014 Letter Fire Building Plan Review
04/03/2014 Letter Codes Plan Review Conditions
04/03/2014 Letter Codes Building Permit
04/09/2014 Letter Inspection Summary
04/15/2014 Letter Inspection Summary
04/22/2014 Letter Inspection Summary
04/23/2014 Letter Inspection Summary
04/30/2014 Letter Inspection Summary
05/01/2014 Letter Inspection Summary
05/07/2014 Letter Inspection Summary
05/19/2014 Letter Inspection Summary
05/23/2014 Letter Inspection Summary
05/27/2014 Letter Inspection Summary
05/29/2014 Letter Codes Temporary Certificate of Occupancy
06/06/2014 Letter Field Certificate of Occupancy
06/09/2014 Letter Codes Final Certificate of Occupancy
09/12/2014 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home