Permit Application Status

PRCOM20131297


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20131297
Building Permit - Commercial
Certificate of Occupancy
TOP STAR LLC
NEW TENANT FINISH
TENANT FINISH
06/21/2013
07/09/2013
12/30/2013
10/09/2013
Locations
Contacts
DEV INC, Address:8807 MONROVIA ST, Phone:(913) 322-8882  
TEMP-CON LLC, Address:15670 S KEELER ST, Phone:(913) 768-4888  
SHAW ELECTRIC COMPANY, Address:3600 FULLER, Phone:(816) 921-0033  
CORLESS MECHANICAL INC, Address:26020 S SKYLINE DR, Phone:(816) 380-4448  
DEV INC, Address:8807 MONROVIA ST, Phone:(913) 322-8882  
TOP STAR LLC, Address:244 W MILL STE 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/10/2013
Brian Austerman
Misc
Corrective Action Required
07/10/2013

Plans received 7-9-13, released for construction 7-10-13
Building Plan Review Approved 07/15/2013 07/08/2013
Mike Weisenborn
Accessibility - Water closet - Grab bars
Resolved
07/08/2013

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - Provide details on the plans.
Accessibility - Water closet - Clearance around
Resolved
07/08/2013

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - Show clearance on the plans.
Accessibility - Water closet - Clearance overlap
Resolved
07/08/2013

ICC/ANSI A117.1 2003 604.3.2 - Overlap. The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, paper dispensers, sanitary napkin receptacles, coat hooks, shelves, accessible routes, clear floor space at other fixtures and the turning space. No other fixtures or obstructions shall be within the required water closet clearance. Action required - The sink is currantly located in the required clear space. Make needed corrections.
Accessibility - Lavatories and sinks - Clear floor space
Resolved
07/08/2013

ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - The height of the breakroom sink is 34" maximum to rim of the sink or the countertop, whichever is higher. Provide additional information on the plans.
Bldg - Toilet rooms - Walls
Resolved
07/08/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, non absorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - Paint in this area must be an epoxy paint. Make needed corrections.
Plumb - Separate facilities
Resolved
07/08/2013

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Please label on the plans.
Plumb - Minimum number of fixtures
Resolved
07/08/2013

2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required - A service sink is required for this project due to the amount of washable floor surface. Make needed corrections.
Misc
Resolved
07/08/2013

The plans do not provide any specs on the electrical installation. Action required - Provide additional information.
Licensed Contractors Approved 12/30/2013 07/08/2013
Mike Weisenborn
Business License
Resolved
07/08/2013

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. Either a Class A or B license is required. This information is required for permit approval.
Fire Plan Review Approved with Conditions 07/05/2013
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
07/05/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval if modifications are made
Construction documents for fire alarm systems
Corrective Action Required
07/05/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval if modifications are made to the alarm system
Portable fire extinguishers - general
Corrective Action Required
07/05/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 2A10B:C extinguisher for ecvery 3,000 sq/ft Location shown on resub
Building Plan Review Rejected 07/03/2013 07/03/2013
Mike Weisenborn
Accessibility - Water closet - Grab bars
Corrective Action Required
07/03/2013

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - Provide details on the plans.
Accessibility - Water closet - Clearance around
Corrective Action Required
07/03/2013

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - Show clearance on the plans.
Accessibility - Water closet - Clearance overlap
Corrective Action Required
07/03/2013

ICC/ANSI A117.1 2003 604.3.2 - Overlap. The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, paper dispensers, sanitary napkin receptacles, coat hooks, shelves, accessible routes, clear floor space at other fixtures and the turning space. No other fixtures or obstructions shall be within the required water closet clearance. Action required - The sink is currantly located in the required clear space. Make needed corrections.
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
07/03/2013

ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - The height of the breakroom sink is 34" maximum to rim of the sink or the countertop, whichever is higher. Provide additional information on the plans.
Bldg - Toilet rooms - Walls
Corrective Action Required
07/03/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, non absorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - Paint in this area must be an epoxy paint. Make needed corrections.
Plumb - Separate facilities
Corrective Action Required
07/03/2013

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Please label on the plans.
Plumb - Minimum number of fixtures
Corrective Action Required
07/03/2013

2006 IPC 403.1 - Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. Types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code. Action required - A service sink is required for this project due to the amount of washable floor surface. Make needed corrections.
Misc
Corrective Action Required
07/03/2013

The plans do not provide any specs on the electrical installation. Action required - Provide additional information.
Fire Plan Review Approved with Conditions 07/03/2013 06/25/2013
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
06/25/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval if modifications are made
Construction documents for fire alarm systems
Corrective Action Required
06/25/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval if modifications are made to the alarm system
Portable fire extinguishers - general
Corrective Action Required
06/25/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 2A10B:C extinguisher for ecvery 3,000 sq/ft
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $308.07 $308.07 Paid 07/09/2013
$308.07
8331506-EFHB Maybrook, Full $213.05 $213.05 Paid 07/09/2013
$213.05
8331507-Sewer Connection Fee $150.00 $150.00 Paid 07/09/2013
$150.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 7/11/2013 at 12:00 AM 07/11/2013
In-wall Inspection Passed 7/11/2013 at 12:00 AM 07/11/2013
Above Ceiling Inspection Failed 7/26/2013 7/26/2013 at 12:00 AM 07/26/2013
Misc
Corrective Action Required
07/26/2013
-COMPLETE INSTALLATION OF WATER HEATER (BOTH PLUMBING AND ELECTRICAL) -ALL ABOVE CEILING PVC VENT LINES SHALL BE WRAPPED WITH LISTED WRAPPING. EXPOSED OSB SHEATHING AT NORTH SIDE OF BUILDING. EXPOSED MATERIAL IN PLENUM SHALL BE NON-COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND SMOKE DEVELOPE INDEX OF NOT MORE THAN 50.
Above Ceiling Inspection Failed 7/29/2013 at 12:00 AM 07/29/2013
Misc
Corrective Action Required
07/26/2013
-COMPLETE INSTALLATION OF WATER HEATER. -THE PVC STORM DRAINE SHALL BE WRAPPED WITH LISTED WRAPPING. EXPOSED OSB SHEATHING AT NORTH SIDE OF BUILDING. EXPOSED MATERIAL IN PLENUM SHALL BE NON-COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND SMOKE DEVELOPE INDEX OF NOT MORE THAN 50. *IMC 602.2.1
Alarm Test Passed 8/2/2013 at 11:00 AM 08/02/2013
Occupancy Inspection - Fire Temporary C of O 8/2/2013 at 12:00 AM 08/02/2013
Misc
Corrective Action Required
08/02/2013
address rear door with the numeric address of 5008 remove the 5012 from side door mount (1) 2A-10BC fire extinguisher on a wall close to exit with top of the extinguisher no higher than 60" from the floor
Above Ceiling Inspection Passed 08/02/2013
Misc
Resolved
08/02/2013
-COMPLETE INSTALLATION OF WATER HEATER. -THE PVC STORM DRAINE SHALL BE WRAPPED WITH LISTED WRAPPING. EXPOSED OSB SHEATHING AT NORTH SIDE OF BUILDING. EXPOSED MATERIAL IN PLENUM SHALL BE NON-COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND SMOKE DEVELOPE INDEX OF NOT MORE THAN 50. *IMC 602.2.1
Occupancy Inspection - Codes Commercial Temporary C of O 8/2/2013 8/2/2013 at 12:00 AM 08/02/2013
Misc
Corrective Action Required
08/02/2013
-COMPLETE FIRE DEPARTMENT LIST -COMPLETE DEDICATED 20 AMP CIRCUIT OF SIGNAGES -POSTED NO-SMOKING SIGNAGE AT ENTRANCE -INSTALL SIGNAGE FOR RESTROOMS
Occupancy Inspection - Fire Passed 8/8/2013 at 12:00 AM 08/08/2013
Occupancy Inspection - Codes Commercial Full C of O 10/9/2013 at 12:00 AM 10/09/2013
Misc
Resolved
10/09/2013
-COMPLETE FIRE DEPARTMENT LIST -COMPLETE DEDICATED 20 AMP CIRCUIT OF SIGNAGES -POSTED NO-SMOKING SIGNAGE AT ENTRANCE -INSTALL SIGNAGE FOR RESTROOMS
Documents & Images
Date Uploaded File Type Document Name
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
07/03/2013 Letter Plan Review Conditions
07/08/2013 Letter Fire Building Plan Review
07/08/2013 Letter Plan Review Conditions
07/09/2013 Letter Building Permit
07/11/2013 Letter Inspection Summary
07/23/2013 Letter Fire (Sprinkler) Plan Review
07/26/2013 Letter Inspection Summary
07/29/2013 Letter Inspection Summary
08/02/2013 Letter Fire Loss Reduction Form
08/02/2013 Letter Codes Temporary Certificate of Occupancy
10/09/2013 Letter Field Certificate of Occupancy
10/10/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home