Permit Application Status

PRCOM20131076


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20131076
Building Permit - Commercial
Certificate of Occupancy
ROCKY TOP HOLDINGS LLC
NEW TENANT FINISH
FULL CHANGE OF TENANT
05/30/2013
06/24/2013
12/08/2013
09/16/2013
Locations
Contacts
PHOENIX CONSTRUCTION INC, Address:1305 HOLLY CT, Phone:(816) 716-8208  
OLIPHANTS HEATING & COOLING, Address:208 WOLLARD BLVD  
BRADLEY-READE INC, Address:810 W 7TH AVE, Phone:(816) 898-2947  
MAYES PLUMBING INC, Address:501 S MCCLEARY RD STE A, Phone:(816) 792-5400  
SCHARHAG ARCHITECTS, Address:310 ARMOUR RD #202, Phone:(816) 221-9297  
ROCKY TOP HOLDINGS LLC, Address:244 W MILL ST STE 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 07/29/2013
Jim Eden
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/29/2013

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have documentation of a current annual inspection. Verified at inspection.
Installation acceptance testing
Corrective Action Required
07/29/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at the tenant finish inspection.
Construction documents - Fire protection systems
Corrective Action Required
07/29/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Receieved July 27, 2013.
Licensed Contractors Approved 12/08/2013 06/24/2013
Codes Admin
Business License
Corrective Action Required
06/11/2013

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. Either a Class A or B license is required. This information is required for permit approval.
License contractors
Corrective Action Required
06/11/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval.
Building Plan Review Approved 06/18/2013 06/12/2013
Mike Weisenborn
Misc
Resolved
06/12/2013

This building is addressed on Akin Dr and not Ralph Powell Rd as indicated on the application and plans. Action required - This comment is for information purposes.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Carried Forward
06/12/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - To be verified on inspection.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
06/12/2013

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Plumb - Water closet general clearance
Resolved
06/12/2013

2006 IPC 405.3.1 - Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches from its center to any side wall, partition, vanity or other obstruction, or closer than 30 inches center-to-center between adjacent fixtures. There shall be at least a 21-inch clearance in front of the water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less than 30 inches wide and 60 inches deep. Action required - The non-accessible water closet compartment in the womens restroom does not meet this requirement. Make needed corrections.
Fire Plan Review Approved with Conditions 06/18/2013 06/11/2013
Brian Austerman
Address numbers required
Corrective Action Required
06/11/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on all exterior doors including suite number. Verify address, plans show it addressed off of Ralph Powell, however the city's system is showing it as Akin Drive Addressed in resub
Portable fire extinguishers - general
Corrective Action Required
06/11/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 2A10B:C extinguisher for every 3000 sq/ft or every 75' travel distance. Verified at inspection Addressed in resub
Construction documents - Fire protection systems
Corrective Action Required
06/11/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Continued Provide sprinkler plans for approval is modifications are required
Construction documents for fire alarm systems
Corrective Action Required
06/11/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval if modifications are required Continued
Building Plan Review Rejected 06/11/2013 06/11/2013
Mike Weisenborn
Misc
Corrective Action Required
06/11/2013

This building is addressed on Akin Dr and not Ralph Powell Rd as indicated on the application and plans. Action required - This comment is for information purposes.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
06/11/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Provide additional information on the plans.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
06/11/2013

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Plumb - Water closet general clearance
Corrective Action Required
06/11/2013

2006 IPC 405.3.1 - Water closets, urinals, lavatories and bidets. A water closet, urinal, lavatory or bidet shall not be set closer than 15 inches from its center to any side wall, partition, vanity or other obstruction, or closer than 30 inches center-to-center between adjacent fixtures. There shall be at least a 21-inch clearance in front of the water closet, urinal, lavatory or bidet to any wall, fixture or door. Water closet compartments shall not be less than 30 inches wide and 60 inches deep. Action required - The non-accessible water closet compartment in the womens restroom does not meet this requirement. Make needed corrections.
Fire Plan Review Approved with Conditions 06/11/2013 06/03/2013
Brian Austerman
Address numbers required
Corrective Action Required
06/03/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on all exterior doors including suite number. Verify address, plans show it addressed off of Ralph Powell, however the city's system is showing it as Akin Drive
Portable fire extinguishers - general
Corrective Action Required
06/03/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 2A10B:C extinguisher for every 3000 sq/ft or every 75' travel distance. Verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
06/03/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval is modifications are required
Construction documents for fire alarm systems
Corrective Action Required
06/03/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval if modifications are required
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $549.50 $549.50 Paid 06/24/2013
$549.50
8331507-Sewer Connection Fee $270.00 $270.00 Paid 06/24/2013
$270.00
8331506-EFHB Maybrook, Full $383.49 $383.49 Paid 06/24/2013
$383.49
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 6/26/2013 6/26/2013 at 12:00 AM 06/26/2013
Electrical Service Inspection Partial 6/26/2013 6/26/2013 at 12:00 AM 06/26/2013
Misc
Corrective Action Required
06/26/2013
PARTIAL ELECTRICAL SERVICE-OK TO RELEASE METER TO UNIT 136 PANEL
In-wall Inspection Failed 7/2/2013 7/2/2013 at 12:00 AM 07/02/2013
Misc
Corrective Action Required
07/02/2013
-PROTECT PLUMBING WHERE INSTALLED WITHIN 1.5" OF STUD/TRACK SURFACE
Electrical Service Inspection Passed 7/2/2013 7/2/2013 at 12:00 AM 07/02/2013
Misc
Resolved
07/02/2013
OK TO RELEASE METER TO PANEL 136 AND 138
In-wall Inspection Failed 7/3/2013 at 12:00 AM 07/03/2013
Misc
Corrective Action Required
07/03/2013
-PROTECT PLUMBING WHERE INSTALLED WITHIN 1.5" OF STUD/TRACK SURFACE
In-wall Inspection Passed 7/5/2013 at 12:00 AM 07/05/2013
Misc
Resolved
07/05/2013
-PROTECT PLUMBING WHERE INSTALLED WITHIN 1.5" OF STUD/TRACK SURFACE
Above Ceiling Inspection Failed 8/15/2013 8/15/2013 at 12:00 AM 08/15/2013
Misc
Corrective Action Required
08/15/2013
-HVAC NOT COMPLETED -VENT BATHFANS TO OUTSIDE
Above Ceiling Inspection Passed 8/21/2013 8/21/2013 at 12:00 AM 08/21/2013
Misc
Resolved
08/21/2013
-HVAC NOT COMPLETED -VENT BATHFANS TO OUTSIDE
Occupancy Inspection - Codes Commercial Temporary C of O 8/28/2013 8/28/2013 at 12:00 AM 08/28/2013
Misc
Corrective Action Required
08/28/2013
PER ICC/ANSI A117.1 SECTION 604.6: WATER CLOSET FLUSH VALVE HANDLE MUST BE AT FREE SIDE OF TANK. SEE MEN'S W.C.
Misc
Corrective Action Required
08/28/2013
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF. SEE AT WOMEN'S RR
Misc
Corrective Action Required
08/28/2013
ADDRESS LABELING OF GAS SERVICE ENTRY PIPE: AFFIX PERMANENT TAG/LABEL TO ENTRY PIPE. FELT TIP MARKER NOT APPROVABLE.
Misc
Corrective Action Required
08/28/2013
DESIGNATE MULTIPLE ELECTRICAL SERVICE PANELS. ALSO LABEL ALL OCCUPIED CIRCUIT BREAKER POSITIONS RE LOADS SERVED.
Occupancy Inspection - Fire Temporary C of O 8/28/2013 at 12:00 AM 08/28/2013
Misc
Corrective Action Required
08/28/2013
-post the numeric address on all front and rear doors leading into occupant space to be the same - 140 - add alarm notification to the occupant space - label the rear door on the exterior which has been walled over to say " this door blocked" - key for sprinkler room access to be placed in the knox box
Alarm Test Passed 9/16/2013 at 8:30 AM 09/16/2013
Occupancy Inspection - Fire Passed 9/16/2013 at 12:00 AM 09/16/2013
Misc
Corrective Action Required
08/28/2013
-post the numeric address on all front and rear doors leading into occupant space to be the same - 140 - add alarm notification to the occupant space - label the rear door on the exterior which has been walled over to say " this door blocked" - key for sprinkler room access to be placed in the knox box
Occupancy Inspection - Codes Commercial Full C of O 9/16/2013 9/16/2013 at 12:00 AM 09/16/2013
Misc
Resolved
09/16/2013
PER ICC/ANSI A117.1 SECTION 604.6: WATER CLOSET FLUSH VALVE HANDLE MUST BE AT FREE SIDE OF TANK. SEE MEN'S W.C.
Misc
Resolved
09/16/2013
ANSI 603.3 MOUNTING OF MIRRORS AT ACCESSIBLE RESTROOMS: SET BOTTOM OF VIEWING SURFACE <= 40" AFF. SEE AT WOMEN'S RR
Misc
Resolved
09/16/2013
ADDRESS LABELING OF GAS SERVICE ENTRY PIPE: AFFIX PERMANENT TAG/LABEL TO ENTRY PIPE. FELT TIP MARKER NOT APPROVABLE.
Misc
Resolved
09/16/2013
DESIGNATE MULTIPLE ELECTRICAL SERVICE PANELS. ALSO LABEL ALL OCCUPIED CIRCUIT BREAKER POSITIONS RE LOADS SERVED.
Documents & Images
Date Uploaded File Type Document Name
06/11/2013 Letter Plan Review Conditions
06/24/2013 Letter Building Permit
06/24/2013 Letter Plan Review Conditions
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
06/26/2013 Letter Inspection Summary
07/02/2013 Letter Inspection Summary
07/03/2013 Letter Inspection Summary
07/03/2013 Letter Inspection Summary
07/05/2013 Letter Inspection Summary
08/05/2013 Letter Fire (Sprinkler) Plan Review
08/15/2013 Letter Inspection Summary
08/21/2013 Letter Inspection Summary
08/28/2013 Letter Codes Temporary Certificate of Occupancy
08/28/2013 Letter Fire Loss Reduction Form
09/16/2013 Letter Field Certificate of Occupancy
09/17/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home