Permit Application Status

PRCOM20132126


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20132126
Building Permit - Commercial
Certificate of Occupancy
DAHMER REALTY LP
CHANGE OF TENANT
CHANGE OF TENANT
09/27/2013
11/26/2013
05/17/2014
03/25/2014
Locations
Contacts
HGK CONSTRUCTION MANAGEMENT INC, Address:11705 E 71ST CT, Phone:(816) 356-7555  
MD REPAIR, Address:7901 S PARRENT RD, Phone:(816) 690-7985  
BRINTON ELECTRIC COMPANY INC, Address:10100 E 65TH ST STE B, Phone:(816) 356-0922  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
DAHMER REALTY LP, Address:2301 NE INDEPENDENCE AVE  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/18/2013
Brian Austerman
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
12/18/2013

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Call 816-969-1300 to schedule alarm testing
Building Plan Review Approved 12/02/2013 11/25/2013
Mike Weisenborn
Bldg - Guards - Height
Resolved
11/25/2013

2006 IBC 1013.2 - Height. Guards shall form a protective barrier not less than 42 inches high, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard. (See exceptions provided in the code.) Action required - Details 12 and 13 on Sheet A1.1 show the top of the guard below 42". Make needed corrections. Mike Weisenborn 11/25/2013 12:13 PM - Corrections have been made.
Screening - Ground mounted equipment
Resolved
11/25/2013

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required - Contact the Planning and Development Department at 816-969-1600 for screening requirements for the new condensing unit. Mike Weisenborn 11/25/2013 2:01 PM - Approved per Hector Soto.
Fire Plan Review Approved with Conditions 12/02/2013 11/25/2013
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
11/22/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval ACKNOWLEDGED 11/14/13
Construction documents for fire alarm systems
Corrective Action Required
11/22/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval ACKNOWLEDGED 11/14/13
Misc
Corrective Action Required
11/22/2013

2006 IFC - 912.3 - Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimu of 3 feet. Action required - It appears that the new condensing unit is to be located in front of the fdc. Add a note to the plans regarding this requirement. Acknowledged 11/25 submittal
Licensed Contractors Approved 11/19/2013 11/18/2013
Mike Weisenborn
License contractors
Resolved
11/18/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical and plumbing contractors. This information is required for permit approval.
Building Plan Review Rejected 11/19/2013 11/18/2013
Mike Weisenborn
Misc
Resolved
11/18/2013

General Note 1 on Sheet A1.0 states that all new walls are to be 1-hour fire rated but a listing for the assembly is not provided. (Per the section on non-separated uses, there are no required rated assemblies in this building.) Action required - Make needed corrections. Mike Weisenborn 11/18/2013 12:10 PM - Notes have been removed/revised.
Misc
Resolved
11/18/2013

The loads used in the design of the new second floor area are not provided on the plans. Action required - Provide additional information on the plans.
Misc
Resolved
11/18/2013

The plans do not show footings or a thickened slab under the new load bearing wall. Action required - Provide justification for not providing additional support for the wall.
Misc
Resolved
11/18/2013

There appears to be a new platform open to the warehouse next to the second floor restrooms. Action required - Provide additional information such as quards and the gate for this area.
Accessibility - Water closet - Grab bars
Resolved
11/18/2013

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The required vertical grab bar is not show on the plans. The plans also do indicate mounting location deminsions for the grab bars. Provide additional information on the plans. Mike Weisenborn 11/18/2013 2:47 PM - Information has been added to the plans.
Misc
Resolved
11/18/2013

The required clearances for an accessible restroom are not shown for the new restroom on the second floor. Action required - Provide additional information on the plans.
Accessibility - Maneuvering Clearance at Doors.
Resolved
11/18/2013

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - Per detail a 18 inches clear is required from the latch side on a front approach door. This requirement is not being meet for the second floor restroom doors. Make needed corrections. Mike Weisenborn 11/18/2013 2:51 PM - Corrections have been made.
Misc
Resolved
11/18/2013

Plans and details for the mechanical, electrical and plumbing work have not been provided. Action required - Provide required information. Mike Weisenborn 11/18/2013 2:51 PM - Plans have been provided.
Bldg - Toilet rooms - Walls
Resolved
11/18/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - Indicate how this requirement will be met on the plans. Mike Weisenborn 11/18/2013 2:52 PM - Information has been provided.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Resolved
11/18/2013

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Show how the second floor breakroom sink will meet this requirement. Mike Weisenborn 11/18/2013 2:53 PM - A detail has been provided.
Bldg - Glazing - Human impact loads
Resolved
11/18/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Indicate locations of required safety glass. Mike Weisenborn 11/18/2013 2:54 PM - A note has been added.
Misc
Resolved
11/18/2013

I am unable to locate information on the window located in the wall between Office 100 and the warehouse area. Action required - Provide additional information. Mike Weisenborn 11/18/2013 2:54 PM - Information has been added.
Misc
Resolved
11/18/2013

The doors to the two new mechanical closets are not show on the door schedule. Action required - Make needed corrections. Mike Weisenborn 11/18/2013 2:57 PM - This is an lift shaft. Information has been provided.
Misc
Resolved
11/18/2013

The plans are not dimensioned. Action required - Provide dimensions on the plans.
Bldg - Guards - Height
Corrective Action Required
11/18/2013

2006 IBC 1013.2 - Height. Guards shall form a protective barrier not less than 42 inches high, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard. (See exceptions provided in the code.) Action required - Details 12 and 13 on Sheet A1.1 show the top of the guard below 42". Make needed corrections.
Screening - Ground mounted equipment
Corrective Action Required
11/18/2013

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required - Contact the Planning and Development Department at 816-969-1600 for screening requirements for the new condensing unit.
Fire Plan Review Rejected 11/19/2013 11/18/2013
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
11/13/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval ACKNOWLEDGED 11/14/13
Construction documents for fire alarm systems
Corrective Action Required
11/13/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval ACKNOWLEDGED 11/14/13
Misc
Corrective Action Required
11/18/2013

2006 IFC - 912.3 - Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimu of 3 feet. Action required - It appears that the new condensing unit is to be located in front of the fdc. Add a note to the plans regarding this requirement.
Sprinkler Plan Review Released for Construction 11/04/2013
Brian Austerman
Installation acceptance testing
Corrective Action Required
11/04/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Per NFPA 13 24.2.1.5 modifications of more than 20 heads shall require hydrostatic testing. Call (816) 969-1300 to schedule testing
Building Plan Review Rejected 10/09/2013 10/07/2013
Mike Weisenborn
Misc
Corrective Action Required
10/07/2013

General Note 1 on Sheet A1.0 states that all new walls are to be 1-hour fire rated but a listing for the assembly is not provided. (Per the section on non-separated uses, there are no required rated assemblies in this building.) Action required - Make needed corrections.
Misc
Corrective Action Required
10/07/2013

The loads used in the design of the new second floor area are not provided on the plans. Action required - Provide additional information on the plans.
Misc
Corrective Action Required
10/07/2013

The plans do not show footings or a thickened slab under the new load bearing wall. Action required - Provide justification for not providing additional support for the wall.
Misc
Corrective Action Required
10/07/2013

There appears to be a new platform open to the warehouse next to the second floor restrooms. Action required - Provide additional information such as quards and the gate for this area.
Accessibility - Water closet - Grab bars
Corrective Action Required
10/07/2013

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The required vertical grab bar is not show on the plans. The plans also do indicate mounting location deminsions for the grab bars. Provide additional information on the plans.
Misc
Corrective Action Required
10/07/2013

The required clearances for an accessible restroom are not shown for the new restroom on the second floor. Action required - Provide additional information on the plans.
Accessibility - Maneuvering Clearance at Doors.
Corrective Action Required
10/07/2013

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - Per detail a 18 inches clear is required from the latch side on a front approach door. This requirement is not being meet for the second floor restroom doors. Make needed corrections.
Misc
Corrective Action Required
10/07/2013

Plans and details for the mechanical, electrical and plumbing work have not been provided. Action required - Provide required information.
Bldg - Toilet rooms - Walls
Corrective Action Required
10/07/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - Indicate how this requirement will be met on the plans.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
10/07/2013

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Show how the second floor breakroom sink will meet this requirement.
Bldg - Glazing - Human impact loads
Corrective Action Required
10/07/2013

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Indicate locations of required safety glass.
Misc
Corrective Action Required
10/07/2013

I am unable to locate information on the window located in the wall between Office 100 and the warehouse area. Action required - Provide additional information.
Misc
Corrective Action Required
10/07/2013

The doors to the two new mechanical closets are not show on the door schedule. Action required - Make needed corrections.
Misc
Corrective Action Required
10/07/2013

The plans are not dimensioned. Action required - Provide dimensions on the plans.
Fire Plan Review Approved with Conditions 10/09/2013 09/30/2013
Brian Austerman
Fire-resistant-rated construction - Maintenance
Corrective Action Required
09/30/2013

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Doors along the one hour rated firewall shall be rated fire doors. Verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
09/30/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
09/30/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $277.78 $277.78 Paid 11/26/2013
$277.78
8331507-Sewer Connection Fee $210.00 $210.00 Paid 11/26/2013
$210.00
8331506-EFHB Maybrook, Full $298.27 $298.27 Paid 11/26/2013
$298.27
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/3/2013 12/3/2013 at 12:00 AM 12/03/2013
All Rough Inspection - Commercial Failed 12/6/2013 12/6/2013 at 12:00 AM 12/06/2013
Misc
Corrective Action Required
12/06/2013
-COMPLETE IN-WALL BLOCKING FOR RESTROOM GRAB BARS -DRAINAGE LINE FROM 2ND FL BREAK RM SINK-MINIMUM 1/4" PER FOOT SLOPE REQUIRED -PROTECT PVC WHERE WITHIN 1.5" OF THE STUD/TRACK SURFACE -COMPLETE WALL FRAMING OF THE 2ND FL BREAK RM
All Rough Inspection - Commercial Passed 12/9/2013 12/9/2013 at 12:00 AM 12/09/2013
Misc
Resolved
12/09/2013
-COMPLETE IN-WALL BLOCKING FOR RESTROOM GRAB BARS -DRAINAGE LINE FROM 2ND FL BREAK RM SINK-MINIMUM 1/4" PER FOOT SLOPE REQUIRED -PROTECT PVC WHERE WITHIN 1.5" OF THE STUD/TRACK SURFACE -COMPLETE WALL FRAMING OF THE 2ND FL BREAK RM
Above Ceiling Inspection Partial 2/12/2014 2/12/2014 at 12:00 AM 02/12/2014
Misc
Corrective Action Required
02/12/2014
-INSTALL RESTROOM EXHAUST -COMPLETE VENTING THROUGH ROOF **OK TO DROP TILES, EXCEPT ABOVE 2ND FL RESTROOMS
Alarm Test Passed 3/21/2014 at 12:00 AM 03/21/2014
Misc
Corrective Action Required
03/21/2014
- program outside horn/strobe to activate on water flow only
Above Ceiling Inspection Passed 03/25/2014
Misc
Resolved
03/25/2014
-INSTALL RESTROOM EXHAUST -COMPLETE VENTING THROUGH ROOF **OK TO DROP TILES, EXCEPT ABOVE 2ND FL RESTROOMS
Occupancy Inspection - Codes Commercial Temporary C of O 3/25/2014 3/25/2014 at 12:00 AM 03/25/2014
Misc
Corrective Action Required
03/25/2014
-FIRE DEPARTMENT APPROVAL REQUIRED FOR FULL CofO
Occupancy Inspection - Fire Temporary C of O 3/25/2014 at 12:00 AM 03/25/2014
Misc
Corrective Action Required
03/25/2014
-alarm system showing sprinkler tamper alarm - label the door for the sprinkler room to say "sprinkler room"
Occupancy Inspection - Fire Passed 3/25/2014 at 12:00 AM 03/25/2014
Misc
Corrective Action Required
03/25/2014
-alarm system showing sprinkler tamper alarm - label the door for the sprinkler room to say "sprinkler room"
Occupancy Inspection - Codes Commercial Full C of O 3/25/2014 at 12:00 AM 03/25/2014
Misc
Resolved
03/25/2014
-FIRE DEPARTMENT APPROVAL REQUIRED FOR FULL CofO
Documents & Images
Date Uploaded File Type Document Name
09/30/2013 Letter Fire Building Plan Review
10/07/2013 Letter Codes Plan Review Conditions
11/04/2013 Letter Fire (Sprinkler) Plan Review
11/14/2013 Letter Fire Building Plan Review
11/18/2013 Letter Codes Plan Review Conditions
11/25/2013 Letter Fire Building Plan Review
11/25/2013 Letter Codes Plan Review Conditions
11/26/2013 Letter Codes Building Permit
12/03/2013 Letter Inspection Summary
12/06/2013 Letter Inspection Summary
12/09/2013 Letter Inspection Summary
12/18/2013 Letter Fire (Alarm) Plan Review Notice
02/12/2014 Letter Inspection Summary
03/25/2014 Letter Codes Temporary Certificate of Occupancy
03/25/2014 Letter Field Certificate of Occupancy
03/26/2014 Letter Codes Final Certificate of Occupancy
04/04/2014 Letter Fire Loss Reduction Form
04/04/2014 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home