Permit Application Status

PRCOM20140038


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20140038
Building Permit - Commercial
Final Completion
JUNIOR COLLEGE DISTRICT OF
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO COLLEGE ENROLLEMENT CENTER AND OFFICES
01/16/2014
02/24/2014
07/29/2014
09/30/2014
Locations
Contacts
METROPOLITAN COMMUNITY COLLEGE, Address:1601 PROSPECT AVE  
EDWARDS MCDOWELL INC, Address:400 E 10TH AVE, Phone:(816) 221-7878  
METROPOLITAN COMMUNITY COLLEGE, Address:1601 PROSPECT AVE  
CORLESS MECHANICAL INC, Address:26020 S SKYLINE DR, Phone:(816) 380-4448  
INTERNATIONAL ARCHITECTS ATELIER, Address:912 BROADWAY SUITE 300  
JUNIOR COLLEGE DISTRICT OF, Address:3200 BROADWAY  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/14/2014
Brian Austerman
Installation acceptance testing
Corrective Action Required
03/14/2014

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. IF THIS AREA IS ABLE TO BE ISOLATED A HYDROSTATIC TEST SHALL BE REQUIRED PER NFPA 24.2.1.5-6. CALL (816) 969-1300 TO SCHEDULE TESTING IF THE AREA CAN BE ISOLATED
Licensed Contractors Approved 06/29/2014 02/24/2014
Joe Frogge
Business License
Corrective Action Required
01/27/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.Action required - Either a Class A or Class B license is required. Provide the name of the licensed general contractor. Action Required: Licensed general contractor must be listed on permit prior to issuance.
License contractors
Corrective Action Required
01/27/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action Required: Mechanical, Electrical, and Plumbing contractors must be licensed and listed on permit prior to permit issuance.
Fire Plan Review Approved with Conditions 02/09/2014 02/06/2014
Brian Austerman
Misc
Corrective Action Required
02/04/2014

901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for any alterations to the system
Misc
Corrective Action Required
02/04/2014

907.1.1 Construction documents. Construction documents for fire alarm systems shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code, the International Building Code, and relevant laws, ordinances, rules and regulations, as determined by the fire code official. Provide alarm plans if any modifications are made
Misc
Corrective Action Required
02/04/2014

906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of 2A10B:C extinguishers. Verified at inspection
Misc
Corrective Action Required
02/06/2014

2-6-14 No additional FD comments
Building Plan Review Approved with Conditions 02/09/2014 02/04/2014
Joe Frogge
Misc
Resolved
02/04/2014

2012 IBC 803.9 Interior finish requirements based on group. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.9 for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286 and meeting the acceptance criteria of Section 803.1.2.1 shall be permitted to be used where a Class A Classification in accordance with ASTM E 84 or UL 723 is required. Required Action: Provide additional information that verifies that finish materials FB-1 & FB-2 meet minimum Class B requirements per 803.1.1
Bldg - Occupant load posting 1004.3
Resolved
02/04/2014

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Required Action: Provide additional information as to what the maximum occupancies will be and where they will be posted.
Misc
Resolved
02/04/2014

2012 IMC 2406.1 Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.4 shall comply with sections 2406.1.1 through 2406.1.4. Action Required. Provide additional information to verify that safety glass will be installed in appropriate locations.
Bldg - Occupant load posting 1004.3
Resolved
02/04/2014

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Corrective Action: Provide justifiction for 39 occupants in the Enrollement Center #205.
Misc
Corrective Action Required
02/24/2014

2012 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action Required: This item will be verified in field.
Building Plan Review Rejected 07/29/2014 01/27/2014
Joe Frogge
Misc
Corrective Action Required
01/27/2014

2012 IBC 803.9 Interior finish requirements based on group. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.9 for the group and location designated. Interior wall and ceiling finish materials tested in accordance with NFPA 286 and meeting the acceptance criteria of Section 803.1.2.1 shall be permitted to be used where a Class A Classification in accordance with ASTM E 84 or UL 723 is required. Required Action: Provide additional information that verifies that finish materials FB-1 & FB-2 meet minimum Class B requirements per 803.1.1
Bldg - Occupant load posting 1004.3
Corrective Action Required
01/27/2014

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Required Action: Provide additional information as to what the maximum occupancies will be and where they will be posted.
Misc
Corrective Action Required
01/27/2014

2012 IMC 2406.1 Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.4 shall comply with sections 2406.1.1 through 2406.1.4. Action Required. Provide additional information to verify that safety glass will be installed in appropriate locations.
Bldg - Occupant load posting 1004.3
Corrective Action Required
01/27/2014

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Corrective Action: Provide justifiction for 39 occupants in the Enrollement Center #205.
Misc
Corrective Action Required
01/27/2014

2012 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action Required: This item will be verified in field.
Fire Plan Review Approved with Conditions 01/29/2014 01/16/2014
Brian Austerman
Misc
Corrective Action Required
01/16/2014

901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for any alterations to the system
Misc
Corrective Action Required
01/16/2014

907.1.1 Construction documents. Construction documents for fire alarm systems shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code, the International Building Code, and relevant laws, ordinances, rules and regulations, as determined by the fire code official. Provide alarm plans if any modifications are made
Misc
Corrective Action Required
01/16/2014

906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of 2A10B:C extinguishers. Verified at inspection
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $904.51 $904.51 Paid 02/24/2014
$904.51
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 3/3/2014 3/3/2014 at 12:00 AM 03/03/2014
Misc
Partial Correction
03/03/2014
THE FOLLOWING AREAS ARE APPROVED TO COVER: BREAK ROOM IN WALL, ADMISSIONS AREA IN WALL, TWO CORNER OFFICES SW CORNER
In-wall Inspection Partial 3/18/2014 3/18/2014 at 12:00 AM 03/18/2014
Misc
Partial Correction
03/03/2014
THE FOLLOWING AREAS ARE APPROVED TO COVER: BREAK ROOM IN WALL, ADMISSIONS AREA IN WALL, TWO CORNER OFFICES SW CORNER;212,213,214, CORRIDOOR 210-
In-wall Inspection Partial 3/26/2014 3/26/2014 at 12:00 AM 03/26/2014
Misc
Partial Correction
03/18/2014
THE FOLLOWING AREAS ARE APPROVED TO COVER: BREAK ROOM IN WALL, ADMISSIONS AREA IN WALL, TWO CORNER OFFICES SW CORNER;212,213,214, CORRIDOOR 210-; 209 hall, STAIR WALL, 215PLUMB IN BREAK ROOM,
In-wall Inspection Partial 4/16/2014 4/16/2014 at 12:00 AM 04/16/2014
Misc
Partial Correction
03/26/2014
THE FOLLOWING AREAS ARE APPROVED TO COVER: BREAK ROOM IN WALL, ADMISSIONS AREA IN WALL, TWO CORNER OFFICES SW CORNER;212,213,214, CORRIDOOR 210-; 209 hall, STAIR WALL, 215PLUMB IN BREAK ROOM, 209 printer room, 203,216.
Rated Assembly Inspection Partial 4/30/2014 4/30/2014 at 12:00 AM 04/30/2014
Misc
Corrective Action Required
04/30/2014
STAIR SIDE SCREW PATT OK
Above Ceiling Inspection Partial 5/22/2014 5/22/2014 at 12:00 AM 05/22/2014
Misc
Partial Correction
05/22/2014
AREA AT ENROLMENT COMMON AREA APPROVED
Rated Assembly Inspection Partial 5/22/2014 5/22/2014 at 12:00 AM 05/22/2014
Misc
Partial Correction
05/22/2014
STAIR SIDE SCREW PATT OK SCREW PATTERN EACH SIDE OF WALL FACING BOTTOM OF STAIR WELL APPROVED. PENETRATIONS IN ASSEMBLY SHALL BE LISTED PENETRATIONS.
Rated Assembly Inspection Passed 6/30/2014 6/30/2014 at 12:00 AM 06/30/2014
Misc
Resolved
06/30/2014
STAIR SIDE SCREW PATT OK SCREW PATTERN EACH SIDE OF WALL FACING BOTTOM OF STAIR WELL APPROVED. PENETRATIONS IN ASSEMBLY SHALL BE LISTED PENETRATIONS.
Above Ceiling Inspection Partial 6/30/2014 6/30/2014 at 12:00 AM 06/30/2014
Misc
Partial Correction
05/22/2014
AREA AT ENROLMENT COMMON AREA APPROVED HARD LIDS APPROVED
All Rough Inspection - Commercial Passed 6/30/2014 6/30/2014 at 12:00 AM 06/30/2014
Above Ceiling Inspection Partial 7/29/2014 7/29/2014 at 12:00 AM 07/29/2014
Misc
Partial Correction
06/30/2014
AREA AT ENROLMENT COMMON AREA APPROVED HARD LIDS APPROVED 217,213,214,209D,210A,54,215,
Above Ceiling Inspection Partial 8/21/2014 8/21/2014 at 12:00 AM 08/21/2014
Misc
Partial Correction
07/29/2014
AREA AT ENROLMENT COMMON AREA APPROVED HARD LIDS APPROVED 217,213,214,209D,210A,54,215, all approved except front office entry
Above Ceiling Inspection Passed 8/26/2014 8/26/2014 at 12:00 AM 08/26/2014
Misc
Resolved
08/26/2014
AREA AT ENROLMENT COMMON AREA APPROVED HARD LIDS APPROVED 217,213,214,209D,210A,54,215, all approved except front office entry
Alarm Test Passed 09/29/2014
Occupancy Inspection - Fire Passed 9/30/2014 at 12:00 AM 09/30/2014
Final Inspection - Commercial Passed 9/30/2014 9/30/2014 at 12:00 AM 09/30/2014
Miscellaneous Inspection Passed 9/30/2014 at 12:00 AM 09/30/2014
Documents & Images
Date Uploaded File Type Document Name
01/16/2014 Letter Fire Building Plan Review
01/27/2014 Letter Codes Plan Review Conditions
02/06/2014 Letter Fire Building Plan Review
02/24/2014 Letter Codes Plan Review Conditions
02/24/2014 Letter Codes Building Permit
03/03/2014 Letter Inspection Summary
03/14/2014 Letter Fire (Sprinkler) Plan Review
03/18/2014 Letter Inspection Summary
03/26/2014 Letter Inspection Summary
04/16/2014 Letter Inspection Summary
04/30/2014 Letter Inspection Summary
05/22/2014 Letter Inspection Summary
06/30/2014 Letter Inspection Summary
07/29/2014 Letter Inspection Summary
08/21/2014 Letter Inspection Summary
08/26/2014 Letter Inspection Summary
09/30/2014 Letter Inspection Summary
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home